MCH-6 数据手册
Velociti™ Series MM0-6RF Description The FCI Velociti™ Series, multi-mod six relay output module (MMO-6RF) provides six (6), Form “C” control relay outputs on one board. Its compact design affords ease of installation while using a minimum of wall space. The VelocitiTM Series use a communication protocol that substantially increases the speed of communication between the sensors and certain FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and concentrates on the single device. The net effect is response speed up to five times greater than earlier designs. The MMO-6RF connects to the signaling line circuit (SLC) of the FCI analog addressable series fire alarm control panels. Each relay circuit on the MMO-6RF occupies its own address on the control panel’s SLC and can be programmed to respond to its own individual controlby-event sequence of operation. The address of the first relay is set by a pair of rotary code switches on the MMO-6RF. Each remaining relay circuit is automatically assigned to its own subsequent address. The MMO-6RF module includes an address disable switch that allows one, two, or three addresses to be turned off to free these addresses for other purposes. Each relay has its own status LED that flashes to indicate proper polling and lights steady when the circuit has been activated. Two (2), multi-mod series units can be mounted in one MBB-2 cabinet. Additional mounting options include the MCH-6 chassis that can accommodate six (6), multi-mod series modules. The MCH-6 chassis can be installed in custom cabinets or mounted in the MBB-6 cabinet. The multi-mod series is ideal for applications where centralized location of circuits is required. As many as thirtysix (36), Form “C” relays may be located in a cabinet that is only 12.63” H x 24” W x 6.5” D in dimension saving valuable wall space in mechanical rooms and electrical closets and reducing cost of installation. MMO-6RF Multi-Mod Relay Output Module Features • Each module provides six (6), individually addressed, individually programmable form “C” relays. • Removable wiring terminal blocks allow ease of installation and servicing. • Terminal blocks can accommodate 12 to 18 AWG wire. • Flexible jumper configuration feature allowing up to three relay addresses to be disabled. • A wide range of contact ratings. • Designed for FCI analog addressable series fire alarm control panels. • Individual LED indicators*. • Suitable for retrofit applications. • Ideal for applications such as elevator control, AHU control, door holder release or similar functions requiring multiple relay outputs. • Two (2), mounting cabinets available for two (2), (MBB-2 cabinet) to six (6), (MBB-6 cabinet) units. Note: Only the red LED is operative in panels that do not operate in Velociti™ mode. An ISO 9001-2000 Company Velociti™ and E3 Series™ are trademarks of Fire Control Instruments. GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. www.gamewell-fci.com 9020-0632 Rev. B page 1 of 2 ©2006 Gamewell-FCI. All rights reserved. Specifications Operating Voltage: Stand-by Current: Alarm Current: Relay Current: Relay Contact Ratings: Temperature Range: Humidity Dimensions: MBB-2 MBB-6 15-32 VDC 1.45 mA 32 mA (with all six relays activated and all six LEDs lit) 30 mA/ relay pulse (see below) Ordering Information Model MMO-6RF MBB-2 MBB-6 MCH-6 Description Multi-mod relay output Backbox, 2 unit Backbox, 6 unit, requires MCH-6 6-Unit mounting chassis 32˚ F to 120˚ F (0˚ to 49˚ C) 10 to 85% (non-condensing) 6.8” H x 5.8” W x 1.0” D (17.3 x 14.7 x 2.5 cm) 12.25” H x 9.25” W x 3.32” D (31.1 x 23.5 x 8.4 cm) 12.63” H x 24” W x 6.5” D (32.1 x 60.1 x 16.5 cm) Contact Ratings Current Rating 3A 2A 1A 0.5A 0.9A 0.9A 0.7A 0.5A Maximum Voltage 30 VDC 30 VDC 30 VDC 30 VDC 110 VDC 125 VAC 70.7 & VAC 125 VAC Load Description Resistive Resistive Inductive (L/R= 2ms) Inductive (L/R= 5ms) Resistive Resistive Inductive (PF= 0.35) Inductive (PF= 0.35) Application Non-coded Coded Coded Coded Non-coded Non-coded Non-coded Non-coded GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118 www.gamewell-fci.com 9020-0632 Rev. B page 2 of 2
MCH-6
1. 物料型号: - MMO-6RF:Multi-mod relay output - MBB-2:Backbox, 2 unit - MBB-6:Backbox, 6 unit, requires MCH-6 - MCH-6:6-Unit mounting chassis

2. 器件简介: - FCI Velociti™ Series的MMO-6RF模块提供了六个(6)Form “C”控制继电器输出,采用紧凑设计,便于安装且占用墙面空间小。该系列使用通信协议,显著提高传感器与FCI模拟地址编码火灾报警控制器之间的通信速度。如果组中的一个设备状态发生变化,面板的微处理器会停止组轮询并集中处理单个设备,从而实现高达五倍于早期设计的响应速度。

3. 引脚分配: - 每个继电器电路在控制面板的SLC上都有自己的地址,并且可以编程以响应其自己的控制事件序列。第一个继电器的地址由MMO-6RF上的一对旋转编码开关设置。其余的继电器电路自动分配到其后续地址。

4. 参数特性: - 工作电压:15-32 VDC - 待机电流:1.45 mA - 报警电流:32 mA(所有六个继电器激活且所有六个LED点亮时) - 继电器电流:每个继电器脉冲30 mA - 温度范围:32°F至120°F(0°C至49°C) - 湿度:10至85%(非凝结) - 尺寸:6.8" Hx 5.8" Wx 1.0" D(17.3x 14.7x2.5cm)

5. 功能详解: - 每个模块提供六个(6)可单独寻址、可单独编程的Form “C”继电器。 - 可拆卸的接线端子,便于安装和服务。 - MMO-6RF模块包括一个地址禁用开关,允许关闭一个、两个或三个地址以便用于其他目的。 - 接线端子可容纳12至18 AWG线。 - 灵活的跳线配置功能,允许禁用多达三个继电器地址。 - 广泛的接触等级。 - 每个继电器都有自己的状态LED,闪烁表示正常轮询,稳定亮起表示电路已激活。

6. 应用信息: - 设计用于FCI模拟地址编码系列火灾报警控制面板。 - 适用于电梯控制、AHU控制、门保持释放或类似需要多个继电器输出的场合。 - 适合改造应用。

7. 封装信息: - MBB-2:12.25" H x 9.25" W 3.32" D(31.1 x 23.5x 8.4 cm) - MBB-6:12.63" Hx 24" Wx 6.5" D(32.1 x 60.1 x 16.5 cm)