FFI SYSTEM
OPTICAL-PNEUMATIC POSITIONER
DATA SHEET
This instrument converts the optical signal from a master station or the like into a pneumatic signal (0.2 to 1.0 kgf/cm 2, etc.) in order to drive a diaphragm type control valve. The operating position of the valve is fed back via link to this positioner to enable accurate positioning. A built-in microcomputer provides intelligent digital processing of signals with a high precision, and the use of a piezoelectric element flapper makes for a low power consumption. This articles are φ6mm optical fiber cable connection type.
ZLF
SPECIFICATIONS
Functional specifications
Input signal: FFI system optical digital signal Operating air pressure, supply air pressure:
Operating air pressure 19.6 to 98.1kPa {0.2 to 1.0kgf/cm2} 39.2 to 196.1kPa {0.2 to 2.0kgf/cm2) 3 to 15psi 3 to 27psi 6 to 30psi Supply air pressure 140kPa {1.43kgf/cm2} 240kPa {2.45kgf/cm2} 20± 1psi 32± 1psi 35± 1psi
Power supply: Self-diagnosis:
Built-in lithium battery (single battery lasts about 2 years) Diagnosis results can be displayed on optional indicator unit and also transmitted to master station.
Contents Battery voltage Output failure (*2) Battery voltage drop Notes: *( 1) HHC: hand-held communicator, MS: master station ( 2) When output overflows, or offset is large HHC, MS (*1) Indication
Ambient humidity: 0 to 95%RH Transmission: Half-duplex bidirectional optical transmission system using single optical fiber cable Transmission distance; 1.2km max. (not affected by noise, surge or the like) Applicable valve: Diaphragm control valve with top diameter of φ240 or more; stroke 10 to 90mm (feedback lever rotating angle 10 to 30 °)
Performance specifications
Accuracy rating: ± 1.0% of full scale (output ripple approx. ± 0.2%) Response speed: Approx. 4 seconds (for 90% response) (with control valve having top diameter φ240 and lift of 16mm) Input/output characteristic: Linear Reference air consumption: 12N r /min (at supply air pressure of 140kPa {1.43kgf/cm2} 20N r /min (at supply air pressure of 240kPa {2.45kgf/cm2} Maximum air supply/discharge flow rate: 60N r /min (at supply air pressure of 140kPa {1.43kgf/cm2} 80N r /min (at supply air pressure of 240kPa {2.45kgf/cm2}
Operation at emergency: Output operation is settable by remote means (HHC, MS) in an emergency (when input fails) (available on request). • Holding of output value just before failure • Scale-out of set value below 0% • Scale-out of set value above 100% Explosionproofing: JIS i3nG5, unnecessary for safety-barrier Ambient temperature: –20 to +60 °C (–10 to +60 °C for indicator unit) Storage temperature: –30 to +70 ° C
EDS9-50b
Date Jul. 31, 1994
ZLF
Structure, materials
Enclosure structure: JIS C0920, splash-proof (equivalent to IEC IP54) Finish: Epoxy/polyurethane double coating, silver (casing cover ..... blue) Outer dimensions (H x W x D): 257 x 165 x 220mm Mass {weight} Approx. 5kg Mounting method: On control valve yoke section Three sizes, small, medium and large, or links and clamps are available for mounting on valve stem. Optical cable and connection method: Fuji's designated optical cable (to be purchased separately). Connection is made by optical connector. Air piping connection: Rc 1/4 (PT1/4); 1/4–18NPT available on request
Optional specifications
Indicator unit: Indicating section; 4 digit LCD (–10 to +60 ° C) Setting section; 4 pushbutton switches Output pressure gauge: JIS Class 3: 0 to 2 or 0 to 3kgf/cm 2 scale (depends on output range) Two built-in lithium batteries: Changed over by internal selector switch (standard specification allows accommodating two batteries) Acid/alkali-proof treatment: 304 stainless steel for bolts and washers
SYSTEM CONFIGURATION DIAGRAM
Pneumatic type controlled device
O/P positioner SUP
Optical star coupler FXQ
Master station
8 lines
CODE SYMBOLS
12345678 9 10 11 12 13
ZLF
1Operating air pressure 19.6 to 98.1kPa {0.2 to 1.0kgf/cm2} 39.2 to 196.1kPa {0.4 to 2.0kgf/cm2} 3 to 15psi 6 to 30psi 3 to 27psi 98.1 to 19.6kPa {1.0 to 0.2kgf/cm2} 196.1 to 39.2kPa {2.0 to 0.4kgf/cm2} 15 to 3psi 30 to 6psi 27 to 3psi A B B C
Description Supply air pressure 140kPa {1.43kgf/cm2} 240kPa {2.45kgf/cm2} 20psi 35psi 32psi 140kPa {1.43kgf/cm2} 240kPa {2.45kgf/cm2} 20psi 35psi 32psi Operation
1 2 3 4 5 6 7 8 9 A
Normal operation(*1)
Reverse operation(*1)
Piping connection Rc 1/4 (PT1/4) 1/4–18NPT 6 optical cable protection adapter
Note: for 9mm connector: non-standard item, on request Indicator unit A B C D 0 1 A B C Y B 1 2 A B C D E F G H Explosionproofing specification General use (non-explosionproof) Intrinsically safe explosionproofing JIS i3nG5 Operation at emergency Holding of output value just before failure Scale-out of set value below 0% Scale-out of set value above 100% Treatment For general use Acid/alkali-proof treatment No. of built-in lithium batteries One Two Link mechanism Valve operation None With small link mechanism Normal With medium link mechanism operation(*2) With large link mechanism None Reverse With small link mechanism operation(*2) With medium link mechanism With large link mechanism pressure gauge
Notes: *(1) Positioner operation • Normal operation: operating air pressure increases with increase of setting single • Reverse operation: operating air pressure decreases with increase of setting single *(2) Valve operation • Normal operation: valve stem lowers with increase of operating air pressure
• Reverse operation: valve stem rises with increase of operating air pressure
ZLF
OUTLINE DIAGRAMS
(Unit:mm)
218 115
12
2-ø11 mounting holes Indicator unit (option)
206 4.5
46
57
ø122
1 0˚ t o 3 0˚
18
88
SUP.
OUT. Air piping connection M42 thread 1 depth 4.8
188
Output pressure gauge (option)
76
Positioner with adapter (option) for optical cable protection
13
Link mechanism ( B, C, D, F, G, H )
22 90
56
Valve stem
76
121
L1
19
66
136
13
5
L1 35 50
L2
16
B,F
Adapter 1/2-14NPT (option)
30
6.2
C,G
55 55
D,H 112
SCOPE OF DELIVERY
Positioner and mounting bracket
RELATED DEVICES
• • • • Optical star coupler (Data sheet No. EDS8-48) HHC (Data sheet No. EDS 8–44) Master station (Data sheet No. EDS 11–86) Optical connector, Cable
ORDERING INFORMATION
1. Product name 2. Type 3. Other necessary items
Caution on Safety *Before using this product, be sure to read its instruction manual in advance.
Head Office
6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan http://www.fesys.co.jp/eng
Sales Div. International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http: //www.fic-net.jp/eng
Information in this catalog is subject to change without notice.
L2
Printed in Japan