CAC-5F 数据手册
Flex 405 Fire Alarm Control Panel with built-in DACT and remote-site upload/download capability Features • Five programmable Initiating Device Circuits (zones). Each zone may be programmed for: two-wire smoke detectors, normally open contact devices (pull stations, heat detectors), four-wire smoke detectors, waterflow operation, supervisory operation, auto-reset supervisory operation. • Two built-in, Class A or B (Style Z or Y) Notification Appliance Circuits (NACs). NACs may be programmed: silenceable, non-silenceable (a strobe circuit can keep flashing after the panel is silenced), autosilence (program 5 to 30 minutes), silence inhibit (60 seconds), coding (march time, temporal, California). • 3.0 amps of notification appliance power, expandable to 5.0 amps (meets the critical power requirements for ADA and UL-1971 devices). • Two built-in Form-C Alarm and Trouble relays. • Supervisory and communication fail outputs. • Dual-line rotary- or Touch-Tone®-dial DACT interfaces to public telephone network (leased phone lines are not required). • 24-Volt operation. • Built-in voltmeter measures: zone voltage; primary AC line voltage; battery voltage; NAC(s) voltage; resettable 24-volt power. • Surface Mount Technology (SMT). • Fully programmable via built-in keypad (no costly external programmers necessary). • Complies with NFPA 72 (Local, Central Station and Remote Station [DACT only – not polarity reversal] Fire Alarm Systems). • Reporting formats include: 3+1, 4+1, 4+2 Standard + Expanded; 4+1, 4+2, Ademco Express. • Integral battery charger for up to 60 hours of standby power. • Fuseless, power-limited technology meets UL power-limiting requirements. • Programmable alarm presignal timer, alarm verification timer, and optional trouble reminder. • Single-person walk test. Fire drill function. • Zone disable capability (software). • 32-Event history buffer with time-and-date stamp. Accurate real-time clock/calendar. • Extensive built-in transient protection. • Electronics and operational controls fully enclosed in a lockable cabinet capable of housing up to 7 AH batteries. • Optional: contact-by-zone module, remote annunciator, printer interface for on- or off-line printing. Description The Gamewell Flex 405 is a 24-volt, five-zone Fire Alarm Control Panel FACP) with built-in communicator and remote-site upload/download capability. The integral communicator transmits event information (alarms, troubles, supervisories, faults, etc.) to a UL-Listed central station. The Flex 405 may be used in a variety of costeffective applications, including: local fire alarm control panel (communicator disabled), fire alarm control panel/ communicator, stand-alone sprinkler supervisory communicator, or slave communicator to a UL-Listed host fire alarm panel (requires normally-open dry contacts to trigger five channels). Selectable transmission formats allow the Flex 405 to communicate to virtually all central stations. Remote-Site Upload/Download The Flex 405 may be downloaded or uploaded without affecting the system fire protection. Download system programming, and upload key system information such as: current system status, history and walk test files; zone, AC line, NAC 1 and NAC 2, resettable power and battery voltages; and system programming. Upload or download within one minute without affecting normal fire panel functions. The upload/download function also features multiple security techniques. The Flex 405 requires the PK-CD programming kit, which works with most Hayescompatible modems (consult factory for listing). g2405ph1.jpg Listings Listings and approvals below apply to the basic Flex 405 panel. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. • UL Listed. • CSFM approved: file 7165-1288:179. • MEA approved: file 366-04-E. Flex 405 CS-2405 09/01/06 Page 1 of 4 Specifications Ordering Information F405 Five-zone, 24-volt fire alarm control communicator. Includes backbox, transformer, technical manual, and frame-and-post operating instruction sheet. 120 VAC, 100 VA transformer expands NAC power from 3.0 to 5.0 amps. Five-zone remote annunciator (RZA-5F), mounts to a singlegang box (requires ADM-24). Annunciator driver module (supports SAN-405). Five-zone relay module, provides contact-by-zone. Class A converter module. Converts all Class B initiating device circuits (zones) to Class A. Printer interface module, provides an EIA-232 printer output. Includes cable, DB9F and DB25 adapter. Contains programming software for Windows®-based PC computer (cable not included). DACT phone cord, 7 feet (2.134 m) long (two required). Battery backbox, required for batteries over 7 AH. Trim ring. Flex 405 Installation and Maintenance Manual. • Single PC board design using Surface Mount Technology (SMT). • Two modular telephone jacks for connection to RJ31X/modules. AC power • 120 VAC, 50/60 Hz, 2.3 A. • Wire size: minimum 14 AWG (2.0 mm²) with 600-volt insulation. • Built-in brownout circuitry, built-in voltmeter. Communicator • One line-active indicator for each of two phone lines. • “Kiss-Off” signal LED. • Dual “low telephone voltage detect” circuitry. • Programmable event codes per each format. • Up to 62 transmitted events/messages. Selectable/deselectable transmissions of 62 events. • Five zones may be configured to five channels as a slave communicator (channels are auto-resettable. Communication formats Express formats allow complete transaction to be communicated in under five seconds. • 20 PPS, 3+1 standard & expanded. • 20 PPS, 4+1 standard & expanded. • 20 PPS, 4+2 standard & expanded. • 4+1 and 4+2 Ademco Express. Initiating device circuits (zones) • The Flex 405 includes five programmable initiating device circuits (zones). Circuits 1, 2, 4, and 5 are Style B (Class B). Circuit 3 is Style D (Class A). Use Class A converter module (P/N CAC-5F) to convert Class B IDCs to Class A. • Each zone may support two-wire smoke detectors. Programming options include: waterflow (silenceable/non-silenceable), supervisory (standard/auto-reset), pull station, normally-open-contact device. • All circuits are power-limited and supervised. • All circuits allow up to 100 ohms of line resistance. Use 12 to 18 AWG wire (3.1 to 0.78 mm²). Notification appliance circuits • Two Style Z/Y (Class A/B) @ 2.5 A each. • All circuits are fully power-limited and meet UL power-limiting requirements. Auxiliary outputs • Resettable four-wire smoke detector power @ 300 mA. Non-resettable power @ 300 mA. • Integral Form-C Alarm and Trouble relays. • Relay drivers for supervisory and communication fail. Cabinet specifications • The compact cabinet can be surface- or semiflush-mounted. • Knockouts on the top, sides, and back provide ease of wire entry. • Dimensions, Door: 15.219” high x 14.219” wide (38.655 cm H x 36.115 cm W). Backbox: 15.0” high x 14.5” wide x 3.0” deep (38.1 cm H x 36.83 cm W x 7.62 cm D). Trim ring (P/N TR1-R): 18.125” high x 17.62” wide (46.038 cm H x 44.755 cm W). Page 2 of 4 Flex 405 CS-2405 09/01/06 XRM-24 SAN-405 ADM-24 RM-5F CAC-5F PRT-24 PK-CD MCBL-7 BB-17F TR-3-R 52223 UL-Listed Receivers Compatible with the Flex 405 Format # (Addresses 16 & 42) 0 1 2 3 4 5 6 7 8 9 A B C D E F 4+1 Ademco Express 4+2 Ademco Express 3+1/Standard/1800/2300 3+1/Expanded/1800/2300 3+1/Standard/1900/1400 3+1/Expanded/1900/1400 4+1/Standard/1800/2300 4+1/Expanded/1800/2300 4+1/Standard/1900/1400 4+1/Expanded/1900/1400 4+2/Standard/1800/2300 4+2/Expanded/1800/2300 4+2/Standard/1900/1400 4+2/Expanded/1900/1400 (NOT USED) (NOT USED) 51348t1.tbl Ademco 685 (1) Silent Knight 9000 ITI CS-4000 (3) FBI CP220FB Osborne Hoffman Models 1&2 Radionics 6000/6500 (5) Sescoa 3000R (7) SurGuard MLR-2 (9) 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 (2) 4 (2) 4 (2) 4 (2) 4 (2) 4 (2) 4 (2) 4 (2) 4 (2) 4 (2) 4 (2) 4 (2) 4 4 4 4 4 4 4 (4) 4 (4) 4 (4) 4 (4) 4 (4) 4 (4) 4 (4) 4 (4) 4 (4) 4 (4) 4 (4) 4 (4) 4 (8) 4 4 4 4 4 4 4 4 4 4 4 4 4 (5) 4 (5) 4 (5, 6) 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 KEY: (1) With 685-8 Line Card with Rev. 4.4d software. (2) With 9002 Line Card Rev. 9035 software or 9032 Line Card with 9326A software. (3) Rev. 4.0 software. (4) FBI CP220FB Rec-11 Line Card with Rev. 2.6 software and a memory card with Rev. 3.8 software. (5) Model 6500 with Rev. 600 software. (6) Model 6000 with Rev. 204 software. (7) With Rev. B control card at Rev. 1.4 software and Rev. C line card at Rev. 1.5 software. (8) Model 2 only. (9) Version 1.62 software. Flex 405 CS-2405 09/01/06 Page 3 of 4 Notes Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 Phone: 203-484-7161 Fax: 203-484-7118 www.gamewell-fci.com A Honeywell Company © 2006 Gamewell-FCI Specifications and wiring information are provided for information only and are believed to be accurate. Gamewell-FCI assumes no responsibility for their use. Data and design are subject to change without notice. Installation and wiring instructions shipped with the product shall always be used for actual installation. For more information, contact Gamewell-FCI. Page 4 of 4 Flex 405 CS-2405 09/01/06
CAC-5F
物料型号: - Flex 405是五区域、24伏火警控制通讯器,包括背盒、变压器、技术手册和框架式操作说明书。

器件简介: - Flex 405是一款24伏、五区域的火警报警控制面板(FAPC),内置通讯器和远程站点上传/下载功能。该通讯器可将事件信息(报警、故障、监督、故障等)传输至UL认证的中央监控站。Flex 405可用于多种成本效益高的应用场景,包括:本地火警控制面板(禁用通讯器)、火警控制面板/通讯器、独立的喷水器监督通讯器,或作为UL认证的主火警报警面板的从通讯器(需要常开干接点触发五个通道)。可选择的传输格式使Flex 405能够与几乎所有中央监控站通信。

引脚分配: - Flex 405包含五个可编程的启动设备电路(区域)。电路1、2、4和5是B型(Class B)。电路3是D型(Class A)。可以使用Class A转换模块(型号CAC-5F)将Class B IDC转换为Class A。

参数特性: - 两个内置的A类或B类(Z型或Y型)通知设备电路(NAC)。NAC可以编程为:可静音、不可静音(一个频闪电路在面板静音后可以继续闪烁)、自动静音(编程5至30分钟)、静音禁止(60秒)、编码(时间码、时间码、加利福尼亚)。提供3.0安培的通知设备电源,可扩展至5.0安培(满足ADA和UL-1971设备的关键电源要求)。

功能详解: - Flex 405可以在不影响系统火保护的情况下进行下载或上传。下载系统编程,并上传关键系统信息,例如:当前系统状态、历史和步行测试文件;区域、交流线路、NAC1和NAC2、可重置电源和电池电压;以及系统编程。上传/下载功能还在一分钟内完成,不影响正常的火灾面板功能。上传/下载功能还具有多重安全技术。

应用信息: - Flex 405可用于多种应用,包括作为本地火警控制面板(禁用通讯器)、火警控制面板/通讯器、独立的喷水器监督通讯器,或作为UL认证的主火警报警面板的从通讯器。

封装信息: - 紧凑的机柜可以表面安装或半嵌入式安装。顶部、侧面和背面的敲击提供方便的电线入口。尺寸:门高15.219英寸x宽14.219英寸(38.655厘米Hx36.115厘米W)。背盒高15.0英寸x宽14.5英寸x深3.0英寸(38.1厘米Hx36.83厘米Wx7.62厘米D)。修整机环(型号TR1-R)高18.125英寸x宽17.62英寸(46.038厘米Hx44.755厘米W)。