72198

72198

  • 厂商:

    GAMEWELL-FCI

  • 封装:

  • 描述:

    72198 - Analog addressable manual pull station - Gamewell-FCI by Honeywell

  • 详情介绍
  • 数据手册
  • 价格&库存
72198 数据手册
MS-95, MS-95T Description The Gamewell-FCI MS-95 is an easily recognized manual pull station with the distinctive bulls-eye design compatible with the Gamewell-FCI addressable 600 Series Fire Alarm Control Panels (FACPs). The MS-95 is approved to UL Standard 38 for manual stations, meets architectural requirements in all building interiors, and is readily noticed in a fire emergency. The addressable MS-95 manual pull station with a rugged toggle switch design offers exceptional resistance to accidental alarms caused by vibration and sudden shock. The MS-95 can be used for surface and semi-flush installations. Addressable Manual Pull Station Alarm Operations MS-95 The manual pull station is activated by pulling forward on the readily identified bulls-eye alarm lever labeled “PULL” in distinctive white letters. Once pulled, this lever locks in the alarm position and remains there until manually reset. To reset the alarm lever, the front cover of the pull station is released by turning the screw on the top of the cover or turning the key (on certain models). This unlocks the front cover which is then lowered. Once the front cover is lowered, the toggle switch is reset. An optional breakglass rod may be used with all stations. The self-clearing design prevents jamming of the station and there is no danger to the operator from broken particles of glass. Space is provided within the station housing for storage of an additional replacement glass rod. The MS-95 connects directly to the analog addressable circuit via two wires. The electronic circuitry has been designed to transmit data that can be interpreted as three (3) output operations: • normal standby operation • alarm operation • trouble operation In its standby mode of operation, the pull station’s circuit monitor the switch for alarm conditions. A trouble condition Features • • • • • • • • • • • Compatible with the Gamewell-FCI 600 Series analog addressable control panels. Field programmable. Durable construction. Compact design, blends with surroundings. Recessed pull lever prevents accidental operation. Surface or semi-flush installation. Double action option. Key reset option. Meets ADA requirements. Visible status LED. Terminal block model available (MS-95T). An ISO 9000-2000 Company SIGNALING S281 7150-1288:148 GAMEWELL-FCI Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. ©2007 Honeywell International Inc. All rights reserved. www.gamewell-fci.com CS-2053 Rev. A page 1 of 2 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 CS-2053ph1.wmf Operations (Continued) occurs when the pull station is addressed by the control panel and either reports back a trouble response or does not respond at all. With the standard priority interrupt feature, the MS-95 will report its condition virtually instantaneously to the Gamewell-FCI FACP. Ordering Information Model MS-95 MS-95T 30653 30653-01 30653-02 27060 28762 50397G 72198 71961 Description Analog addressable manual pull station. Analog addressable manual pull station with terminals. Double action option. Key reset option. Key reset/double action option. Breakglass rod. Surface backbox. Weather proof gasket for MS-95 station. NYC backplate manual station backplate with 1" (2.54 cm) white stripe. Backbox, surface for key reset options. Programming Programming of the MS-95 manual station address is accomplished by setting a single DIP switch easily accessible on the device’s printed circuit board. All other programming is accomplished at the FACP. Engineer’s Specifictions The analog addressable manual pull station shall contain the electronic interface circuitry required for individual device identification, alarm reporting andtrouble supervision. It shall communicate to the main control panel via the analog addressable circuit. The single-action station shall consist of a die-cast aluminum housing fitted with a pull out lever which, when operated, locks in position after activating an alarm initiating contact. Specifications Standby Current: Alarm Current: Operating Temperature: Relative Humidity: Material: Finish: 0.0005 A 0.0015 A 0° C to 49° C (32° F to 120° F) 85%, non-condensing Die-cast aluminum Fire alarm red, smooth gloss enamel. Raised cast letters are highlighted. Target background for pull lever is white glossed enamel. Dimensions MS-95: 4 .625" high x 3.25" wide x 2.0" deep (11.75 H x 8.26 W x 5.08 D cm)( from the backplate). MS-95T: 4.625" high x 3.25" wide x 1.625" deep (11.75 H x 8.26 W x 4.13 cm) (from the backplate). MS-95 with key reset option: 6.25" high x 3.25" wide x 2.0" deep (15.88 H x 8.26 W x 5.08 D cm) (from backplate) with Cat 60 Key. Surface Backbox P/N 28762: 4.625" high x 3.25" wide x 2.375" deep (11.75 H x 8.26 W x 6.03 D cm) tapped for 3/4" conduit. Surface Backbox 71961: 6.25" high x 3.0" wide x 3.25" (15.88 H x 7.6 W x 8.26 D cm) deep. GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 www.gamewell-fci.com CS-2053 Rev. A page 2 of 2
72198
1. 物料型号: - MS-95:模拟地址编码手动拉响警站。 - MS-95T:带接线端子的模拟地址编码手动拉响警站。

2. 器件简介: - Gamewell-FCI MS-95是一款易于识别的手动拉响警站,具有独特的靶心设计,兼容Gamewell-FCI 600系列火灾报警控制面板(FACPs)。MS-95符合UL标准38的手动站要求,满足所有建筑内部的建筑要求,并在火灾紧急情况下容易被注意到。

3. 引脚分配: - MS-95通过两根线直接连接到模拟地址编码电路。

4. 参数特性: - 待机电流:0.0005 A - 报警电流:0.0015 A - 操作温度:0°C至49°C(32°F至120°F) - 相对湿度:85%,不凝结 - 材料:压铸铝 - 外观:火警红色,光滑光泽珐琅。凸起的铸字母突出显示。拉杆的靶心背景为白色光泽珐琅。

5. 功能详解: - 手动拉响警站通过向前拉动标有“PULL”的靶心报警杆激活,一旦拉动,该杆锁定在报警位置,直到手动重置。 - 重置报警杆时,通过转动盖子顶部的螺丝或转动某些型号上的钥匙来释放拉响警站的前盖。这解锁了前盖,然后降低它。前盖降低后,切换开关被重置。

6. 应用信息: - MS-95可用于表面和半嵌入式安装,设计耐用,紧凑,与周围环境融为一体。表面或半嵌入式安装,双动作选项,钥匙重置选项,满足ADA要求,可见状态LED,提供端子块型号(MS-95T)。

7. 封装信息: - MS-95尺寸:4.625"高x 3.25"宽x 2.0"深(11.75 H x 8.26 Wx 5.08 D cm)(从背板起)。 - MS-95带钥匙重置选项:6.25"高x 3.25"宽x 2.0"深(15.88 Hx 8.26 Wx 5.08 D cm)(从背板起),配有Cat 60钥匙。
72198 价格&库存

很抱歉,暂时无法提供与“72198”相匹配的价格&库存,您可以联系我们找货

免费人工找货