FCX – C2
DATA SHEET
PRESSURE TRANSMITTER
FKP...4
The FCX –C 2 p ressure transmitter accurately measures gauge pressure and transmits proportional 4 to 20mA signal. The transmitter utilizes the unique micromachined capacitive silicon sensor with state-of-the-art microprocessor technology to provide exceptional performance and functionality.
FEATURES
1. High accuracy ± 0.1% 0.1% accuracy is a standard feature. Fuji’s micro-capacitance silicon sensor assures this accuracy for all elevated or suppressed calibration ranges without additional adjustment. 2. Minimum environmental influence The “Advance Floating Cell” design which protects the pressure sensor against changes in temperature, and overpressure substantially reduces total measurement error in actual field applications. 3. Fuji/HART ® b ilingual communications protocol and FOUNDATION™ fieldbus and Profibus™ compatibility FCX–C2 series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART®. Any HART® compatible devices can communicate with FCX–C2 . Further, by upgrading electronics FOUNDATION™ fieldbus and Profibus™ are also available. 4. Application flexibility Various options that render the FCX – C2 suitable for almost any process applications include: – Analog indicator at either the electronics side or terminal side – Full range of hazardous area approvals – Built-in RFI filter and lightning arrester – 5-digit LCD meter with engineering unit 5. Burnout current flexibility (Under Scale: 3.2 to 3.8mA, Over Scale: 20.8 to 21.6mA) Burnout signal level is adjustable using Model FXW Hand Held Communicator (HHC) to comply with NAMUR NE43. 6. Dry calibration without reference pressure Thanks to the best combination of unique construction of mechanical parts (Sensor unit) and high performance electronics circuit (Electronics unit), reliability of dry calibration without reference pressure is at equal level as wet calibration.
SPECIFICATIONS
Functional specifications
Service: Liquid, gas, or vapour Span, range and overrange limit:
Span limit [kPa] {bar} Type Min. FKP□01 FKP□02 FKP□03 FKP□04 8.125 {0.08125} 31.25 {0.3125} 187.5 {1.875} 625 {6.25} Max. 130 {1.3} 500 {5} 3000 {30} 10000 {100} Range limit [kPa] {bar} –100 to +130 {–1 to +1.3} –100 to +500 {–1 to +5} –100 to +3000 {–1 to +30} –100 to +10000 {–1 to + 100} Overrange limit [MPa] {bar} 1 {10} 1.5 {15} 9 {90} 15 {150}
— Lower range limit (vacuum limit) is; Silicone fill sensor: See Fig. 1 Fluorinated fill sensor: 66kPa abs (500mmHg abs) at below 80°C — Conversion factors to different units; 1 MPa=103 KPa=10bar=10.19716kgf/cm2= 145.0377psi 1KPa=10mbar=101.9716mmH2O =4.01463inH2O Output signal: 4 to 20mA DC with digital signal superimposed on the 4 to 20mA signal.
EDSX5-87a
Date Jun. 1, 2006
FKP...4
Power supply: Transmitter operates on 10.5V to 45V DC at transmitter terminals. 10.5V to 32V DC for the units with optional arrester. Load limitations: see figure below
[Ω] 2000
Load resistance
Authorities ATEX
Intrinsic safety Ex II 1 GD EEx ia IIC T5 Tamb = -40°C to +40°C EEx ia IIC T4 Tamb = -40°C to +80°C Entity Parameters: Ui=28V, Ii=93.3mA, Pi=0.66W, Ci=27nF (Without Arrester), Ci=34.2nF (With Arrester), Li=1.134mH
1533Ω
1500 1000 500 250 10
Factory Mutual
600Ω Operating area 24V 16.1 10.5V Power voltage 45V 50 [V]
Class I II III Div.1 Groups A, B, C, D, E, F, G T4 Entity Type 4X Model code 13th digit 9th digit A,B,D L,P,1,2 Q,S,4,5 E,F,H Y,G,N Y,G,N Y,G,N Y,G,N A Tamb -40°C to +85°C -20°C to +80°C -20°C to +60°C -40°C to +60°C -10°C to +60°C
Note: For communication with HHC (1) ( Model: FXW), min. of 250 Ω required.
Entity Parameters: Vmax=42.4V, Imax=113mA, Pi=1W, Ci=34.2nF, Li=1.134mH CSA Class I Div.1 Groups A, B, C, D Class II Div.1 Groups E, F, G Class III Div.1 Temp Code T4 Tamb max = +40°C Temp Code T3C Tamb max = +85°C Entity Parameters: Vmax=28V, Imax=93mA, Ci=27nF (Without Arrester), Ci=34.2nF (With Arrester), Li=1.4mH Ex ia IIC T4 IP66/67 Tamb = -40°C to +70°C Ex ia IIC T5 IP66/67 Tamb = -40°C to +50°C Entity Parameter: Ui=28V, Ii=93.3mA, Pi=0.66W, Ci=0.033µF, Li=1.034mH
Hazardous locations: (Approval pending)
Authorities ATEX Flameproof Ex II 2 GD EEx d IIC T6 IP66/67 T85°C Tamb = -40°C to +65°C EEx d IIC T5 IP66/67 T100°C Tamb = -40°C to +85°C Class I Div.1 Groups B, C, D T6 Type 4X Class II III Div.1 Groups E, F, G T6 Type 4X Tamb max = +60°C Class I Div.1 Groups C, D Class II Div.1 Groups E, F, G Class III Div.1 Note) “Seal Not Required” enclosure is allowed. IECEx Scheme /SAA Ex d IIC T5 IP66/67 pending Tamb = -40°C to +85°C Ex d IIC T6 IP66/67 pending Tamb = -40°C to +65°C
Factory Mutual
IECEx Scheme /SAA
CSA
2
Authorities ATEX
Type n Nonincendive Ex II 3 GD EEx nL IIC T5 Tamb = -40°C to +40°C EEx nL IIC T4 Tamb = -40°C to +80°C Specific Parameters: Model without arrester: Ui=42.4V, Ii=113mA, Pi=1W, Ci=27nF, Li=1.134mH Model with arrester: Ui=32V, Ii=113mA, Pi=1W, Ci=34.2nF, Li=1.134mH EEx nAL IIC T5 Tamb = -40°C to +40°C EEx nAL IIC T4 Tamb = -40°C to +80°C Specific Parameters: Model without arrester: Umax=42.4V, Imax=113mA, Pmax=1W, Model with arrester: Umax=32V, Imax=113mA, Pmax=1W
“Output Underscale”: Adjustable within the range 3.2mA to 3.8mA from HHC
3.2 3.8 4 20 20.8 21.6 [mA] Over scale Burnout Normal operating range Under scale Probable under range Burnout (Note) (1) HHC: Hand Held Communicator Probable over range
Factory Mutual
Class I II III Div.2 Groups A, B, C, D, F, G T4 Entity Type 4X Model code 13th digit 9th digit A,B,D L,P,1,2 Q,S,4,5 E,F,H Y,G,N Y,G,N Y,G,N Y,G,N A Tamb -40°C to +85°C -20°C to +80°C -20°C to +60°C -40°C to +60°C -10°C to +60°C
CSA
Class I Div.2 Groups A, B, C, D Class II Div.2 Groups E, F, G Class III Div.2 Temp Code T4 Tamb max = +40°C Temp Code T3C Tamb max = +85°C Entity Parameters: Vmax=28V, Ci=27nF (Without Arrester), Ci=34.2nF (With Arrester), Li=1.4mH -
IECEx Scheme /SAA
Loop-check output: Transmitter can be configured to provide constant signal 3.8mA through 21.6mA by HHC. Temperature limit: Ambient: – 40 to +85°C (–20 to +80°C for LCD indicator) (– 40 to +60°C for arrester option) (–10 to +60 ° C for fluorinated oil fill transmitter) For explosionproof units (flameproof or intrinsic safety), ambient temperature must be within the limits specified by each standard. Process: – 40 to +100 °C for silicone fill sensor –20 to +80°C for fluorinated oil fill sensor Storage: –40 to +90°C Humidity limit: 0 to 100% RH Communication: With HHC(1) ( Model FXW, consult Data Sheet No. EDS8-47), following information can be remotely displayed or reconfigured. Note: HHC’s version must be more than 6.0 (or FXW 1– 3), for FCXC2.
Items Tag No. Model No. Serial No. Engineering unit Range limit Measuring range Damping Output mode Burnout direction Calibration Output adjust Data Self diagnoses Printer External switch lock Transmitter display Linearize Rerange (Note) Display Set
Zero/span adjustment: Zero and span are adjustable from the HHC(1). Zero and span are also adjustable externally from the adjustment screw (span adjustment not available with 9th digit code “L, P, Q, S”). Damping: Adjustable from HHC or local adjustment unit with LCD display. The time constant is adjustable between 0.12 to 32 seconds. Zero elevation/suppression: Zero can be elevated or suppressed within the specified range limit of each sensor model. Normal/reverse action: Selectable from HHC(1). Indication: Analog indicator or 5-digit LCD meter, as specified. Burnout direction: Selectable from HHC(1) If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale” or “Output Underscale” modes. “Output Hold”: Output signal is hold as the value just before failure happens. “Output Overscale”: Adjustable within the range 20.8mA to 21.6mA from HHC(1)
v v v v v v v v v v — v v — v v v v
v v — v — v v — v v v — — — v v v v
(1) HHC: Hand Held Communicator
3
FKP...4
Performance specifications
Accuracy rating: (including linearity, hysteresis, and repeatability) For spans greater than 1/10 of URL: ± 0.1% of span For spans below 1/10 of URL (Model FKP only): 0.1 x URL ± (0.05 + 0.05 span ) % of span ± 0.1% of upper range limit (URL) for 6 months Temperature effect: Effects per 55°C change between the limits of – 40°C and +85°C Zero shift : URL ± (0.1 )%/28°C span Total effect: URL ± (0.075 + 0.1 span )%/28°C Overrange effect: Zero shift, 0.3% of URL for any overrange to maximum limit Supply voltage effect: Less than 0.05% fo calibrated span per 10V RFI effect: Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength 30 V/m when electronics covers on. (Classification: 2-abc: 0.2% span per SAMA PMC 33.1) Update period: 120 msec Step response: Time constant: 0.2s Dead time: about 0.2s (without electrical damping) Mounting position effect: Zero shift, less than 0.1kPa {1mbar} for a 10° tilt in any plane. No effect on span. This error can be corrected by adjusting zero. (Double the effect for fluorinated fill sensors) Dielectric strength: 500V AC, 50/60Hz 1 min., between circuit and earth Insulation resistance: More than 100MΩ at 500V DC Turn-on time: 4 sec. Internal resistance for external field indicator: 12Ω or less. Stability:
Physical specifications
Electrical connections: G1/2, 1/2-14 NPT, Pg13.5, or M20 ×1.5 conduit, as specified. Process connections: 1/2-14NPT, Rc1/2, Rc1/4 or 1/4-18NPT, as specified. Process-wetted parts material:
Material code (7th digit in Code symbols) V Wetted sensor body
Process cover
Diaphragm
316 stainless steel
316L stainless steel
316 stainless steel
Non-wetted parts material: Electronics housing: Low copper die-cast aluminum alloy (standard), finished with epoxy/polyurethane double coating. Fill fluid: Silicone oil (standard) or fluorinated oil (Daifloil) Mounting bracket: 304 stainless steel Environmental protection: IEC IP67 and NEMA 6/6P Mounting: On 60.5mm (JIS 50A or 2B) pipe using mounting bracket, direct wall mounting, or direct process mounting. Mass{weight}: Transmitter approximately 1.9kg without options. Add; 0.5kg for mounting bracket 0.8kg for indicator option
4
Optional features
A plug-in turnable analog indicator (1.5% accuracy) can be housed in the electronics compartment or in the terminal box of the housing. An optional 5digits LCD meter with engineering unit is also available. Local adjustment unit with LCD display: An optional 5-digit LCD meter with Zero/ Span adjustment function, loop-check function and damping adjustment function, is available. Arrester: A built-in arrester protects the electronics from lightning surges. Lightning surge immunity: 4kV (1.2 x 50 µs) Oxygen service: Special cleaning procedures are followed throughout the process to maintain all process wetted parts oil-free. The fill fluid is fluorinated oil. Degreasing: Process-wetted parts are cleaned, but the fill fluid is standard silicone oil. Not for use for oxygen or chlorine measurement. NACE specification: Metallic materials for all pressure boundary parts comply with NACE MR-01-75. Optional tag plate: An extra stainless steel tag with customer tag data is wired to the transmitter.
Silicone oil (Code:Y,G,N)
ACCESSORIES
Hand-held communicator: (Model FXW, refer to Data Sheet No. EDS8-47) Z/S board: Parts No.=ZZPFCX4-A070 When Z/S board is mounted on the FCX– C 2 a mplifier unit, external adjustment screw will be available for zero and span adjustment.
Indicator:
The product conforms to the requirements of the Electromagnetic compatibility Directive 94/9/EC as detailed within the technical construction file number TN513035. The applicable standards used to demonstrate compliance are : EMI (Emission)
Frequency range MHz 30 to 230 230 to 1000
EN61326 : 1997 Class A (standard for Industrial Location)
Limits 40dB (µV/m) quasi peak, measured at 10m distance 47dB (µV/m) quasi peak, measured at 10m distance Reference standard CISPR16-1 and CISPR16-2
EMI (Immunity)
Phenomenon Electrostatic discharge
EN61326: 1997 Annex A (standard for Industrial Location)
Test value Basic standard IEC61000-4-2 Performance criteria B
4kV (Contact) 8kV (Air)
[kPa abs] (mmHg abs) 101 (760)
Operating pressure
80 to 1000MHz Electromagnetic 10V/m field 80%AM (1kHz) Rated power frequency magnetic field Burst 30A/m 50Hz 2kV 5kHz 1.2µs/50µs 1kV (Line to line) 2kV (Line to ground) 0.15 to 80MHz 3V 80%AM (1kHz)
IEC61000-4-3
A
IEC61000-4-8
A
IEC61000-4-4
B
Operating area 20 (150)
Surge
IEC61000-4-5
B
Conducted RF
4 (30) 2.7 (20) –40
IEC61000-4-6
A
None-operating area 60 100 Process temperature[°C ]
Note) Definition of performance criteria A: During testing, normal performance within the specification limits. B: During testing, temporary degradation, or loss of function or performance which is self-recovering.
Fig. 1 Relation between process temperature and operating pressure
5
FKP...4
CODE SYMBOLS
12345678 9 10 11 12 13 14 15
Digit 4 Process conn.
Description Conduit conn. G1/2 1/2-14NPT Pg 13.5 M20 x 1.5
Note
FKP
0
4
0
Digit No. of code
1/2-14NPT 6
S T V W 1 2 3 4
7
9
10
11
12
13
14
FKP kPa {bar} 8.125 … 130 {0.08125 … 1.3} 31.25 … 500 {0.3125 … 5} 187.5 … 3000 {1.875 … 30} 625 …10000 {6.25 …100} Process cover Diaphragm Wetted cell body 316 stainless steel 316L stainless steel 316 stainless steel Indicator Arrester None None Analog, 0 to 100% linear scale None Z/S board Analog, custom scale None attached. None Yes Analog, 0 to 100% linear scale Yes Analog, custom scale Yes Digital, 0 to 100% linear scale None Digital, custom scale None Digital, 0 to 100% linear scale Yes Digital, custom scale Yes Digital, 0 to 100% (Local adjustment unit with LCD displey) None Digital, Custom scale (Local adjustment unit with LCD displey) None Digital, 0 to 100% (Local adjustment unit with LCD displey) Yes Digital, Custom scale (Local adjustment unit with LCD displey) Yes None (for ordinary locations) FM, Flameproof (or explosionproof) (Available for 4th code "T") CSA Flameproof (or explosionproof) (Available for 4th digit code "T") ATEX, Flameproof IECEx Scheme/SAA, Flameproof (Approval pending) FM, Intrinsic safety and nonincendive CSA Intrinsic safety and nonincendive ATEX, Intrinsic safety ATEX, Type n IECEx Scheme/SAA, Intrinsic safety None Yes (stainless steel) Stainless tag None Yes Treatment Filled liquid None (standard) Silicon oil Degreasing Silicon oil Oxygen service Fluorinated oil NACE specification Silicon oil None (1/2 -14NPT) Rc1/4 Rc1/2 1/4-18NPT
V
A B D E F H L P Q S 1 2 4 5
A D E X R H J K P T A C
Y B
Y G A N Y A B C
6
OUTLINE DIAGRAM (Unit:mm)
FASTENER (IN CASE OF 10TH DIGIT CODE“X”) 2 HOLES 9 DIA. 170 UP
IN CASE OF 4TH DIGIT CODE“S,V,W”
U-BOLT M8
108
Ø80
100
DOWN ZERO/SPAN ADJ. SCREW
10 88 50
“B”
CONDUIT CONN. 196 CABLE GLAND (OPTION) SEE NOTE
MTG. PIPE JIS 50A (2B)
WITH FIELD IND. (OPTION) EARTH TERMINAL (BOTH SIDE) SEE TABLE 1 51 71 (27)
“C”
CONDUIT CONN.
DETAIL “A”
(PRESS. CONN.) Ø18
DETAIL “B”
(CONDUIT CONN.) Ø15
DETAIL “C”
Ø13
Ø80
214
F
16
70
27
G
1/2-14NPT SEE TABLE 1
D SEE TABLE 1
G1/2
“A” PRESS. CONN.
85
DETAIL “D”
4TH DIGIT CONDUIT CONN. CODE EF D S T V G1/2 1/2-14NPT Pg13.5 M20x1.5 17 16 8 5 EARTH TERMINAL M4 M4 M4 M4 L Ø6
“D” ADAPTER (OPTION)
SEE TEBLE2 35
8 4.5 16 5
J
W
TABLE 1 ADAPTER CONN. L G H J Rc1/2 HEXAGON SOCKET HEAD CAP SCREW M4 NPT1/4 Rc1/4
H
K
CONNECTION DIAGRAMS
+ − CK+ CK−
44 31 27 16 14 25 22 8
TABLE 2 NOTE) CABLE GLAND IS SUPPLIED IN CASE OF FLAMEPROOF PACKING TYPE. Ø11 CABLE IS SUITABLE.
K
+
−
17
E
7
FKP...4
Caution on Safety *Before using this product, be sure to read its instruction manual in advance.
Head Office
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fesys.co.jp/eng
Instrumentation Div. International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http://www.fic-net.jp/eng
Information in this catalog is subject to change without notice.
Printed in Japan