7200 SERIES QZU-EZU-EZD-EZA (-L) QUAD/EIGHT ZONE UNITS EIGHT ZONE DAUGHTER/ ANNUNCIATOR BOARDS QZU-L EZU-L EZD-L EZA-L DESCRIPTION The Quad Zone Unit (QZU-L) provides the 7200 Series Fire Alarm Control Panel with four (4) Class A, Style D or Class B, Style B conventional, hard-wired, zone initiating circuits. Each circuit is field programmable for waterflow detection/supervisory monitoring on a common multi-level detection circuit. Each circuit also provides verification capability for two-wire smoke detectors. The Eight Zone Unit (EZU-L) is similar to the Quad Zone Unit (QZU-L), except it provides eight (8) Class B, Style B conventional zone initiating circuits. Class A, Style D wiring return connections are made to the optional Eight Zone Daughter Board (EZD-L) which contains end of line devices and is mounted between the backboard and its associated EZU-L. The QZU-L initiating circuits each contain a red “ALARM” LED and a yellow “TROUBLE” LED, along with a supervised, power limited LED annunciator output for each zone. The EZU-L likewise contains “ALARM” and “TROUBLE” LEDs, while supervised power limited annunciator output from the EZU-L circuits is available via an associated Eight Zone Daughter board (EZD-L), or Eight Zone Annunciator board (EZA-L). The EZA-L does not contain Class A circuitry. Each initiating circuit also incorporates a zone “DISCONNECT” user switch, for individual initiating circuit control and programming functions. The QZU-L and EZU-L will accommodate FCI Approved, UL Listed, compatible two-wire smoke detectors. See the FCI Addendum, P/N 9000-0427 for a list of detectors and quantities that can be accommodated per circuit. Pluggable terminal blocks are provided with each unit for the connection of field wiring. These blocks will accommodate wire sizes up to 12 AWG. The QZU-L and EZU-L each occupy a full-unit size space in the cabinet, and mount in any available module position below the SCU System Control Unit. TECHNICAL AND ORDERING INFORMATION Part No. 1120-0575 1120-0576 1120-0579 1120-0580 Model QZU-L EZU-L EZD-L EZA-L Supervisory Current .027 amp. .045 amp. .002 amp. .002 amp. Alarm Current .062 amp. .086 amp. .009 amp. .009 amp. Description Quad Zone Unit Eight Zone Unit Eight Zone Daughter Board Eight Zone Annunciator Board Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice. © 1997 All Rights Reserved 16 Southwest Park, Westwood, MA 02090 USA TEL: (781) 471-3000 FAX: (781) 471-3099 An ISO 9001 Certified Company 9020-0293/Ver. 1.5
1120-0576
1. 物料型号: - QZU-L(四区单元) - EZU-L(八区单元) - EZD-L(八区女儿板) - EZA-L(八区报警器板)

2. 器件简介: - QZU-L提供4个A类D型或B类B型的常规硬连线区域启动电路,每个电路都可以现场编程用于水流检测/监控。 - EZU-L类似于QZU-L,但提供8个B类B型常规区域启动电路。 - EZD-L是EZU-L的可选配件,包含终端设备,用于A类接线返回连接。 - EZA-L不包含A类电路,用于EZU-L电路的监控功率限制报警器输出。

3. 引脚分配: - 每个启动电路都包含一个“ALARM”红色LED和一个“TROUBLE”黄色LED,以及每个区域的监控、功率限制LED报警器输出。 - EZU-L的监控功率限制报警器输出可通过EZD-L或EZA-L获得。

4. 参数特性: - QZU-L:监控电流0.027安培,报警电流0.062安培。 - EZU-L:监控电流0.045安培,报警电流0.086安培。 - EZD-L:监控电流0.002安培,报警电流0.009安培。 - EZA-L:监控电流0.002安培,报警电流0.009安培。

5. 功能详解: - QZU-L和EZU-L可以容纳FCI批准的、UL列表兼容的双线烟雾探测器。 - 提供可插拔端子块,用于现场布线连接,可适应高达12AWG的线径。

6. 应用信息: - QZU-L和EZU-L各占用一个全单元大小的空间,并安装在SCU系统控制单元下方的任何可用模块位置。