FCX – AX SERIES
DATA SHEET
DIFFERENTIAL PRESSURE TRANSMITTER
FHC, FKC...3
The FCX – AX differential pressure transmitter accurately measures differential pressure, liquid level or gauge pressure and transmits a proportional 4 to 20mA signal. The transmitter utilizes a unique micromachined capacitance silicon sensor with state-of-the-art microprocessor technology to provide exceptional performance and functionality.
FEATURES
1. High accuracy 0.07% accuracy for all calibrated spans is a standard feature for all DP models covering 0.1kPa{1m bar} draft range to 3000kPa{30 bar} high differential. Fuji's microcapacitance silicon sensor assures this accuracy for all elevated or suppressed calibration ranges without additional adjustment. 2. Minimum environmental influence The "Advanced Floating Cell" design which protects the pressure sensor against changes in temperature, static pressure, and overpressure substantially reduces total measurement error in actual field applications. 3. Replaceable Communication Module Fuji micro-electronics manufacturing technology offers replaceable communication module that makes FCX – AX transmitter very unique in design. In case of change in communication protocol, all that needs to be done is just to replace the module and the transmitter gets upgraded to the new version. 4. Fuji/HART bilingual communication module The communication module is "bilingual" to speak both Fuji proprietary protocol and HART. Any HART compatible devices can communicate with FCX – AX series transmitters. 5. Application flexibility Various options that render the FCX – AX suitable for almost any process applications include. – Analog indicator at either the electronics side or terminal side – Full range of hazardous area approvals – Built-in RFI filter and lightning arrester – 4 1 -digits LCD meter 2 – Stainless steel electronics housing – Wide selection of materials 6. Programmable output Linearization Function In addition to Linear and Square Root, output signal can be freely programmable. (Up to 14 compensated points at approximation.)
(Available for amplifier unit from version 24 and FXW(HHC) version 5.3.)
8. Dry calibration without reference pressure Thanks to the best combination of unique construction of mechanical parts (Sensor unit) and high performance electronics circuit (Electronics unit), reliability of dry calibration without reference pressure is at equal level as wet calibration.
SPECIFICATIONS
Functional specifications
Type: Model FHC: 4 to 20mA Model FKC: 4 to 20mA with digital signal Service: Liquid, gas, or vapour Static pressure, span, and range limit:
Span limit [kPa] {m bar} Type Static pressure [MPa] {bar} FHC F C 11 –0.1 to + 3.2 {–1 to + 32} F C 22 –0.1 to + 10 {–1 to + 100 } F C 23 –0.1 to + 10 {–1 to + 100 } F C 25 –0.1 to + 10 {–1 to + 100 } F C 26 –0.1 to + 10 {–1 to + 100 } F C 33 –0.1 to + 16 {–1 to + 160 } F C 35 –0.1 to + 16 {–1 to + 160 } F C 36 –0.1 to + 16 {–1 to + 160 } F C 38 –0.1 to + 16 {–1 to + 160 } F C 43 –0.1 to + 42 {–1 to + 420 } F C 44 –0.1 to + 42 {–1 to + 420 } F C 45 –0.1 to + 42 {–1 to + 420 } F C 46 –0.1 to + 42 {–1 to + 420 } F C 48 –0.1 to + 42 {–1 to + 420 } 0.1 { 1} 0.6 { 6} 3.2 { 32 } 13 { 130 } 50 { 500} 3.2 { 32} 13 { 130 } 50 { 500 } 300 {3000 } 3.2 { 32 } 6.4 { 64 } 13 { 130 } 50 { 500 } 300 { 3000 } { Min. FKC 0.1 1} 0.1 { 1} 0.32 { 3.2 } 1.3 { 13 } 5 { 50 } 0.32 { 3.2 } 1.3 { 13 } 5 { 50 } 30 { 300 } 0.32 { 3.2 } 0.64 { 6.4 } 1.3 { 13 } 5 { 50 } 30 { 300 } Max. FHC/FKC 1 10 } 6 60 } 32 320 } 130 1300 } 500 5000 } 32 320 } 130 1300 } 500 5000 } 3000 30000 } 32 320 } 64 640 } 130 1300 } 500 5000 } 3000 30000 } Range limit [kPa] {m bar}
{ { { { { { { { { { { { { {
7. Burnout current flexibility (Under Scale: 3.2 to 3.8mA, Over Scale: 20.8 to 21.6mA) Burnout signal level is adjustable using Model FXW hand Held Communicator (HHC) to comply with NAMUR NE43.
(Available for amplifier unit from version 24 and FXW(HHC) version 5.3.)
+/– 1 { +/– 10 } +/– 6 { +/– 60 } +/– 32 { +/– 320 } +/– 130 { +/– 1300 } +/– 500 { +/– 5000 } +/– 32 { +/– 320 } +/– 130 { +/– 1300 } +/– 500 { +/– 5000 } +/– 3000 { +/– 30000 } +/– 32 { +/– 320 } +/– 64 { +/– 640 } +/– 130 { +/– 1300 } +/– 500 { +/– 5000 } +/– 3000 { +/– 30000 }
Remark : To minimize environmental influence, span should be greater than 1/40 of the max. span in most applications.
EDSX6-100
Date Mar. 15, 1999
FHC, FKC...3
– Lower limit of static pressure (vacuum limit) ; Silicone fill sensor: See Fig. 1 F C 38 and F C 48: –0.5kgf/cm2 Fluorinated fill sensor: 66kPa abs (500mmHg abs) at temperature below 80°C – The maximum span of each sensor can be converted to different units using below factors. 1MPa= 103KPa=10bar=10.19716kgf/cm2= 145.0377psi 1kpa=10mbar=101.9716mmH2O=4.01463inH2O Over range limit: To maximum static pressure limit Output signal: Model FHC: 4 to 20mA DC 2-wire, linear signal Model FKC: 4 to 20mA DC (linear or square root) with digital signal superimposed on the 4 to 20mA signal Power supply: Transmitter operates on 10.5V to 45V DC at transmitter terminals. 10.5V to 32V DC for the units with optional arrester. Load limitations: see figure below
[Ω]
2000
Load resistance
1533Ω
1500 1000 500 250 10
Zero elevation/suppression: –100% to +100% of URL Normal/reverse action: Model FHC: Selectable by moving a jumper pin located on the electronics unit. Model FKC: Selectable from HHC Indication: Analog indicator or 4 1 -digit LCD meter, as 2 specified. Burnout direction: If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale” or “Output Underscale” modes. Model FHC: Unless otherwise specified in the order, the transmitter will be shipped in “Output Hold” mode. (Output signal just before failure happens is maintained.) Model FKC: Selectable from HHC “Output Hold”: Output signal is hold as the value just before failure happens. “Output Overscale”: Approx. 21.6mA (Adjustable within the range 20.8mA to 21.6mA from HHC) “Output Underscale”: Approx. 3.8mA (Adjustable within the range 3.2mA to 3.8mA from HHC)
3.2 3.8 4 20 20.8 Over scale Burnout
600Ω Operating area 24V 16.1 10.5V Power voltage 45V 50 [V]
0 Normal operating range Under scale Probable under range Burnout
21.6 Probable over range
Note: For communication with HHC (Model: FXW), min. of 250 Ω required.
Hazardous locations: (Approval pending)
Authorities BASEEFA Factory Mutual CSA Flameproof Ex ds IIC T5, T6 Class I II III Div. 1 Groups B thru. G Class I II III Div. 1 Groups C thru. G Ex ds IIB+H2 T4 Ex d II C T5, T6 IP 66/67 Intrinsic safety EEx ia IIC T4, T5 Class I II III Div. 1 Groups A thru. F Class I II III Div. 1 Groups A thru. G — Ex ia II C T5, T6 IP 66/67 Type N Nonincendive Ex N II T5 Class I II III Div. 2 Groups A thru. G Class I II III Div. 2 Groups A thru. G — Ex n II C T5, T6 IP 66/67
RIIS SAA
Zero/span adjustment: Model FHC: Zero is adjustable from the external adjustment screw. The adjustment screw can also function to adjust span when MODE SWITCH (located on the electronics unit) is in the span mode. INHIBIT mode to disable the adjustment screw is also available. Model FKC: Zero and span are adjustable from the HHC. Zero is also adjustable externally from the adjustment screw. Damping: Adjustable electrical damping. Model FHC: The time constant is adjustable to 0, 0.3, 1.2, 4.8, or 19.2 seconds. Model FKC: The time constant is adjustable between 0 to 38.4 seconds. (4 steps)
Loop-check output: Model FHC: Transmitter can output constant signal of 4mA, 12mA, or 20mA if MODE SWITCH is set to the loop check mode. Model FKC: Transmitter can be configured to provide constant signal 3.8mA through 21.6mA by HHC. Temperature limit: Ambient: – 40 to +85°C (–20 to +80°C for LCD indicator) (– 40 to +60°C for arrester option) (–10 to +60°C for fluorinated oil filled transmitters) – 15 to +85°C for 5th digit code “4” and 6 digit code “8”. For explosionproof units (flameproof or intrinsic safety), ambient temperature must be within the limits specified in each standard. Process: – 40 to +120 °C for silicone fill sensor –20 to +80°C for fluorinated oil fill sensor Storage: – 40 to +90°C Humidity limit: 0 to 100% RH
2
Communication: (Model FKC only) With HHC (Model FXW, consult Data Sheet No. EDS8-47), following information can be remotely displayed or reconfigured.
Items Tag No. Model No. Serial No. Engineering unit Range limit Measuring range Damping Output mode Burnout direction Adjustment Output adjust Data Self diagnoses Printer External switch lock Transmitter display(*) Linearise (**) Rerange (**) Display v v v v v v v v v v — v v — v v v v Set v v — v — v v v v v v — — — v v v v
Static pressure effect:
Static pressure code (5th digit in Code symbols) “1” /1kPa {10m bar} sensor “2” /6kPa {60 m bar} sensor “2” “3” “4” Zero shift (% of URL) Span shift (% of calibrated span)
± 0.1% / 1MPa{10bar} –0.2% /3.2MPa{32bar} ± 0.1% / 3.2MPa{32bar} –0.2% /3.2MPa{32bar} ± 0.05%/10MPa{100bar} –0.2%/10MPa{100bar}
Double the Zero shift for material code (7th digit in Code symbols) “H”, “M”, “T”, “B”, “L” and “U”. Overrange effect:
Static pressure code (5th digit in Code symbols) “1” / 1kPa {10m bar} sensor “2” / 6kPa {60m bar} sensor “2” “3” “4” Zero shift (% of URL) ± 0.3% / 1MPa ± 0.3% / 3.2MPa ± 0.1% /10MPa ± 0.1% /16MPa ± 0.17% /42MPa {10bar } {32bar } {100bar } {160bar } {420 bar}
(*1)
Notes: (*) HHC's version must be more than 5.0 (or FXW 1 – 2 ), to use this function. (**) HHC's version must be more than 5.3, and Amplifier unit version 24.
Double the effects for material code (7th digit in Code symbols) “H”, “M”, “T”, “B”, “L” and “U”. Note: (*1) In case of 6th code “5”. Supply voltage effect: Less than 0.05% of calibrated span per 10V RFI effect: Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength 30 V/m when electronics covers on. (Classification: 2-abc: 0.2% span per SAMA PMC 33.1) Step response: (without electrical damping)
Range code “1” “2” “3” “4” through “8” Time constant 1.25 s 0.85 s 0.45 s 0.2 s approx. 0.3 s Dead time
Programmable output linearization function: In smart version, output signal can be characterized with “14 points linear approximation function” from HHC.
Performance specifications for linear output
Accuracy rating: (including linearity, hysteresis, and repeatability) Max span above 32kPa model: For spans greater than 1/10 of URL: ± 0.07% of span For spans below 1/10 of URL (Model FKC only): 0.1 × URL ± 0.02+0.05 % of span Span Max span 1kPa, 6kPa model: For spans greater than 1/10 of URL: ± 0.1% of span For spans below 1/10 of URL (Model FKC only):
( (
) )
0.1 × URL % of span Span Linearity: 0.05% of calibrated span Stability: ± 0.1% of upper range limit (URL) for 24 months Temperature effect: Effects per 55°C change between the limits of – 40°C and +85°C ± 0.05+0.05
Range code (6th digit in Code Zero shift symbols) “1”/1kPa {10mbar} max. span “2”/6kPa {60mbar} max. span Total effect
± 0.125+0.1 URL %/28°C ± 0.15+0.1 URL %/28°C Span Span
(
)
(
)
Mounting position effect: Zero shift, less than 0.12kPa {1.2m bar} for a 10° tilt in any plane. No effect on span. This error can be corrected by adjusting Zero. (Double the effect for fluorinated fill sensors) Dielectric strength: 500V AC, 50/60Hz 1 min., between circuit and earth. Insulation resistance: More than 100MΩ at 500V DC. Turn-on time: 4 sec. Internal resistance for external field indicator: 12Ω or less
“3”/32kPa {320mbar} max. span “4”/64kPa {640mbar} max. span “5”/130kPa {1300mbar} max. ± 0.1+0.025 URL %/28°C ± 0.125+0.025 URL %/28°C span Span Span “6”/500kPa {5000mbar} max. span “8”/3000kPa {30000mbar} max. span
(
)
(
)
Double the effects for material code (7th digit in Code symbols) “H”, “M”, “T”, “B”, “L” and “U”.
3
FHC, FKC...3
Performance specifications for square root output
(Model FKC only) Accuracy rating:
Span Output 50 to 100% 20 to 50% 10 to 20% over 0.1 × URL ± 0.07 % ± 0.175 % ± 0.35 % below 0.1 × URL ± (0.02+0.05 × 0.1 × URL/Span)% ± 2.5 × (0.02+0.05 × 0.1 × URL/Span)% ± 5 × (0.02+0.05 × 0.1 × URL/Span)%
Physical specifications
Electrical connections: G1/2, 1/2-14 NPT, Pg13.5, or M20 × 1.5 conduit, as specified. Process connections: 1/4-18 NPT or Rc1/4 on 54mm centers, as specified. Meets DIN 19213. Process-wetted parts material:
Max span 1kPa, 6kPa model:
Output 50 to 100% 20 to 50% 10 to 20% Accuracy ± 0.1 % ± 0.25% ± 0.5 %
Material code (7th digit Process cover in Code symbols) V H 316 stainless steel(*1) 316 stainless steel(*1) 316 stainless steel(*1) 316 stainless steel(*1) Hastelloy-C lining Monel lining Tantalum lining
Diaphragm
Wetted sensor body
Vent/drain
Temperature effect: effect per 55°C change between the limits of – 40°C and +85°C
Range code Shift at 20% output point
316L stainless 316 stainless steel steel Hastelloy-C Hastelloy-C lining Monel Tantalum Monel lining Tantalum lining Hastelloy-C lining Monel lining Tantalum lining
316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel Hastelloy-C Monel Tantalum
M T
“1” and “2” “3” through “8”
URL ± 0.3+0.25 Span %/28°C URL ± 0.25+0.0625 Span %/28°C
(
)
(
)
B L U
Hastelloy-C Monel Tantalum
Low flow cut-off: Customer configurable for any point between 7 to 20% of output
Notes: * (1) SCS14 per JIS G 5121 Remark: Sensor O-rings: Viton and teflon selectable. Availability of above material design depends on ranges and static pressure. Refer to “Code symbols”.
Non-wetted parts material: Electronics housing: Low copper die-cast aluminum alloy (standard), finished with polyester coating, or 316 stainless steel (SCS14 per JIS G5124), as specified. Bolts and nuts: Cr-Mo alloy (standard), 304 stainless steel (for static pressure code “1”, “2”, and “3” only), or 630 stainless steel (for static pressure code “3” and “4” only). Static pressure rating for code “3” with 304 stainless steel bolts is degraded to 10MPa. Fill fluid: Silicone oil (standard) or fluorinated oil (Daifloil) Mounting bracket: Carbon steel with epoxy coating or 304 stainless steel, as specified Environmental protection: IEC IP67 and NEMA 4X Mounting: On 60.5mm(JIS 50A) pipe using mounting bracket, direct wall mounting, or direct process mounting. Mass{weight}: Transmitter approximately 4.4kg without options. Add; 0.5kg for mounting bracket 0.8kg for indicator option 4.5kg for stainless steel housing option
4
Optional features
A plug-in analog indicator (1.5% accuracy) can be housed in the electronics compartment or in the terminal box of the housing. An optional 4 1 digits LCD meter is also 2 available. Arrester: A built-in arrester protects the electronics from lightning surges. Lightning surge immunity: 4KV (1.2 × 50µs) Oxygen service: Special cleaning procedures are followed throughout the process to maintain all process wetted parts oil-free. The fill fluid is fluorinated oil. Chlorine service: The fill fluid is fluorinated oil. Degreasing: Process-wetted parts are cleaned, but the fill fluid is standard silicone oil. Not for use on oxygen or chlorine measurement. NACE specification: Metallic materials for all pressure boundary parts comply with NACE MR-01-75. ASTM B7M or L7M bolts and 2HM nuts (Class II) are available. Static pressure rating for code “3” (16 MPa) is degraded to 10MPa. Vacuum service: Special silicone oil and filling procedure are applied. See below figure.
Silicone oil (Code:Y,G,N) Silicone oil (Code:R) [kPa abs] {mbar abs} 101 {1010} Operating pressure
ACCESSORIES
Oval flanges: (Model FFP, refer to Data Sheet No. EDS6-10) Converts process connection to 1/2-14 NPT or to Rc1/2; in carbon steel or in 316 stainless steel.
Indicator:
Equalizing valves: (Model FFN, refer to Data Sheet No. EDS6-10) Available in CS or in 316 stainless steel and in pressure rating 16MPa or 42MPa. Hand-held communicator: (Model FXW, refer to Data Sheet No. EDS 8-47) Communication module: (standard for model FKC) By adding communication module, remote setting functions becomes available for model FHC.
Remark: When the communication module is connected, the operation mode of external zero/span adjustable screw is limited to zero adjustment only.
20 {200}
Operating area
4 {40} 2.7 {27} –40
None-operating area –15 60 85 120 Process temperature[°C ]
Fig. 1 Relation between process temperature and operating pressure
Customer tag: Coating of cell:
A stainless steel tag with customer tag data is wired to the transmitter. Cell's surface is finished with epoxy/polyurethane double coating. Specify if environment is extremely corrosive.
5
FHC, FKC...3
CODE SYMBOLS
12345678 9 10 11 12 13 14 15
3 FHC FKC Type 4 to 20mA, Output type 4 to 20mA with digital signal, Output type Connections Process connection S T V W X Rc1/4 1/4-18NPT 1/4-18NPT 1/4-18NPT 1/4-18NPT Oval flange screw 7/16-20UNF 7/16-20UNF M10 (or M12)(*!) M10 (or M12)(*!) 7/16-20UNF
Description
Conduit connection G 1/2 1/2-14NPT Pg 13.5 M20×1.5 Pg 13.5
Span and materials
Static pressure [MPa] {bar} –0.1 to +3.2 {–1 to +32} –0.1 to +10 {–1 to 100} Span limit (*2) FHC/FKC [kPa] (m bar) 0.1/0.1…1/1 {1/1…10/10} 0.6/0.1…6/6 {6/1…60/60} Process cover 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel –0.1 to +16 3.2/0.32…32/32 {–1 to +160} {32/3.2…320/320} 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel Hast. C lining Monel lining Tantalum lining Hast. C lining Monel lining Tantalum lining Hast. C lining Monel lining Diaphragm Wetted cell body 316 stainless steel Hast. C lining 316 stainless steel Hast. C lining 316 stainless steel Hast. C lining Monel lining Tantalum lining 316 stainless steel Hast. C lining Monel lining Tantalum lining 316 stainless steel Hast. C lining Monel lining Tantalum lining 316 stainless steel 316 stainless steel Hast. C lining Monel lining 316 stainless steel Hast. C lining Monel lining 316 stainless steel Hast. C lining Monel lining 316 stainless steel Hast. C lining Monel lining Tantalum lining Hast. C lining Monel lining Tantalum lining Hast. C lining Monel lining
11V 11H 22V 22H 33V 33H 33M 33T 35V 35H 35M 35T 36V 36H 36M 36T 38V 43V 43H 43M 45V 45H 45M 46V 46H 46M 48V 23B 23L 23U 25B 25L 25U 26B 26L 26U
316L stainless steel Hast. C 316L stainless steel Hast. C 316L stainless steel Hast. C Monel Tantalum 316L stainless steel Hast. C Monel Tantalum 316L stainless steel Hast. C Monel Tantalum 316L stainless steel 316L stainless steel Hast. C Monel 316L stainless steel Hast. C Monel 316L stainless steel Hast. C Monel 316L stainless steel Hast. C Monel Tantalum Hast. C Monel Tantalum Hast. C Monel Tantalum
13/1.3…130/130 {130/13…1300/1300}
50/5…500/500 {500/50…5000/5000}
300/30…3000/3000 {3000/300…30000/30000} –0.1 to +42 3.2/0.32…32/32 {–1 to +420} {32/3.2…320/320} 13/1.3…130/130 {130/13…1300/1300} 50/5…500/500 {500/50…5000/5000} 300/30…3000/3000 {3000/300…30000/30000} 3.2/0.32…32/32 {32/3.2…320/320} 13/1.3…130/130 {130/13…1300/1300} 50/5…500/500 {500/50…5000/5000}
–0.1 to +10 {–1 to+100}
Notes: * (1) The thread is M12, if 42MPa {420bar} static pressure is specified. (2) 100: 1 turn down is possible for model FKC, but should be used at the span greater than 1/40 of the maximum span for better performance.
6
12345678
9 10 11 12 13
14 15
FHC FKC
3 3 Description Indicator and arrester Indicator Arrester None Available for 4th digit code “S“) None Analog, 0 to 100% linear scale None Analog, 0 to 100% sq. root scale None Analog, custom scale None Analog, double scale None (*6) None Yes Analog, 0 to 100% linear scale Yes Analog, 0 to 100% sq. root scale Yes Analog, custom scale Yes Analog, double scale Yes (*6) Digital, 0 to 100% None Digital, custom scale None (Model FKC only) (*7) Digital 0 to 100% square root None Digital, 0 to 100% Yes Digital, custom scale Yes (Model FKC only) (*7) Digital 0 to 100% square root Yes Approvals for hazardous locations (Approval pending) None (for ordinary locations) JIS, Flameproof (Conduit seal) (Available for 4th digit code “S“) JIS, Flameproof (Cable gland seal) (Available for 4th digit code “S“) FM, Flameproof (or explosionproof) (Available for 4th digit code “T“) CSA, Flameproof (or explosionproof) (Available for 4th digit code “T“) BASEEFA, Flameproof (Conduit seal) BASEEFA, Flameproof (Cable gland seal) (Conduit connection G 1/2 only) FM, Intrinsic safety and Nonincendive CSA, Intrinsic safety and Nonincendive CENELEC, Intrinsic safety CENELEC, Intrinsic safety and BASEEFA, Type N SAA Flameproof (Conduit seal)(Available for 4th digit cord (“S,T,W) SAA Intrinsic safety (Available for 4th digit cord (“S,T,W) SAA Type–N (non-sparking)(Available for 4th digit cord (“S,T,W) Side vent/ drain and mounting bracket Side vent/drain Mounting bracket None None None Yes, carbon steel Specify "A", "B", or "C" for the None Yes, stainless steel 7th digit code "B", "L", or "U" Yes None Yes Yes, carbon steel Yes Yes, stainless steel
A B C D J E F G H K L P M Q S N A B C D E M N H J K P R T Q
A B C D E F
}
Y B C E M N P Q
Y W G A D N R A B A B C D E F
Stainless steel parts Stainless steel tag plate Stainless steel elec, housing Coating of cell None None None Yes None None None Yes None Yes Yes None None None Yes Yes None Yes None Yes Yes Yes Yes Yes Special applications and fill fluid Treatment Fill fluid None (standard) Silicone oil None (standard) Fluorinated oil Degreasing Silicone oil Oxygen service Fluorinated oil (7th digit code "W", "V" only) Chlorine service Fluorinated oil (7th digit code "H", "T", "B", "U") NACE specification Silicone oil (Not available for 7th digit code "T", "U" and 15th digit code "A", "B") Vacuum service Silicone oil for vacuum use Sensor O-ring Viton Teflon Bolt/nut Cr-Mo alloy hexagon socket head cap screw/carbon steel nut Cr-Mo alloy hexagon bolt/nut NACE bolt/nut (ASTM A193 B7M/A194 2HM) (*3) NACE bolt/nut (ASTM A320 L7M/A194 2HM) 304 stainless steel/304 stainless steel } (*4) (*8) 630 stainless steel/304 stainless steel } (*5)
}
}
Notes: (*3) Static pressure should be –0.1 to +10MPa{–1 to +100bar}. (*4) Available for 5th digit code "1", "2", "3". In case of stainless steel bolt with 5th digit code "3", static pressure should be –0.1 to +10MPa {–1 to + 100bar}. (*5) Available for 5th digit code "3", "4". (*6) The scale is selectable "JIS and SI unit" or "Linear and sq. root" or "Linear and sq. root by 10". (*7) Incase of FKC, specified the output mode linear or sq. root. Unless specified, the output mode is linear. In case of 9th digit code "P", "S" with FKC, specified the output indication. Unless specified, the indication is output mode. (*8) In case of tropical use, select a stainless bolts and nuts.
7
FHC, FKC...3
OUTLINE DIAGRAM (Unit:mm)
Fastener (In case of 10th digit code “B,C,M,N“) Zero/span ADJ. screw In case of 4th digit code “S,V,W,X“ Vent/drain plug (When the vent/drain plug attatched on the upper side of the detector) “A“ Press. conn. U - Bolt M8 Mtg. Pipe JIS 50A (2")
Up 43.5 110
ø80
104
126.5
Down 88 4 Holes 9 dia.
50
“B“ Conduit conn. 120 With field ind. (option) Earth terminal (both side ) see table1 51 71 (27) Cable gland (option) see note
Vent/drain plug 37 242 “C“ Conduit conn.
38 58
Detail “A“ (press conn.)
ø80 2.5 ø18.5 H
DETAIL “B“ (Conduit conn.)
ø15
Detail “C“
ø13
8
F
70 ø7 D G 1/2 see table 1 See table 1
Conduit conn. D G1/2 1/2–14NPT Pg13.5 M20x1.5 Pg13.5 E 17 16 8 16 8 F 8 5 4.5 5 4.5 Press. Conn. H Rc1/4 1/4-18NPT 1/4-18NPT 1/4-18NPT 1/4-18NPT Ovale frange screw 7/16–20UNF Screw depth 13 7/16–20UNF Screw depth 13 M10 or M12 Screw depth 13 M10 or M12 Screw depth 13 7/16–20UNF Screw depth 13 Earth Terminal M4 No.8–32UNC M4 M4 M4
270
Side vent (option) 41.3
4-M8 × 12
Oval flange screw see table1 1
L.P. 54 70 104
H.P.
4th digit code S T V W X
CONNECTION DIAGRAM
+ – CK+ CK–
+–
Note1) : Cable gand is supplied in case of flamproof packing type. ø11 cable is suitable.
S T FH CV K W X
W V H3 M T
8
17
E
Fastener (In case of 10th digit code “B,C,M,N“)
Zero/span ADJ. screw
In case of 4th digit code “S,V,W,X“
“A“ or “B“ press conn. U - Bolt M8 Oval fgange screw see table 1 Mtg.pipe JIS 50A (2")
41.3
43.5
Up
110 70 88 50
104
φ80
Down
38 “C“ Conduit conn. 120 With field ind (option) Earth terminal (both side) see table 1 51 71 (27) Cable gland (option) note see 245 Vent/drain plug “B“ Conduit conn. 40 58 4 Holes 9 dia.
(Press. conn.“) 4th digit code “S“ φ16
2 -0.1
Detail “A“
Detail “B“
4th digit code “T,V,W,X“ φ16 1/4-18NPT
10
0
φ12
φ80 1
+0.2 +0.1
φ4
273
φ4
Detail “C“
(Conduit conn.) L.P. 4-M8 × 12
H 17
Detail “D“
H.P.
φ15
φ13
54 70 104 E See table 1
4th digit code S Conduit conn. E G1/2 1/2 -14NPT Pg13.5 M20 × 1.5 Pg13.5 F 17 16 8 16 8 H 8 5 4.5 5 4.5
F
G 1/2
Oval flange screw 7/16–20UNF Screw depth 13 7/16–20UNF Screw depth 13 M10 Screw depth 13 M10 Screw depth 13 7/16–20UNF Screw depth 13 Earth terminal M4 No. 8-32UNC M4 M4 M4
CONNECTION DIAGRAM + – CK+ CK–
+–
S HCT F V2 K W X
T
B L3 U
V W X
Note) : Cable gland is supplied in case of flameproof packing type. φ11 cable is suitable.
Table 1
The product conforms to the requirements of the Electromagnetic compatibility Directive 89/336/EEC as detailed within the technical construction file number TN510412. The applicable standards used to demonstrate compliance are :EMI (Emission)
Test item Applicable Electromagnetic Radiation Disturbance
EMS (Immunity)
No. 1 2 Test item Electrostatic discharge
EN50082-1 : 1992
Test specification 8kV (Air) Basic standard IEC 801-2:1984 Performance criteria B A
EN50081-1 : 1992
Frequency range 30-1000MHz Basic standard EN55022 Class B
Radio-frequency 27-500MHz electromagnetic 3V/m IEC 801-3:1984 field. (Unmodulated) Fast transients common mode 0.5kV, 5/50 (Tr/Th) ns 5kHz Rep. IEC 801-4:1988
3
B
"LVD - The transmitter is not covered by the requirements of the LVD standard."
9