PRESSURE TRANSMITTER (DIRECT MOUNT TYPE)
DATA SHEET
The FCX– A III p ressure transmitter accurately measures gauge pressure and transmits proportional 4 to 20mA signal. The transmitter utilizes the unique micromachined capacitive silicon sensor with state-of-the-art microprocessor technology to provide exceptional performance and functionality.
FKP...5
FEATURES
1. High accuracy ±0.1% 0.1% accuracy is a standard feature. Fuji’s micro-capacitance silicon sensor assures this accuracy for all elevated or suppressed calibration ranges without additional adjustment. 2. Minimum environmental influence The “Advance Floating Cell” design which protects the pressure sensor against changes in temperature, and overpressure substantially reduces total measurement error in actual field applications. 3. Fuji/HART® bilingual communications protocol FCX– AIII series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART®. Any HART® compatible devices can communicate with FCX– AIII. 4. Application flexibility V arious options that render the FCX– A III s uitable for almost any process applications include: – Full range of hazardous area approvals – Built-in RFI filter and lightning arrester – 5-digit LCD meter with engineering unit 5. Burnout current flexibility (Under Scale: 3.2 to 4.0mA, Over Scale: 20.0 to 22.5mA) B urnout signal level is adjustable using Model FXW Hand Held Communicator (HHC) to comply with NAMUR NE43. 6. Dry calibration without reference pressure Thanks to the best combination of unique construction of mechanical parts (Sensor unit) and high performance electronics circuit (Electronics unit), reliability of dry calibration without reference pressure is at equal level as wet calibration.
SPECIFICATIONS
Functional specifications
Service: Liquid, gas, or vapour Span, range and overrange limit:
Span limit [kPa] {bar} Type Min. FKP □ 01 FKP □ 02 FKP □ 03 FKP □ 04 8.125 {0.08125} 31.25 {0.3125} 187.5 {1.875} 625 {6.25} Max. 130 {1.3} 500 {5} 3000 {30} 10000 {100} Range limit [kPa] {bar} −100 to +130 {−1 to +1.3} −100 to +500 {−1 to +5} −100 to +3000 {−1 to +30} −100 to +10000 {−1 to + 100} Overrange limit [MPa] {bar} 1 {10} 1.5 {15} 9 {90} 15 {150}
— Lower range limit (vacuum limit) is; Silicone fill sensor: See Fig. 1 Fluorinated fill sensor: 66kPa abs (500mmHg abs) at below 60°C Output signal: 4 to 20mA DC with digital signal superimposed on the 4 to 20mA signal.
EDSX5-98g
Date Aug. 10, 2011
FKP...5
Power supply: Transmitter operates on 10.5V to 45V DC at transmitter terminals. 10.5V to 32V DC for the units with optional arrester. Load limitations: see figure below
[Ω] 2000 Load resistance 1474Ω R= E-10.5 (Imax+0.9)x10-3 577Ω Operating area 24V 10 16.35 10.5V Power voltage (DC) 45V 50 E[ V ]
1500 1000 500 250 0
Note: For communication with HHC(1) (Model: FXW), min. of 250 required.
Hazardous locations: SEE TABLE3 Zero/span adjustment: Zero and span are adjustable from the HHC(1). Zero and span are also adjustable externally from the adjustment screw. Damping: Adjustable from HHC or local configurator unit with LCD display. The time constant is adjustable between 0.06 to 32 seconds. Zero elevation/suppression: Zero can be elevated or suppressed within the specified range limit of each sensor model. Normal/reverse action: Selectable from HHC(1). Indication: Analog indicator or 5-digit LCD meter, as specified. Burnout direction: Selectable from HHC(1) If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale” or “Output Underscale” modes. “Output Hold”: Output signal is hold as the value just before failure happens. “Output Overscale”: Adjustable within the range 20.0mA to 22.5mA from HHC(1) “Output Underscale”: Adjustable within the range 3.2mA to 4.0mA from HHC
3.2 4 20 22.5 [mA] Over scale Burnout Normal operating range Under scale Probable under range Burnout Probable over range
Temperature limit: Ambient: − 40 to +85°C (−20 to +80°C for LCD indicator) (− 40 to +60°C for arrester option) (−10 to +60°C for fluorinated oil fill transmitter) For explosionproof units (flameproof or intrinsic safety), ambient temperature must be within the limits specified by each standard. Process: − 40 to +100°C for silicone fill sensor −20 to +80°C for fluorinated oil fill sensor Storage: −40 to +90°C Humidity limit: 0 to 100% RH Communication: W ith HHC(1) (Model FXW, consult Data Sheet No. EDS8-47), following items can be remotely displayed or configured. Note: HHC’s version must be higher than 7.0 (or FXW 1– 4), for FCX AIII. Local configurator with LCD display (option): Local confi gurator with 3 push button and LCD display can support following items.
Items By communication By local configurator with FXW (with 3 push button) Display Tag No. Model No. Serial No. & Software Version Engineering unit Range limit Measuring range Damping Output mode Burnout direction Calibration Output adjust Data Self diagnoses Printer (In case of FXW with printer option) External switch lock Transmitter display Linearize Rerange Saturate current Write protect History – Calibration history – Ambient temperature history v v v v v v v v v v — v v v v v v v v v v v Set v v — v — v v — v v v — — — v v v v v v v — Display v v v v v v v v v v — v v — v v — v v v v v Set v v — v — v v — v v v — — — v v — v v v v —
EMC Conformity: EN61326-1: 2006
Output limits conforming to NAMUR NE43 by order. Loop-check output: Transmitter can be configured to provide constant signal 3.2mA through 22.5mA by HHC.
(Note)
(1) HHC: Hand Held Communicator
2
Performance specifications
Accuracy rating: ( including linearity, hysteresis, and repeatability) For spans greater than 1/10 of URL: ±0.1% of span For spans below 1/10 of URL : ± (0.05 + 0.05 0.1 x URL ) % of span span Stability: ±0.2% of upper range limit (URL) for 10 years (In case of 6th digit code “2”, “3”, “4”) Temperature effect: E ffects per 55°C change between the limits of − 40°C and +85°C Zero shift : URL ± (0.4 + 0.1 span )%/28°C Total effect: URL ± (0.475 + 0.1 span )%/28°C Overrange effect: Zero shift, 0.3% of URL for any overrange to maximum limit Supply voltage effect: Less than 0.05% of calibrated span per 10V Update rate: 60 msec Step response: Time constant: 0.08s (at 23°C) Dead time: about 0.12s (without electrical damping) Mounting position effect: Zero shift, less than 0.1kPa {1mbar} for a 10° tilt in any plane. No effect on span. This error can be corrected by adjusting zero. (Double the effect for fluorinated fill sensors) Dielectric strength: 500V AC, 50/60Hz 1 min., between circuit and earth Insulation resistance: More than 100M at 500V DC Internal resistance for external field indicator: 12 or less.
Physical specifications
Electrical connections: G1/2, 1/2-14 NPT, Pg13.5, or M20×1.5 conduit, as specified. Process connections: 1/2-14NPT, Rc1/2, Rc1/4 or 1/4-18NPT, as specified. Process-wetted parts material:
l a i reta M edoc Process t i g i d ht7 ( cover e d oC n i symbols) V 316 stainless steel 316L stainless steel 316 stainless steel Wetted sensor body
Diaphragm
Non-wetted parts material: Electronics housing: Low copper die-cast aluminum alloy (standard), finished with polyester coating. Fill fluid: Silicone oil (standard) or fluorinated oil (Daifloil) Mounting bracket: 304 stainless steel Environmental protection: IEC IP67 and NEMA 6/6P Mounting: On 60.5mm (JIS 50A or 2B) pipe using mounting bracket, direct wall mounting, or direct process mounting. Mass{weight}: Transmitter approximately 2.2kg without options. Add; 0.5kg for mounting bracket
3
FKP...5
Optional features
Indicator: A plug-in turnable analog indicator (2.5% accuracy) An optional 5digits LCD meter with engineering unit is also available. Local configurator with LCD display: An optional 5 digits LCD meter with 3 push buttons can support items as using communication with FXW. Arrester: A built-in arrester protects the electronics from lightning surges. Lightning surge immunity: 4kV (1.2 x 50 µs) Oxygen service: Special cleaning procedures are followed throughout the process to maintain all process wetted parts oil-free. The fill fluid is fluorinated oil. Degreasing: Process-wetted parts are cleaned, but the fill fluid is standard silicone oil. Not for use for oxygen or chlorine measurement. NACE specification: Metallic materials for all pressure boundary parts comply with NACE MR-01-75. Optional tag plate: An extra stainless steel tag with customer tag data is wired to the transmitter.
ACCESSORIES
Hand-held communicator: ( Model FXW, refer to Data Sheet No. EDS8-47)
Silicone oil (Code:Y,G,N)
[kPa abs] (mmHg abs) 101 (760) Operating pressure Operating area 20 (150)
4 (30) 2.7 (20) −40
None-operating area 60 100
Process temperature [°C ] Fig. 1 Relation between process temperature and operating pressure
4
CODE SYMBOLS
12345678 9 10 11 12 13 14 15 21
Digit 4
Description Conduit connection Process connection Case type 1/2-14NPT G1/2 T type 1/2-14NPT 1/2-14NPT T type 1/2-14NPT T type Pg13.5 1/2-14NPT T type M20×1.5 FKP kPa {bar} 8.125 … 130 {0.08125 … 1.3} 31.25 … 500 {0.3125 … 5} 187.5 … 3000 {1.875 … 30} 625 …10000 {6.25 …100} Process cover Diaphragm Wetted cell body 316 stainless steel 316L stainless steel 316 stainless steel Indicator Arrester None None Analog, 0 to 100% linear scale None Analog, custom scale None None Yes Analog, 0 to 100% linear scale Yes Analog, custom scale Yes Digital, 0 to 100% linear scale None Digital, custom scale None Digital, 0 to 100% linear scale Yes Digital, custom scale Yes Digital, 0 to 100% linear scale (Local configurator unit with LCD displey) None Digital, Custom scale (Local configurator unit with LCD displey) None Digital, 0 to 100% linear scale (Local configurator unit with LCD displey) Yes Digital, Custom scale (Local configurator unit with LCD displey) Yes None (for ordinary locations) TIIS, Flameproof (Cable gland seal) (*1) TIIS, Intrinsic safety FM, Flameproof (or explosionproof) (*4) FM, Intrinsic safety and nonincentive FM Combined of flameproof and intrinsic safety (*4) ATEX Flameproof (*3) ATEX Intrinsic safety ATEX Type n ATEX Combined of flameproof and intrinsic safety (*3) IECEx Scheme, Flameproof (*3) IECEx Scheme, Intrinsic safety CSA, Flameproof (or explosionproof) (*4) CSA, Intrinsic safety and nonincentive NEPSI, Flameproof (or exprosionproof) NEPSI, Intrinsic safety NEPSI, Combined of flameproof and intrinsic safety None Yes (stainless steel) Stainless tag None (*5) Yes Treatment Filled liquid None (standard) Silicon oil Degreasing Silicon oil Oxygen service Fluorinated oil NACE specification Silicon oil None (1/2 -14NPT) Rc1/4 Rc1/2 1/4-18NPT (*6) Instruction manual unattached (*1) (*3) (*4) (*5) (*6)
Note
FKP
0
5
0
Digit No. of code
5 6 7 8 1 2 3 4
6
7
V
9
A B D E F H L P Q S 1 2 4 5
10
Note 1 Note 4 Note 4 Note 3
Note 3 Note 3 Note 4
A C G D H V X K P M R T E J F S U A C
11
12
Note 5
Y B
13
Y G A N Y A B C Note 6 L
15
21 Note1: Note3: Note4: Note5: Note6:
Available for 4th digit code "5". Available for 4th digit code "6", "8". Available for 4th digit code "6". Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required select "Yes". If other option is not necessary, 21st digit code is blank. In case of 21st digit code is blank, instruction manual attached.
5
FKP...5
OUTLINE DIAGRAM (Unit:mm)
IN CASE OF 4TH DIGIT CODE "6" 2 HOLES 9 DIA. ZERO ADJ. SCREW EARTH TERMINAL 8 17 10 IN CASE OF 4TH DIGIT CODE "5, 7, 8" MTG. PIPE JIS 50A (2B)
ZERO
100
212
"B" CONDUIT CONN. WITH ANALOG IND. (21) (11)
WITH DIGITAL IND.
127 20 DETAIL "A" φ18 φ81 φ15 DETAIL "B" DETAIL "D"
F
φ6
16
E
70 "A" PRESS. CONN. 1/2-14NPT
D SEE TABLE1
L SEE TABLE2
27
G
MTG. BLACKET 85 U-BOLT M8 SEE TABLE2
4th digit of the code symbols 5
Conduit conn. D G 1/2 1/2-14NPT Pg13.5 M20×1.5 E 18 16 10.5 16 F 2 4 4.5 4 CONN. (L) Rc 1/2 NPT 1/4 Rc 1/4 ADAPTER G 38 18 H 31 25 J 27 22 K 16 8
"D" ADAPTER (OPTION) SEE TABLE2
6 7
J
8
TABLE 1
TABLE 2
108
35 170
H
OPTION PARTS FOR FLAMEPROOF OF TIIS (JAPAN)
CONNECTION DIAGRAM
+ −/CK− CK+
10th digit code C (Cable gland type) NOTE1)
G1/2 φ33.5
DETAIL C φ13
75
106 20
"C" CONDUIT CONN. G1/2
CABLE GLAND
NOTE1) IN CASE OF 10TH CODE “C”φ11 CABLE IS SUITBLE. ,
6
17
19
K
TABLE 3
Authorities ATEX Intrinsic safety Ex II 1 G Ex ia IIC T5 Tamb = –40°C to +50°C Ex ia IIC T4 Tamb = –40°C to +70°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator), Ci=36nF (With Arrester), Li=0.7mH (With analog indicator) Factory Mutual Class I II III Div.1 Groups A, B, C, D, E, F G , T4 Entity Type 4X Model code 13th digit 9th digit A,B,D L,P ,1,2 Q,S,4,5 E,F ,H − Y,G,N Y,G,N Y,G,N Y,G,N A Tamb −40°C to +85°C −20°C to +80°C −20°C to +60°C −40°C to +60°C −10°C to +60°C IECEx Scheme CSA Authorities ATEX Flameproof Ex II 2 GD Ex d IIC T6 IP66/67 T85°C Tamb = −40°C to +65°C Ex d IIC T5 IP66/67 T100°C Tamb = −40°C to +85°C Class I Div.1 Groups B, C, D T6 Type 4X Class II III Div.1 Groups E, F G , T6 Type 4X Tamb max = +60°C Class I Div.1 Groups C, D Class II Div.1 Groups E, F G , Class III Div.1 Note) “Seal Not Required” enclosure is allowed. Ex d IIC T5 IP66/67 Tamb = −40°C to +85°C Ex d IIC T6 IP66/67 Tamb = −40°C to +65°C Ex do IIB+H2 T4 Tamb max = +60°C Maximum process temp. = +120°C Ex d IIB+H2 T6 Tamb = −40°C to +60°C Type n Nonincendive Ex II 3 GD EEx nL IIC T5 Tamb = −40°C to +50°C EEx nL IIC T4 Tamb = −40°C to +70°C Specific Parameters: Model without arrester: Ui=42.4V, Ii=113mA, Pi=1W, Ci=25.18nF Li=0.694mH , Model with arrester: Ui=32V, Ii=113mA, Pi=1W, Ci=35.98nF Li=0.694mH , EEx nAL IIC T5 Tamb = −40°C to +50°C EEx nAL IIC T4 Tamb = −40°C to +70°C Specific Parameters: Model without arrester: Umax=42.4V, Imax=113mA, Pmax=1W, Model with arrester: Umax=32V, Imax=113mA, Pmax=1W Factory Mutual (pending) Class I II III Div.2 Groups A, B, C, D, F G , T4 Entity Type 4X Model code 9th digit 13th digit A,B,D L,P ,1,2 Q,S,4,5 E,F ,H − CSA Y,G,N Y,G,N Y,G,N Y,G,N A Tamb −40°C to +85°C −20°C to +80°C −20°C to +60°C −40°C to +60°C −10°C to +60°C
Factory Mutual
Entity Parameters: Vmax=28V, Imax=94.3mA, Pi=0.66W, Ci=35.98nF Li=0.694mH , CSA Class I Div.1 Groups A, B, C, D Class II Div.1 Groups E, F G , Class III Div.1 Temp Code T5 Tamb max = +50°C Temp Code T4 Tamb max = +70°C Entity Parameters: Vmax=28V, Imax=94.3mA, Ci=25nF (Without Arrester), Ci=36nF (With Arrester),Li=0.6mH (Without analog meter), Li=0.7mH (With analog meter) Ex ia IIC T4 Tamb max = +60°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=38.4nF Li=0.694mH , Ex ia IIC T4 Tamb = –40°C to +70°C Ex ia IIC T5 Tamb = –40°C to +50°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator), Ci=36nF (With Arrester), Li=0.7mH (With analog indicator) Ex ia IIC T4 Ex d IIB+H2 T6 / Ex ia IIC T4 Model code 9th digit A,B,D L,P ,1,2 Q,S,4,5 E,F ,H − 13th digit Y,G,N Y,G,N Y,G,N Y,G,N A Tamb −40°C to +85°C −20°C to +80°C −20°C to +60°C −40°C to +60°C −10°C to +60°C
TIIS
NEPSI
Authorities ATEX
TIIS
IECEx Scheme
NEPSI
Entity Parameters: Ui=42.4V, Ii=113mA, Pi=1W, Ci=35.98nF Li=0.694mH ,
Class I Div.2 Groups A, B, C, D Class II Div.2 Groups E, F G , Class III Div.2 Temp Code T5 Tamb max = +50°C Temp Code T4 Tamb max = +70°C Entity Parameters: Vmax=28V, Ci=25.18nF (Without Arrester), Ci=35.98nF (With Arrester), Li=0.694mH
7
FKP...5
Caution on Safety *Before using this product, be sure to read its instruction manual in advance.
International Sales Div Sales Group Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fujielectric.com Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425 http://www.fjielectric.com/products/instruments/ Information in this catalog is subject to change without notice.