DIFFERENTIAL PRESSURE (FLOW) TRANSMITTER
DATA SHEET
The FCX–A2 differential pressure (flow) transmitter accurately measures differential pressure, liquid level, gauge pressure or flow rate and transmits a proportional 4 to 20mA signal. The transmitter utilizes a unique micromachined capacitance silicon sensor with state-of-the-art microprocessor technology to provide exceptional performance and functionality.
FKC...4
FEATURES
1. High accuracy ± 0.07% 0.07% accuracy is a standard feature. Fuji’s micro-capacitance silicon sensor assures this accuracy for all elevated or suppressed calibration ranges without additional adjustment. 2. Minimum environmental influence The “Advanced Floating Cell” design which protects the pressure sensor against changes in temperature, static pressure, and overpressure substantially reduces total measurement error in actual field applications. 3. Fuji/HART® bilingual communications protocol and FOUNDATION™ fieldbus and Profibus™ compatibility FCX–A2 series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART®. Any HART ® compatible devices can communicate with FCX–A2. Further, by upgrading electronics FOUNDATION™ fieldbus and Profibus™ are also available. 4. Application flexibility Various options that render the FCX–A2 suitable for almost any process applications include. – Analog indicator at either the electronics side or terminal side – Full range of hazardous area approvals – Built-in RFI filter and lightning arrester – 5-digit LCD meter with engineering unit – Stainless steel electronics housing – Wide selection of materials 5. Programmable output Linearization Function In addition to Linear and Square Root, output signal can be freely programmable. (Up to 14 compensated points at approximation.) 6. Burnout current flexibility (Under Scale: 3.2 to 3.8mA, Over Scale: 20.8 to 21.6mA) Burnout signal level is adjustable using Model FXW Hand Held Communicator (HHC) to comply with NAMUR NE43. 7. Dry calibration without reference pressure Thanks to the best combination of unique construction of mechanical parts (Sensor unit) and high performance electronics circuit (Electronics unit), reliability of dry calibration without reference pressure is at equal level as wet calibration.
SPECIFICATIONS
Functional specifications
Service: Liquid, gas, or vapour Static pressure, span, and range limit:
Type F KC 11 F KC 22 F KC 23 F KC 25 F KC 26 F KC 33 F KC 35 F KC 36 F KC 38 F KC 43 F KC 45 F KC 46 F KC 48 Static pressure [MPa] {bar} –0.1 to + 3.2 {–1 to + 32} –0.1 to + 10 {–1 to + 100 } –0.1 to + 10 {–1 to + 100 } –0.1 to + 10 {–1 to + 100 } –0.1 to + 10 {–1 to + 100 } –0.1 to + 16 {–1 to + 160 } –0.1 to + 16 {–1 to + 160 } –0.1 to + 16 {–1 to + 160 } –0.1 to + 16 {–1 to + 160 } –0.1 to + 42 {–1 to + 420 } –0.1 to + 42 {–1 to + 420 } –0.1 to + 42 {–1 to + 420 } –0.1 to + 30 {–1 to + 300 } Span limit [kPa] {m bar} Min. 0.1 1} 0.1 { 1} 0.32 { 3.2 } 1.3 { 13 } 5 { 50 } 0.32 { 3.2 } 1.3 { 13 } 5 { 50 } 30 { 300 } 0.32 { 3.2 } 1.3 { 13 } 5 { 50 } 30 { 300 } { { { { { { { { { { { { { { Max. 1 10 } 6 60 } 32 320 } 130 1300 } 500 5000 } 32 320 } 130 1300 } 500 5000 } 3000 30000 } 32 320 } 130 1300 } 500 5000 } 3000 30000 } Range limit [kPa] {m bar} +/– 1 { +/– 10 } +/– 6 { +/– 60 } +/– 32 { +/– 320 } +/– 130 { +/– 1300 } +/– 500 { +/– 5000 } +/– 32 { +/– 320 } +/– 130 { +/– 1300 } +/– 500 { +/– 5000 } +/– 3000 { +/– 30000 } +/– 32 { +/– 320 } +/– 130 { +/– 1300 } +/– 500 { +/– 5000 } +/– 3000 { +/– 30000 }
Remark : To minimize environmental influence, span should be greater than 1/40 of the max. span in most applications.
– Lower limit of static pressure (vacuum limit) ; Silicone fill sensor: See Fig. 1 Fluorinated fill sensor: 66kPa abs (500mmHg abs) at temperature below 60°C – The maximum span of each sensor can be converted to different units using factors as below. 1MPa =10 3KPa=10bar=10.19716kgf/cm2 =145.0377psi 1kpa=10mbar=101.9716mmH2O=4.01463inH2O
EDSX6-114j
Date Mar. 7, 2007
FKC...4
Over range limit: To maximum static pressure limit Output signal: 4 to 20mA DC (linear or square root) with digital signal superimposed on the 4 to 20mA signal Power supply: Transmitter operates on 10.5V to 45V DC at transmitter terminals. 10.5V to 32V DC for the units with optional arrester. Load limitations: see figure below
[Ω] 2000 1533Ω
Authorities ATEX
Intrinsic safety Ex II 1 GD EEx ia IIC T5 Tamb = –40°C to +40°C EEx ia IIC T4 Tamb = –40°C to +80°C Entity Parameters: Ui=28V, Ii=93.3mA, Pi=0.66W, Ci=27nF (Without Arrester), Ci=34.2nF (With Arrester), Li=1.134mH
Factory Mutual
Class I II III Div.1 Groups A, B, C, D, E, F, G T4 Entity Type 4X Model code 9th digit A,B,C,D,J L,P,M,1,2,3 Q,S,N,4,5,6 E,F,G,H,K – 13th digit Y,G,N Y,G,N Y,G,N Y,G,N W,A,D Tamb –40°C to +85°C –20°C to +80°C –20°C to +60°C –40°C to +60°C –10°C to +60°C
Load resistance
1500 1000 500 250 0 10
600Ω Operating area 24V 16.1 10.5V Power voltage 45V 50 [V]
Entity Parameters: Vmax=42.4V, Imax=113mA, Pi=1W, Ci=34.2nF, Li=1.134mH CSA Class I Div.1 Groups A, B, C, D Class II Div.1 Groups E, F, G Class III Div.1 Temp Code T4 Tamb max = +40°C Temp Code T3C Tamb max = +85°C Entity Parameters: Vmax=28V, Imax=93mA, Ci=27nF (Without Arrester), Ci=34.2nF (With Arrester), Li=1.4mH Ex ia IIC T4 Tamb max = +60°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=32.6nF, Li=1.134mH Ex ia IIC T4 IP66/67 Tamb = –40°C to +70°C Ex ia IIC T5 IP66/67 Tamb = –40°C to +50°C Entity Parameters: Ui=28V, Ii=93.3mA, Pi=0.66W, Ci=0.033µF, Li=1.034mH
Note: For communication with HHC(1) (Model: FXW), min. of 250 Ω required.
Hazardous locations:
Authorities ATEX Flameproof Ex II 2 GD EEx d IIC T6 IP66/67 T85°C Tamb = –40°C to +65°C EEx d IIC T5 IP66/67 T100°C Tamb = –40°C to +85°C Class I Div.1 Groups B, C, D T6 Type 4X Class II III Div.1 Groups E, F, G T6 Type 4X Tamb max = +60°C Class I Div.1 Groups C, D Class II Div.1 Groups E, F, G Class III Div.1 Note) “Seal Not Required” enclosure is allowed. TIIS Ex do IIB+H2 T4 Tamb max = +55°C Maximum process temp. = +120°C Ex d IIC T5 IP66/67 pending Tamb = –40°C to +85°C Ex d IIC T6 IP66/67 pending Tamb = –40°C to +65°C
TIIS
Factory Mutual
IECEx Scheme /SAA
CSA
IECEx Scheme /SAA
2
Authorities ATEX
Type n Nonincendive Ex II 3 GD EEx nL IIC T5 Tamb = –40°C to +40°C EEx nL IIC T4 Tamb = –40°C to +80°C Specific Parameters: Model without arrester: Ui=42.4V, Ii=113mA, Pi=1W, Ci=27nF, Li=1.134mH Model with arrester: Ui=32V, Ii=113mA, Pi=1W, Ci=34.2nF, Li=1.134mH EEx nAL IIC T5 Tamb = –40°C to +40°C EEx nAL IIC T4 Tamb = –40°C to +80°C Specific Parameters: Model without arrester: Umax=42.4V, Imax=113mA, Pmax=1W Model with arrester: Umax=32V, Imax=113mA, Pmax=1W
“Output Underscale”: Adjustable within the range 3.2mA to 3.8mA from HHC(1)
3.2 3.8 4 20 20.8 21.6 [mA] Over scale Burnout Normal operating range Under scale Probable under range Burnout Probable over range
Factory Mutual
Class I II III Div.2 Groups A, B, C, D, F, G T4 Entity Type 4X Model code 9th digit A,B,C,D,J L,P,M,1,2,3 Q,S,N,4,5,6 E,F,G,H,K – 13th digit Y,G,N Y,G,N Y,G,N Y,G,N W,A,D Tamb –40°C to +85°C –20°C to +80°C –20°C to +60°C –40°C to +60°C –10°C to +60°C
CSA
Class I Div.2 Groups A, B, C, D Class II Div.2 Groups E, F, G Class III Div.2 Temp Code T4 Tamb max = +40°C Temp Code T3C Tamb max = +85°C Entity Parameters: Vmax=28V, Ci=27nF (Without Arrester), Ci=34.2nF (With Arrester), Li=1.4mH –
TIIS
Loop-check output: Transmitter can be configured to provide constant signal 3.8mA through 21.6mA by HHC(1). Temperature limit: Ambient: – 40 to +85°C (–20 to +80°C for LCD indicator) (– 40 to +60°C for arrester option) (–10 to +60°C for fluorinated oil filled transmitters) For explosionproof units (flameproof or intrinsic safety), ambient temperature must be within the limits specified in each standard. Process: – 40 to +120°C for silicone fill sensor –20 to +80°C for fluorinated oil fill sensor Storage: – 40 to +90°C Humidity limit: 0 to 100% RH Communication: With HHC(1) (Model FXW, consult Data Sheet No. EDS8-47), following information can be remotely displayed or reconfigured. Note: HHC’s version must be more than 6.0 (or FXW 1– 3), for FCXA2.
Items Tag No. Model No. Serial No. Engineering unit Range limit Measuring range Damping Output mode Linear Square root Burnout direction Calibration Output adjust Data Self diagnoses Printer External switch lock Transmitter display Linearize Rerange Display v v v v v v v v v v v — v v — v v v v Set v v — v — v v v v v v v — — — v v v v
IECEx Scheme /SAA
–
Zero/span adjustment: Zero and span are adjustable from the HHC(1). Zero and span are also adjustable externally from the adjustment screw (span adjustment is not available with 9th digit code “L, P, M, Q, S, N”). Damping: Adjustable from HHC or local adjustment unit with LCD display. The time constant is adjustable between 0.12 to 32 seconds. Zero elevation/suppression: –100% to +100% of URL Normal/reverse action: Selectable from HHC(1) Indication: Analog indicator or 5-digit LCD meter, as specified. Burnout direction: Selectable from HHC(1) If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale” or “Output Underscale” modes. “Output Hold”: Output signal is hold as the value just before failure happens. “Output Overscale”: Adjustable within the range 20.8mA to 21.6mA from HHC(1)
Programmable output linearization function: Output signal can be characterized with “14 points linear approximation function” from HHC(1). EMC Conformity: EN61326
(Note) (1) HHC: Hand Held Communicator
3
FKC...4
Performance specifications for linear output
Reference conditions, silicone oil fill, 316SS isolating diaphragms, 4 to 20mA analog output in linear mode.
Performance specifications for square root output
Accuracy rating:
Span Output 50 to 100% 20 to 50% 10 to 20% over 0.1 × URL ± 0.07 % ± 0.175 % ± 0.35 % below 0.1 × URL ± (0.02+0.05 × 0.1 × URL/Span)% ± 2.5 × (0.02+0.05 × 0.1 × URL/Span)% ± 5 × (0.02+0.05 × 0.1 × URL/Span)%
Accuracy rating: (including linearity, hysteresis, and repeatability) Max span above 32kPa model: For spans greater than 1/10 of URL: ± 0.07% of span For spans below 1/10 of URL: 0.1 × URL ± 0.02+0.05 % of span Span Max span 1kPa, 6kPa model: For spans greater than 1/10 of URL: ± 0.1% of span For spans below 1/10 of URL: 0.1 × URL ± 0.05+0.05 % of span Span Stability: ± 0.1% of upper range limit (URL) for 3 years for 6th digit code 3, 5, 6, 8. Temperature effect: Effects per 28°C change between the limits of – 40°C and +85°C
( (
) )
Max span 1kPa, 6kPa model:
Output 50 to 100% 20 to 50% 10 to 20% Accuracy ± 0.1 % ± 0.25% ± 0.5 %
Temperature effect: Effects per 55°C change between the limits of – 40°C and +85°C
Range code Shift at 20% output point URL ± 0.375+0.25 Span %/28°C URL ± 0.24+0.03125 Span %/28°C
Range code (6th digit in Code symbols) “1”/1kPa {10mbar} max. span “2”/6kPa {60mbar} max. span
“1” and “2”
Zero shift Total effect
(
)
“3” through “8”
URL % Span
(
)
± 0.125+0.1
(
URL % Span
)
± 0.15+0.1
(
)
Low flow cut-off: Customer configurable for any point between 0 to 20% of output
“3”/32kPa {320mbar} max. span “5”/130kPa {1300mbar} max. URL URL span % ± 0.075+0.0125 % ± 0.095+0.0125 Span Span “6”/500kPa {5000mbar} max. span “8”/3000kPa {30000mbar} max. span
(
)
(
)
Static pressure effect:
Static pressure code (5th digit in Code symbols) “1” /1kPa {10m bar} sensor “2” /6kPa {60 m bar} sensor “2” “3” “4” Zero shift (% of URL) ± 0.2% / 1MPa{10bar} ± 0.2% / 3.2MPa{32bar} ± 0.05%/10MPa{100bar}
Supply voltage effect: Less than 0.005% of calibrated span per 1V RFI effect: Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength 30 V/m when electronics covers on. (Classification: 2-abc: 0.2% span per SAMA PMC 33.1) Update period: 120 msec *) Step response: (without electrical damping)
Range code (6th digit in code symbols) “1” “2” “3” “5” through “8” Time constant*) 0.8 s 0.5 s 0.3 s 0.2 s 0.2 s Dead time*)
Overrange effect:
Static pressure code (5th digit in Code symbols) “1” / 1kPa{10m bar} sensor “2” / 6kPa{60m bar} sensor “2” “3” “4” Zero shift (% of URL) ± 0.3% / 1MPa ± 0.1% / 3.2MPa ± 0.1% /10MPa ± 0.1% /16MPa ± 0.25% /42MPa {10bar } {32bar } {100bar } {160bar } {420 bar}
*) Faster response is available as option (maximum update rate: 25 times per second).
Mounting position effect: Zero shift, less than 0.12kPa {1.2m bar} for a 10° tilt in any plane. No effect on span. This error can be corrected by adjusting Zero. Dielectric strength: 500V AC, 50/60Hz 1 min., between circuit and earth. Insulation resistance: More than 100MΩ at 500V DC. Turn-on time: 4 sec. Internal resistance for external field indicator: 12Ω or less
4
Physical specifications
Electrical connections: G1/2, 1/2-14 NPT, Pg13.5, or M20 × 1.5 conduit, as specified. And 1 conduit or 2 conduits, as specified. Process connections: 1/4-18 NPT or Rc1/4 on 54mm centers, as specified. Meets DIN 19213. Process-wetted parts material:
Material code (7th digit Process cover in Code symbols) V H J 316 stainless steel(*1) 316 stainless steel(*1) 316 stainless steel(*1) Wetted sensor body
Optional features
Indicator: A plug-in analog indicator (2.5% accuracy) can be housed in the electronics compartment or in the terminal box of the housing. An optional 5-digit LCD meter with engineering unit is also available. Local adjustment unit with LCD display: An optional 5-digit LCD meter with Zero/ Span adjustment function, loop-check function and damping adjustment function, is available. Arrester: A built-in arrester protects the electronics from lightning surges. Lightning surge immunity: 4kV (1.2 × 50µs) Oxygen service: Special cleaning procedures are followed throughout the process to maintain all process wetted parts oil-free. The fill fluid is fluorinated oil. Chlorine service: The fill fluid is fluorinated oil. Degreasing: Process-wetted parts are cleaned, but the fill fluid is standard silicone oil. Not for use on oxygen or chlorine measurement. NACE specification: Metallic materials for all pressure boundary parts comply with NACE MR-01-75. ASTM B7M or L7M bolts and 2HM nuts (Class II) are available. Static pressure rating for code “3” (16 MPa) is degraded to 10MPa. Vacuum service: Special silicone oil and filling procedure are applied. See Fig. 1. Optional tag plate: An extra stainless steel tag with customer tag data is wired to the transmitter. Coating of cell: Cell’s surface is finished with epoxy/ polyurethane double coating. Specify if environment is extremely corrosive.
Silicone oil (Code:Y,G,N) Silicone oil (Code:R) [kPa abs] {mbar abs} 101 {1010} Operating pressure
Diaphragm
Vent/drain
316L stainless 316 stainless steel steel Hastelloy-C Hastelloy-C lining 316L stainless 316 stainless steel steel +Au coating Monel Tantalum Monel lining Tantalum lining Hastelloy-C lining Monel lining Tantalum lining
316/316L stainless steel 316/316L stainless steel 316/316L stainless steel
M T
316 stainless steel(*1) 316 stainless steel(*1) Hastelloy-C lining Monel lining Tantalum lining
316/316L stainless steel 316/316L stainless steel Hastelloy-C Monel Hastelloy-C
B L U
Hastelloy-C Monel Tantalum
Note: (*1) SCS14A per JIS G 5121 (equivalent CF8M per ASTM A351/A351M) Remarks: Sensor O-rings: Viton O-ring and teflon gasket selectable. Availability of above material design depends on ranges and static pressure. Refer to “Code symbols”.
Non-wetted parts material: Electronics housing: Low copper die-cast aluminum alloy finished with epoxy/ polyurethane double coating (standard), or 316 stainless steel (SCS14A per JIS G5121), as specified. Bolts and nuts: Cr-Mo alloy (standard), 304 stainless steel (for static pressure code “1”, “2”, and “3” only), or 630 stainless steel (for static pressure code “3” and “4” only). Static pressure rating for code “3” with 304 stainless steel bolts is degraded to 10MPa. Fill fluid: Silicone oil (standard) or fluorinated oil Mounting bracket: 304 stainless steel Environmental protection: IEC IP67 and NEMA 6/6P Mounting: On 60.5mm(JIS 50A) pipe using mounting bracket, direct wall mounting, or direct process mounting. Mass{weight}: Transmitter approximately 4.4kg without options. Add; 0.5kg for mounting bracket 0.8kg for indicator option 4.5kg for stainless steel housing option
20 {200}
Operating area
4 {40} 2.7 {27} –40
None-operating area –15 60 85 120 Process temperature[°C ]
Fig. 1 Relation between process temperature and operating pressure
5
FKC...4
ACCESSORIES
Oval flanges: (Model FFP, refer to Data Sheet No. EDS6-10) Converts process connection to 1/2 -14 NPT or to Rc1/2; in carbon steel or in 316 stainless steel.
ORDERING INFORMATION
When ordering this instrument, specify: 1. CODE SYMBOLS 2. Measuring range 3. Output orientation (burnout direction) when abnormality is occurred in the transmitter. Hold / Overscale (21.6mA) / Underscale (3.2mA) Unless otherwise specified, output hold function is supplied. 4. Output mode (linear or square root output) Unless otherwise specified, output mode is linear. 5. Indication method (indicated value and unit) in case of the actual scale (code D, H, P, S on 9th digit). 6. Tag No. (up to 26 alphanumerical characters), if required.
Equalizing valves: (Model FFN, refer to Data Sheet No. EDS6-10) Available in Carbon steel or in 316 stainless steel and in pressure rating 16MPa or 42MPa. Hand-held communicator: (Model FXW, refer to Data Sheet No. EDS 8-47) Z/S board: Parts No.=ZZPFCX4-A070 When Z/S board is mounted on the FCX– A2 a mplifier unit, external adjustment screw will be available for zero and span adjustment.
6
CODE SYMBOLS
Oval flange Conduit Process connection connection screw 7/16-20UNF G1/2 (×1) Rc1/4 7/16-20UNF 1/2-14NPT (×1) 1/4-18NPT Combination with 12th 1/4-18NPT M10 (or M12)(*1) Pg 13.5 (×1) digit code "C, E, P, Q" 1/4-18NPT M10 (or M12)(*1) M20×1.5 (×1) are not available. 7/16-20UNF 1/4-18NPT Pg 13.5 (×1) 7/16-20UNF G1/2 (×2) Rc1/4 7/16-20UNF 1/2-14NPT (×2) 1/4-18NPT 1/4-18NPT M10 (or M12)(*1) Pg 13.5 (×2) 1/4-18NPT M10 (or M12)(*1) M20×1.5 (×2) 7/16-20UNF 1/4-18NPT Pg 13.5 (×2) 5, 6, 7 Static Span limit (*2) Process Diaphragm Wetted pressure cover cell body [MPa] [kPa] {bar} (m bar) –0.1 to 0.1…1 316 stainless steel 316L stainless steel 316 stainless steel +3.2 {1…10} 316 stainless steel 316L stainless steel 316 stainless steel {–1 to+32} +Au coating 316 stainless steel Hast. C Hast. C lining –0.1 to+10 0.1…6 316 stainless steel 316L stainless steel 316 stainless steel {–1 to 100} {1…60} 316 stainless steel 316L stainless steel 316 stainless steel +Au coating 316 stainless steel Hast. C Hast. C lining –0.1 to+16 0.32…32 316 stainless steel 316L stainless steel 316 stainless steel {–1 to+160} {3.2…320} 316 stainless steel 316L stainless steel 316 stainless steel +Au coating 316 stainless steel Hast. C Hast. C lining 316 stainless steel Monel Monel lining 316 stainless steel Tantalum Tantalum lining 316 stainless steel 316L stainless steel 316 stainless steel 1.3…130 {13…1300} 316 stainless steel 316L stainless steel 316 stainless steel +Au coating 316 stainless steel Hast. C Hast. C lining 316 stainless steel Monel Monel lining 316 stainless steel Tantalum Tantalum lining 316 stainless steel 316L stainless steel 316 stainless steel 5…500 {50…5000} 316 stainless steel 316L stainless steel 316 stainless steel +Au coating 316 stainless steel Hast. C Hast. C lining 316 stainless steel Monel Monel lining 316 stainless steel Tantalum Tantalum lining 316 stainless steel 316L stainless steel 316 stainless steel 30…3000 {300…30000} 316 stainless steel 316L stainless steel 316 stainless steel +Au coating –0.1 to+42 0.32…32 316 stainless steel 316L stainless steel 316 stainless steel {–1 to+420} {3.2…320} 316 stainless steel 316L stainless steel 316 stainless steel +Au coating 316 stainless steel Hast. C Hast. C lining 316 stainless steel Monel Monel lining 316 stainless steel 316L stainless steel 316 stainless steel 1.3…130 {13…1300} 316 stainless steel 316L stainless steel 316 stainless steel +Au coating 316 stainless steel Hast. C Hast. C lining 316 stainless steel Monel Monel lining 316 stainless steel 316L stainless steel 316 stainless steel 5…500 {50…5000} 316 stainless steel 316L stainless steel 316 stainless steel +Au coating 316 stainless steel Hast. C Hast. C lining 316 stainless steel Monel Monel lining –0.1 to+30 30…3000 316 stainless steel 316L stainless steel 316 stainless steel {–1 to+300} {300…30000} 316 stainless steel 316L stainless steel 316 stainless steel +Au coating –0.1 to+10 0.32…32 Hast. C lining Hast. C Hast. C lining {–1 to+100} {3.2…320} Monel lining Monel Monel lining Tantalum lining Tantalum Tantalum lining 1.3…130 Hast. C lining Hast. C Hast. C lining {13…1300} Monel lining Monel Monel lining Tantalum lining Tantalum Tantalum lining 5…500 Hast. C lining Hast. C Hast. C lining {50…5000} Monel lining Monel Monel lining Tantalum lining Tantalum Tantalum lining Digit 4 Description Note
12345678
9 10 11 12 13
14 15
21
FKC
4
Digit No. of code
Note 1 Note 1
Note 1 Note 1
A B C D E S T V W X
Note 2
11V 11J 11H 22V 22J 22H 33V 33J 33H 33M 33T 35V 35J 35H 35M 35T 36V 36J 36H 36M 36T 38V 38J 43V 43J 43H 43M 45V 45J 45H 45M 46V 46J 46H 46M 48V 48J 23B 23L 23U 25B 25L 25U 26B 26L 26U
Note 1: (*1) The thread is M12, if 42MPa {420bar} static pressure is specified. Note 2: (*2) 100: 1 turn down is possible, but should be used at the span greater than 1/40 of the maximum span for better performance.
7
FKC...4
12345678
9 10 11 12 13
14 15
21
Digit 9
Description
Note
FKC
4
Digit No. of code
10
11
12
13
14
Indicator Arrester None None Analog, 0 to 100% linear scale None Note 3 Analog, 0 to 100% sq. root scale None (*3) Z/S board Analog, custom scale None attached. Analog, double scale (Linear and sq. root) None None Yes Analog, 0 to 100% linear scale Yes Note 3 Analog, 0 to 100% sq. root scale Yes (*3) Analog, custom scale Yes Analog, double scale (Linear and sq. root) Yes Digital, 0 to 100% None Digital, custom scale None Digital 0 to 100% square root None Digital, 0 to 100% Yes Digital, custom scale Yes Digital 0 to 100% square root Yes Digital, 0 to 100% (Local adjustment unit with LCD display) None Digital, custom scale (Local adjustment unit with LCD display) None Digital, 0 to 100% square root (Local adjustment unit with LCD display) None Digital, 0 to 100% (Local adjustment unit with LCD display) Yes Digital, custom scale (Local adjustment unit with LCD display) Yes Digital, 0 to 100% square root (Local adjustment unit with LCD display) Yes None (for ordinary locations) TIIS, Flameproof (Conduit seal) (Available for 4th digit code “A“, “S“) TIIS, Flameproof (Cable gland seal) (Available for 4th digit code “A“, “S“) FM, Flameproof (or explosionproof) (Available for 4th digit code “B“, “T“) CSA, Flameproof (or explosionproof) (Available for 4th digit code “B“, “T“) ATEX, Flameproof IECEx Scheme/SAA, Flameproof (Approval pending) TIIS, Intrinsic safety FM, Intrinsic safety and Nonincendive CSA, Intrinsic safety and Nonincendive ATEX, Intrinsic safety ATEX, Type n IECEx Scheme/SAA, Intrinsic safety FM, Combined of Flameproof and Intrinsic safety Vent/drain Mounting bracket Standard None Specify “A” or “C” for the 7th Standard Yes, stainless steel digit code “B”, “L”, or “U” Side None Side Yes, stainless steel Extra SS tag plate Stainless steel elec, housing Coating of cell Note 4 None None None Yes None None None Yes None Yes Yes None (*4) None None Yes Yes None Yes None Yes Yes Yes Yes Yes Treatment Fill fluid Standard Silicone oil Standard Fluorinated oil Degreasing Silicone oil Oxygen service Fluorinated oil (7th digit code “V”, “J” only) Chlorine service Fluorinated oil (7th digit code “H”, “T”, “B”, “U”) NACE specification Silicone oil (Not available for 7th digit code “T”, “U” and 15th digit code “A”, “B”) Vacuum service Silicone oil for vacuum use Viton (O-ring) Teflon (gasket)
A B C D J E F G H K L P M Q S N 1 2 3 4 5 6
A B C D E X R G H J K P T V
A C D F
Y B C E M N P Q
Y W G A D N R A B
Note 3: (*3) In case of square root output mode, square root scale is not available. Note 4: (*4) Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required, select “Yes”.
8
12345678
9 10 11 12 13
14 15
21
Digit 15
Description (*8) Cr-Mo alloy hexagon socket head cap screw/carbon steel nut Cr-Mo alloy hexagon bolt/nut NACE bolt/nut (ASTM A193 B7M/A194 2HM) (*5) NACE bolt/nut (ASTM A320 L7M/A194 2HM) 304 stainless steel bolt/304 stainless steel nut (*6) 630 stainless steel bolt/304 stainless steel nut (*7) (*9) Instruction manual unattached
Note Note 8
FKC
4 A B C D E F L
Digit No. of code
Note 5 Note 6 Note 7 Note 9
21
Note 5: (*5) Static pressure should be –0.1 to +10MPa{–1 to +100bar}. Note 6: (*6) Available for 5th digit code “1”, “2”, “3”. In case of stainless steel bolt with 5th digit code “3”, static pressure should be –0.1 to +10MPa {–1 to + 100bar}. Note 7: (*7) Available for 5th digit code “3”, “4”. Note 8: (*8) In case of tropical use, select stainless bolts and nuts. Note 9: (*9) If other option is not necessary, 21st digit code is blank. In case of 21st digit code is blank, instruction manual attached.
9
FKC...4
OUTLINE DIAGRAM (Unit:mm)
< 7th digit code : V, H, M, T, J >
Note 2)
Vent/drain plug (When the vent/drain plug attatched on the upper side of the detector) MTG. pipe JIS 50A (2B) "A" Press. conn.
In case of 4th digit code "A.B.C.D.E" In case of 4th digit code "S.V.W.X" In case of 4th digit code "T" Fastener (Flameproof only)
94.5
8
10
Up
Zero ADJ. screw
130 120 43.5
ø80
105
105
52.5
Down
41
58 4 Holes 9 Dia. U-bolt M8
37 210 Vent/drain plug With field ind. (27) "B" Conduit conn.
88
38
Note 1)
Cable gland (option) "C" Conduit conn.
154 Detail "A" (Press. conn.) ø18.5 H Detail "B" (Conduit conn.) ø15 Detail "C" ø13 Earth terminal 59 43
2.5
ø80
Electronics unit
70
8
Oval flange screw See table 1
F
E
See table 1
See table 1
Press.conn. (Low pressure side)
4th digit of the code symbols 3, 4, A, S B, T C, V D, W E, X Conduit conn. E F D G1/2 17 8 5 4.5 5 4.5 Press. conn. H Rc1/4 1/4-18NPT 1/4-18NPT 1/4-18NPT 1/4-18NPT Oval flange screw 7/16-20UNF SCREW DEPTH15 7/16-20UNF SCREW DEPTH15 M10 SCREW DEPTH15 M10 SCREW DEPTH15 7/16-20UNF SCREW DEPTH15
4-M8 12
Press.conn. (High pressure side)
1/2-14NPT 16 Pg13.5 M20 1.5 8 16 8
54 70 104
Pg13.5
TABLE 1
CONNECTION DIAGRAM
CK CK
Note 1) Cable gland is supplied in case of flamproof packing type. ø11 cable is suitable. Note 2) The pressure connector is located on the down side surface of the detector, when the vent/drainplug is attatched on the upper side of the detector (when the 21th digit of the code symbols: c, e or d).
10
41.3
Side vent (option)
231
ø7
D
G 1/2
17
Sensor unit
< 7th digit code : B, L, U >
Oval flange screw See table 1 In case of 4th digit code "A.B.C.D.E" MTG. pipe JIS 50A (2B) "A"or"B" Press. conn. In case of 4th digit code "T" U-bolt M8 41.3 Fastener (Flameproof only) In case of 4th digit code "S.V.W.X"
94.5
10
Up
8
Zero ADJ. screw
105
ø80
52.5
Down
41
88
38 4 Holes 9 Dia. 58 40 213 Vent/drain plug (27)
Note 1)
Cable gland (option) "C" Conduit conn. "D" Conduit conn.
With field ind. 186 43
120
Detail "A" Detail "C" (Press. conn.) (Conduit conn.) 4TH DIGIT CODE "A, S" ø16 ø15
+0.2 ø12 +0.1
Detail "D" Earth terminal ø13
91
ø80
Electronics unit
2 -0.1
1
0
H
F
17
105
70
234
G 1/2 Press.conn. (Low pressure side) 4-M8 12 Press.conn. (High pressure side)
Conduit conn. E F H G1/2 1/2-14NPT Pg13.5 M20 1.5 Pg13.5 17 16 8 16 8 8 5 4.5 5 4.5 Oval flange screw 7/16-20UNF SCREW DEPTH10 7/16-20UNF SCREW DEPTH10 M10 SCREW DEPTH10 M10 SCREW DEPTH10 7/16-20UNF SCREW DEPTH10
ø4
E See table 1
Sensor unit
Detail "B" (Press. conn) 4TH DIGIT CODE "B, C, D, E, T, V, W, X" ø16 1/4-18NPT
4th digit of the code symbols 3, 4, A, S B, T C, V
10
54 70 104
CONNECTION DIAGRAM
CK CK
ø4
D, W E, X
TABLE 1
Note 1) Cable gland is supplied in case of flamproof packing type. ø11 cable is suitable.
11
FKC...4
The product conforms to the requirements of the Electromagnetic compatibility Directive 94/9/EC as detailed within the technical construction file number TN513035. The applicable standards used to demonstrate compliance are : EMI (Emission)
Frequency range MHz 30 to 230 230 to 1000
EN61326 : 1997 Class A (standard for Industrial Location)
Limits 40dB (µV/m) quasi peak, measured at 10m distance 47dB (µV/m) quasi peak, measured at 10m distance Reference standard CISPR16-1 and CISPR16-2
EMI (Immunity)
Phenomenon Electrostatic discharge
EN61326: 1997 Annex A (standard for Industrial Location)
Test value Basic standard EN61000-4-2 Performance criteria B
4kV (Contact) 8kV (Air)
80 to 1000MHz Electromagnetic 10V/m field 80%AM (1kHz) Rated power frequency magnetic field Burst 30A/m 50Hz 2kV 5kHz 1.2µs/50µs 1kV (Line to line) 2kV (Line to ground) 0.15 to 80MHz 3V 80%AM (1kHz)
EN61000-4-3
A
EN61000-4-8
A
EN61000-4-4
B
Surge
EN61000-4-5
B
Conducted RF
EN61000-4-6
A
Note) Definition of performance criteria A: During testing, normal performance within the specification limits. B: During testing, temporary degradation, or loss of function or performance which is self-recovering.
Caution on Safety *Before using this product, be sure to read its instruction manual in advance.
Head Office
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fesys.co.jp/eng
Instrumentation Div. International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http://www.fic-net.jp/eng
Information in this catalog is subject to change without notice.
Printed in Japan