AC Output Modules
FEATURES • Transient Protection: Meets the requirements of IEEE 472, “Surge Withstanding Capability Test” • SPST, Normally Open • Zero Crossing Turn-On • UL, CSA, CE, TÜV Certified • Optical Isolation • OpenLine® and G5 Modules Provide Replaceable 5x20 mm Glass Fuses • Built-in Status LED • Lifetime Warranty
70L-OAC For complete dimensional drawings, see pages L-4 or L-5.
LOAD CURRENT (AMPS)
70G-OAC
70-OAC
70M-OAC
DIMENSIONS
4 3 2 1
STANDARD, G5 PACKAGES MINIATURE PACKAGE
FUSES
G5 Fuses are 5 Amp Littelfuse part number 217005 or equivalent. OpenLine® fuses are 3.15 Amp Littelfuse part number 2173.15.
OPENLINE PACKAGE/CH
Maximum Current Versus Ambient Temperature The chart indicates continuous current to limit the junction temperatures to 100°C. Information is based on steady state heat transfer in a 2 cubic foot sealed enclosure.
-40˚
-20˚
0 20˚ 40˚ 60˚ 80˚ AMBIENT TEMPERATURE (˚C)
100˚
CIRCUITRY
Standard, Mini, G5
LOAD VAC LOAD
2 1
Figure 1 OpenLine®
TYPICAL WIRING FOR MODULE 0
SNUBBER
GND Vcc
5
CHANNEL A
I/O MODULE PIN # 1 1
LOAD
6 A
OPTICAL ISOLATION SNUBBER
TRIGGER CIRCUIT
CH. A CONTROL
7
2 3 B
OPTICAL ISOLATION SNUBBER
2 3
+
DC CONTROL
Rx
3 4
CH. B CONTROL
CHANNEL B
4 2.15K
RACK OR BASE
4
LOAD
–
MODULE ID MODULE
TERMINAL BLOCK #
Fuse and status LED in G5 and OpenLine modules only.
I/O Modules
SPECIFICATIONS: By Package Style
Package Style Specifications Load Current Range Maximum 1 Cycle Surge 2 Maximum Turn-On-Time (60 Hz)3 Maximum Turn-Off Time (60 Hz) Static dv/dt7 Typ. Power Dissipation Isolation Voltage 4 Vibration5 Mechanical Shock6 Storage Temp. Range Operating Temp. Range Warranty
1 2 1
Std (70-) Units A rms A rms mSec mSec V/µsec W/A V rms °C °C 0.03 to 3.5 80 8.33 8.33 3000 1.0 4000 MIL-STD-202 MIL-STD-202 -40 to 125 -40 to 100 Lifetime
Mini (70M-)
G5 (70G-)
OL (70L-)
0.03 to 3.0 80 8.33 8.33 3000 1.0 4000 MIL-STD-202 MIL-STD-202 -40 to 125 -40 to 100 Lifetime
0.03 to 3.5 80 8.33 8.33 3000 1.0 4000 MIL-STD-202 MIL-STD-202 -40 to 125 -40 to 100 Lifetime
0.03 to 2.0/CH 30 8.33 8.33 3000 1.0 2500 IEC68-2-6 IEC68-2-27 -40 to 100 -40 to 85 Lifetime
3 4 5 6 7
See Figure 1 for derating. Maximum 10 cycle surge is 50% of 1 cycle surge. Application of maximum surge may not be repeated until module temperature has returned to its steady state value. Except 70-OAC5A5 which is 200 µSec and 70-OAC5A-11, 70M-OAC5A-11, and 70G-OAC5A-11 which are 100 µSec. Field to logic and channel-to-channel if Grayhill racks are used. MIL-STD-202, Method 204, 20 , 10-2000 Hz or IEC68-2-6, 0.15 mm/sec2, 10-150 Hz. MIL-STD-202, Method 213, Condition F, 1500G or IEC68-2-27, 11 mS, 15g. Except part numbers with -L suffix which have a dv/dt rating of 200 V/µSec.
G rayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
I/O 6
AC Output Modules
SPECIFICATIONS: By Part Number
Standard and Miniature Modules
Type/Function Miniature, Normally Open, Random Turn-on Miniature, Normally Open, Zero Voltage Turn-on (ZVT) Miniature, Normally Open, ZVT, Inductive Load Standard, Normally Closed, Random Turn-on Standard, Normally Open, Random Turn-on Standard, Normally Open, ZVT Standard, Normally Open, ZVT, Inductive Load Specifications Nominal Line Voltage Load Voltage Range Minimum Peak Blocking Voltage Maximum Off-state Leakage @ 60Hz Nominal Logic Voltage (Vcc) Logic Voltage Range Max. Logic Supply Current @ Nominal Vcc Nominal Input Resistance (Rx) Minimum Drop Out Voltage Maximum Reverse Logic Voltage Units Vac Vac Volts mA, rms Vdc Vdc mA Ω Vdc Vdc 70-OAC5 70-OAC5-L 120 24-140 400 2 5 2.5-10 16 240 1 -5 70M-OAC5 70M-OAC5-L 70M-OAC5A-11 70M-OAC5A 70M-OAC5A-L 70-OAC5A5 70-OAC5A-11 70-OAC5A 70-OAC5A-L 240 24-280 600 4 5 2.5-10 16 240 1 -5 120 24-140 400 2 15 10-18 9 1800 1 -5 240 24-280 600 4 15 10-18 9 1800 1 -5 120 24-140 400 2 24 15-30 9 2700 1 -5 240 24-280 600 4 24 15-30 9 2700 1 -5 70-OAC15 70-OAC15A 70-OAC24 70-OAC24A-11 70-OAC24A 70M-OAC15 70M-OAC15A 70M-OAC24 70M-OAC24A Grayhill Part Number
G5 Modules
Type/Function G5 Fusible, Normally Open, ZVT G5 Fusible, Normally Open, ZVT, Inductive Load G5 Fusible, Normally Open, Random Turn-on Specifications Nominal Line Voltage Load Voltage Range Minimum Peak Blocking Voltage Maximum Off-state Leakage @ 60Hz Nominal Logic Voltage (Vcc) Logic Voltage Range Max. Logic Supply Current @ Nominal Vcc Nominal Input Resistance (Rx) Minimum Drop Out Voltage Maximum Reverse Logic Voltage Units Vac Vac Volts mA, rms Vdc Vdc mA W Vdc Vdc 120 24-140 400 2 5 4-6 20 100 1 -5 240 24-280 600 4 5 4-6 20 100 1 -5 120 24-140 400 2 15 8-20 12 1000 1 -5 240 24-280 600 4 15 8-20 12 1000 1 -5 120 24-140 400 2 24 18-32 8 2700 1 -5 240 24-280 600 4 24 18-32 8 2700 1 -5 70G-OAC5 70G-OAC5A 70G-OAC5A-11 Grayhill Part Number 70G-OAC15 70G-OAC15A 70G-OAC24 70G-OAC24A 70G-OAC24A-L
70G-OAC5-L 70G-OAC5A-L
70G-OAC15-L 70G-OAC15A-L 70G-OAC24-L
I/O Modules
OpenLine® Modules
Type/Function Dual, Fusible, Normally Open, ZVT Dual, Fusible, Normally Open, ZVT, Inductive Load Specifications Nominal Line Voltage Load Voltage Range Minimum Peak Blocking Voltage Maximum Off-State Leakage @ 60 Hz Nominal Logic Voltage Logic Voltage Range Max. Logic Supply Current @ Nominal Vcc Module ID Resistance to Logic Ground Minimum Drop Out Voltage Units Vac Vac Volts mA, rms Vdc Vdc mA Ω Vdc 120 24-140 600 2 5 4.5-28 7/CH 2.15K 1 240 24-280 600 4 5 4.5-28 7/CH 2.15K 1 Grayhill Part Number 70L-OAC 70L-OAC-L 70L-OACA 70L-OACA-L
Available from your local Grayhill Distributor. For prices and discounts, contact a local Sales Office, an authorized local Distributor or Grayhill.
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois
60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com