FFI SYSTEM
OPTICAL-PNEUMATIC CONVERTER
DATA SHEET
The optical-pneumatic converter is used to convert optical signal from master station, etc. to pneumatic signal (0.2 to 1.0kg/cm 2 e tc.). It is installed in site when operating pneumatic final control element such as pneumatic positioner or diaphragm valve. Signals are processed in digital mode with built-in microcomputer, providing high accuracy and intelligent performance, adoption of piezo-electric element (flapper) has realized low-power operation. This instrument is φ6 mm optical fiber cable connection type.
ZLD
SPECIFICATIONS
Functional specifications
Input signal: FFI system optical digital signal Output signal and air supply pressure:
Output signal 19.6 to 98.1kPa {0.2 to 1.0kgf/cm2} 39.2 to 196.1kPa {0.4 to 2.0kgf/cm2) 3 to 15psi 3 to 27psi 6 to 30psi Air supply pressure 140kPa {1.43kgf/cm2} 240kPa {2.45kgf/cm2} 20± 1psi 32± 1psi 35± 1psi
Power supply: Self-diagnosis:
Built-in lithium battery (expected life; about 2 years/cell) Indication on display unit (option) and transmission to host master station
HHC, MS (*1) Indication
Item Battery voltage Converter temperature Abnormal output (*2) Battery voltage drop
Ambient humidity: 0 to 95% RH Transmission: Half-duplex bidirectional optical transmission with one-line optical fiber Transmission distance; 1.2 km max. (free from effect of noise and surge)
Performance specifications
± 0.5% of full scale (output ripple; about ± 0.1%) Response speed: 1.5 to 2.5 sec (90% response time at load capacity 0.5 r ) Input/output characteristic: Linear Standard air consumption: 12Nr/min.(at air supply pressure 140kPa {1.43kgf/cm 2}) 20Nr/min.(at air supply pressure 240kPa {2.45kgf/cm 2}) Maximum air flow: 60Nr/min.(at air supply pressure 140kPa {1.43kgf/cm 2}) 80Nr/min.(at air supply pressure 240kPa {2.45kgf/cm 2}) Accuracy:
Notes: *( 1) HHC: Hand-held communication MS: Master station ( 2) Output overflow or large offset
Emergency operation: In case of emergency (abnormal input), output operation can be select from remote setting unit (HHC, MS), as specified. • Output; Less than –10% • Output; more than +110% Explosion proofing: Intrinisically safety (JIS i3nG5, safety barriers not required) Ambient temperature: –20 to +60 ° C Storage temperature: –30 to +70 ° C
EDS9-47c
Date Jul. 31, 1994
ZLD
Structure and material
Enclosure: JIS C0920, splash-proof type (equivalent to IEC IP54) Finish color: Epoxy/polyurethane double coating, silver (Case cover ...... blue) External dimension (HxWxD): 257 x 165 x 220 mm Mass (weight} Approx. 5 kg Mounting method: Mounted on 50A (2B) pipe with U-bolt Optical cable and connection: Fuji’s specified optical cable (supplied as separate item) Connection; Optical connector is used. Air piping connection: Rc 1/4 (PT 1/4) 1/4-18NPT as specified
CODE SYMBOLS
12345678 9 11 12 13
ZLD 1 2 3 4 5 A B B C
1-
Description Output signal and supply pressure 19.6 to 98.1 kPa {0.2 to 1 .0kgf/cm2} (140kPa {1.43kgf/cm2}) 39.2 to 196.1kPa {0.4 to 2.0kgf/cm2} (240kPa {2.45kgf/cm2}) 3 to 15psi (20psi) 6 to 30psi (35psi) 3 to 27psi (32psi) Air piping connection Rc 1/4 (PT 1/4) 1/4-18 NPT 6 optical cable protection adapter With Without Notes: 9 mm optical cable connection type: manufacture non-standard Display unit and output pressure gauge Output pressure Display unit gauge – – – (output % scale) – (output % scale) – (output % scale) (output % scale) Explosion-proof specification Standard (non-explosion-proof) Intrinsic safety explosion-proof (JIS i3nG5) Emergency operation (at abnormal input) Scale out to less than -10% output Scale out to more than 110% output Y B Treatment Standard (non acid/alkali-proof) Acid/alkali-proof treatment Number of built-in lithium batteries One Two
Additional specifications
Indicator ....LCD, 4 digits (–10°C to +60°C) Setting unit .... Pushbutton switch (4 switches) Output pressure gauge: JIS Class-3 Scale; 0 to 2kgf/cm2 or 0 to 3 kgf/cm2 (depends on output range) Lithium battery (2 batteries, built-in): Changed over by internal select switch. [Two batteries can be built into the housing (standard specification)] Acid/alkali-proofing: Mounting U-bolts, nuts and washers; Stainless steel (304 stainless steel) Display unit:
A B C D E F
0 1
B C
1 2
SYSTEM CONFIGURATION DIAGRAMS
Pneumatic operation final element Optical-pneumatic converter ZLD P/P SUP 8 pcs. SUP O/P
Optical star coupler FXQ
Master station
OUTLINE DIAGRAM
(Unit:mm)
Mounting pipe (JIS 2B)
108 70
U-bolt (M8)
50
Display unit (option)
70
ø122
Approx. 245
112
OUT SUP
76
Approx. 196 62
Optical connector connection M42 screw thread 4.8 depth
45
165
Air piping connection (Rc 1/4)
With optical protection adapter
Adapter 1/2-14NPT (option)
SCOPE OF DELIVERY
Converter (excluding the optical items), U-bolt.
RELATED DEVICES
• • • • Optical star couple (Data sheet No. EDS 8–48) HHC (Data sheet No. EDS 8-44) Master station (Data sheet No. EDS 11–86) Option connector, cable
ORDERING INFORMATION
1. Product name 2. Code symbols 3. Other necessary items
121
76
56
ZLD
Caution on Safety *Before using this product, be sure to read its instruction manual in advance.
Head Office
6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan http://www.fesys.co.jp/eng
Sales Div. International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http: //www.fic-net.jp/eng
Information in this catalog is subject to change without notice.
Printed in Japan