70896-02

70896-02

  • 厂商:

    GAMEWELL-FCI

  • 封装:

  • 描述:

    70896-02 - Analog Addressable Duct Smoke Detectors - Gamewell-FCI by Honeywell

  • 详情介绍
  • 数据手册
  • 价格&库存
70896-02 数据手册
XP95-PD/-PDR, XP95-ID/-IDR Description The Gamewell-FCI analog addressable duct smoke detectors provide early detection of smoke and products with combustion present in air moving through an HVAC duct. Fans, blowers and complete systems may be shut down or activated in fire alarm mode by the Fire Alarm Control Panel (FACP) in the event of smoke detection. The Gamewell-FCI analog addressable duct smoke detectors may utilize either interchangeable photoelectric or ionization sensor heads. The external alarm indication is a light-emitting diode (LED), easily visible through the housing. A manual reset switch is provided on the front of the sensor. Duct smoke detectors are also available with auxiliary relay contacts. The relay requires two additional wires for power and will activate when the sensor reaches alarm levels. All wiring must comply with local codes and regulations. XP95 Duct Smoke Detectors digitally transmit their address and the chamber’s analog value to the FACP for analysis. Air sampling is accomplished by two tubes which protrude into the duct. An exhaust tube of one standard length 7.5" (19.05 cm) is provided with the sensor housing. Intake sampling tubes, which must be ordered separately, are supplied in three standard lengths: 2.5, 5, or 10 feet (0.762, 1.524, or 3.048 m). Analog Addressable Duct Smoke Detectors Features • • • • • • • • • • • • • XP95 Series Installation Duct mounting is accomplished by the use of a template and four sheet metal screws, provided. The duct detectors are compatible with the analog loops on Gamewell-FCI’s 600 Series Analog Addressable Control Panels. Compatible with the Gamewell-FCI 600 Series analog addressable control panels Interchangeable “Plug-in” photoelectric or ionization heads Address is stored in the sensor base Address is set by XPert addressing card Remote alarm LED option Two-wire supply- polarity insensitive Very low standby current LED alarm indication on sensor head Rugged steel backbox with clear plastic cover Large terminal connection screws No additional screens or filters to clean or replace Relay version available with optional remote test unit Three standard tube lengths available: 2.5, 5, or 10 ft. (0.762, 1.524, or 3.048 m) Programming The only programming required for the XP95 Duct Smoke Sensors is address setting. This is accomplished through the use of the XPert addressing card which is inserted into the sensor base. An ISO 9000-2000 Company SIGNALING FM 268A APPROVED MEA Approved 73-92-E 3242-1004:103 (photo) 3242-1004:102 (ion) Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. www.gamewell-fci.com CS-2049 Rev. a1 page 1 of 2 ©2007 by Honeywell International Inc. All rights reserved. 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 GAMEWELL-FCI CS-2049ph1.wmf Programming (Continued) When the sensor head is inserted into the base, the address is automatically relayed to the sensor. Changing the sensor does not require additional programming since the address remains on the XPert card located in the base. All other sensor-specific programming is accomplished at the FACP. Specifications (Continued) Relay Versions Only: Relay Contacts: Two dry Form-C contacts Relay Contact Ratings: 10 A @ 24 VDC resistive maximum Operating Voltage: 24 VDC Current: Standby current: 0.010 A @ 24 VDC Alarm current: 0.055 A @ 24 VDC Engineer’s Specifications The contractor shall furnish and install, where indicated on the plans, analog addressable air duct smoke detectors. The sensors shall be listed by Underwriter’s Laboratories per UL 268A and UL-Listed as compatible with the Fire Alarm Control Panel (FACP). The sensors shall operate at air velocities from 300 to 4,000 feet (91.44 to 1219.20 m) per minute. The smoke sensor shall contain an integral LED that shall latch in when the unit goes into alarm, mounted at a 30° slant to provide a wide viewing angle. A manual reset/test switch shall be located on the front of the device. The housing shall contain a sensor base which will accept photoelectric or ionization heads. All wiring must comply with local codes and regulations. The duct sensor housing shall have a metal chassis with a clear plastic cover and complete mechanical installation may be performed without removal of the cover. The duct smoke detector shall be the Gamewell-FCI model, XP95-ID(R) or XP95-PD(R) analog addressable duct smoke detector. Ordering Information Description Two-wire air duct, ionization smoke detector 24 VDC (RW-AAN) XP95-PD Two-wire air duct, photoelectric smoke detector 24 VDC (RW-AAP) 30203-01 Remote LED alarm indicator (two VDCs); used with XP95-PD and XP95-ID XP95-IDR Four-wire air duct, ionization smoke detector 24 VDC with relay (RW-ARN) XP95-PDR Four-wire air duct, photoelectric smoke detector 24 VDC with relay (RW-ARP) 30203 Remote LED alarm indicator (24 VDCs); used with relay versions 30007-02 Remote test station with alarm LED; used with relay versions 70896-02 Sampling tube, 2.5 feet (0.762 m) 70896-05 Sampling tube, 5 feet (1.524 m) 70896-10 Sampling tube, 10 feet (3.048 m) XP95-I Ionization sensor head (replacement) XP95-P Photoelectric sensor head (replacement) 72247 Duct detector enclosure (WP-1) (See Data Sheet CS-2308). Model XP95-ID Specifications Ambient Temperature: 32° F to 120°F (0°C to 49°C) Humidity: 10% to 85% R.H Material: 18 gauge steel backbox, clear plastic cover Dimensions: 10.0" H x 8.25" W x 2.25" D (25.4 H x 21.0 W x 5.7 D cm) Maximum Net Weight: 4.0 lbs. (1.814 kg) Mounting: Template and necessary hardware supplied Radioactive Element: For Ionization versions only: Americium 241 (0.9 microcuries) Sensitivity: Factory set (ion); or adjustable via the IF600 control panel (photoelectric) Air Velocity: 300 to 4,000 feet per minute. Pressure Differential: 0.01 to 1.2 inches (1.524 to 20.320 meters per second) of water Standby Current: Photoelectric: 340 µA Ionization: 280 µA Alarm LED Current: Photoelectric: 4 mA Ionization: 2 mA Remote Alarm Output 20 mA maximum; diode gated Range: 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 CS-2049 Rev. a1 page 2 of 2 www.gamewell-fci.com GAMEWELL-FCI
70896-02
### 物料型号 - XP95-ID: 两线空气管道式离子烟雾探测器 - XP95-PD: 两线空气管道式光电烟雾探测器 - XP95-PDR: 四线空气管道式光电烟雾探测器,带有继电器

### 器件简介 Gamewell-FCI模拟地址编码式管道烟雾探测器提供早期烟雾和燃烧产物的检测。当检测到烟雾时,可通过火警控制面板(FACP)关闭或激活风扇、鼓风机和完整的系统。这些探测器可以使用可更换的光电或离子传感器头,外部报警指示为LED灯,手动复位开关位于传感器前部。

### 引脚分配 - XP95-ID/PD: 两线供电,极性不敏感 - XP95-PDR: 四线,包括两线供电和两线继电器

### 参数特性 - 环境湿度: 10%至85% R.H - 环境温度: 32°F至120°F (0°C至49°C) - 材料: 18号钢背盒,透明塑料盖 - 尺寸: 10.0" H x 8.25" W x 2.25" D (25.4 Hx21.0 Wx5.7 D cm) - 最大净重: 4.0 lbs. (1.814 kg) - 空气流速: 300至4,000英尺/分钟 - 待机电流: 光电型为340μA,离子型为280μA - 报警LED电流: 光电型为4mA,离子型为2mA

### 功能详解 XP95系列烟雾探测器通过数字方式传输其地址和腔室的模拟值至火警控制面板进行分析。采样通过两个伸入管道的管道完成。探测器兼容Gamewell-FCI的600系列模拟地址编码控制面板。

### 应用信息 适用于需要早期检测烟雾和燃烧产物的HVAC管道系统。通过火警控制面板在检测到烟雾时可以关闭或激活风扇、鼓风机和完整的系统。

### 封装信息 - 安装: 使用模板和四个金属板螺丝安装 - 管径: 需要单独订购,提供三种标准长度:2.5英尺、5英尺或10英尺