MODEL FP2000
008835
Issue 6
Differential Pressure Transducer
DESCRIPTION
The FP2000 series is a configurable
differential pressure transducer which
allows the customer to select the
configuration which best fits the needs
of the application. Choose from multiple
accuracies, outputs, pressure ports,
electrical terminations, and pressure
ranges.
The FP2000 is available with differential
wet/wet and wet/dry configurations.
DIFFERENTIATION
• Welded stainless steel construction
• Customized specifications available
• Configurable platform enables
a sensor to be built to customer
requirements
• Bi-directional functionality of pressure
measurement
• Optional bi-directional calibration
available
• Small package size
VALUE TO CUSTOMERS
• Built on the Honeywell history of
higher-quality pressure sensing
technologies
• Configurable platform creates a wide
range of standard configurations
• Broad compensated temperature
ranges
• Multiple outputs to choose from to
meet variety of application needs
POTENTIAL APPLICATIONS
• Test stands (automotive, aerospace,
and industrial)
• R&D test labs
• Hydraulic and pneumatic system
monitoring
• Leak detection
• Pump and compressor control
• Tank level measurement
• Monitor pressure changes for
preventive maintenance
• Flow rate measurement
Approved
Approved
FEATURES
• mV/V, 4 mA to 20 mA, ±5 Vdc, ±10 Vdc
• Differential (wet/wet, wet/dry)
• Multiple electrical connector and
pressure port offerings
• Intrinsically safe option
• CE available
FP2000 pressure sensors are custom
built from stocked components. Please
see http://sensing.honeywell.com for
updated listings
FIGURE 1. TYPICAL SYSTEM DIAGRAM
In-line amplifiers
(Used with unamplified units only)
Amplifier
Output
Universal in-line amplifiers
U2W
4 mA to 20 mA (2-wire)
6q
PORTFOLIO
6r
6a
Customer supplied
Chart recorder
Alarm panel
Data acquisition
Computer
PLC
Model FP2000
6m
Mating connectors & cables
PT06A-10-6S (option 6a)
mV/V – 4 conductor cable
4 mA to 20 mA – 3 conductor cable
0-5/ 0-10 Vdc – 3 conductor cable
Standard DIN 43650 (option 6m)
Mini DIN 40050 (option 6n)
Display units
SC500
SC2000
SC2001
SC3004
GM (unamp. only)
GM-A (amp. only)
NK (unamp. only)
HH (unamp. only)
From general process
pressure transducers to
hazardous location pressure
products, Honeywell offers
a comprehensive selection of gage,
absolute, differential, vacuum, and
barometric pressure transducers
to meet market demands. Each of
our trandsucers can be customized
to meet your needs, whatever your
application. To view the entire
product portfolio, click here.
DIFFERENTIAL PRESSURE TRANSDUCER, MODEL FP2000
TABLE 1. PERFORMANCE SPECIFICATIONS
TABLE 3. MECHANICAL SPECIFICATIONS
CHARACTERISTIC
MEASURE
CHARACTERISTIC
MEASURE
Accuracy
see Note 1
Media
Gas, liquid
Output (selectable)
mV/V , 4 mA to 20 mA (two wire),
±5 Vdc, ±10 Vdc
Resolution
Infinite
Overload safe
Positive (+) direction
Model FDW and FDD
4X full scale or 3000 psi
whichever is less
Overload safe
Negative (-) direction
Model FDW and FDD
4X full scale or 250 psi whichever
is less
Overload burst
Positive (+) direction
Model FDW and FDD
3000 psi
Overload burst
Negative (-) direction
Model FDW and FDD
500 psi
Wetted material
Ha C276 & 316L Stainless Steel
TABLE 2. ELECTRICAL SPECIFICATIONS
CHARACTERISTIC
MEASURE
Amplified
(4 mA to 20 mA; ±5 Vdc)
9 Vdc to 28 Vdc
Amplified
(±10 Vdc)
15 Vdc to 28 Vdc
Unamplified (mV/V)
10 Vdc
Note 1: Unless otherwise specified on order, amplified units with 4 mA to 20 mA output will provide 4 mA at 0 psid and 20 mA at positive full scale
and the unit will not operate in the negative direction. Consult Factory to specify 4 mA at negative full scale and 20 mA at positive full scale.
Note 2: All amps add 2 inches to sensor housing length.
TABLE 4. ENVIRONMENTAL SPECIFICATIONS
ORDER
CODE
FDD
FDW
Temperature,
error band
RANGE
TEMPERATURE,
COMPENSATED
less than 1 psi
10 °C to 45 °C [50 °F to 110 °F]
1 psi and less than 5 psi
5 °C to 50 °C [40 °F to 120 °F]
5 psi and above
5 °C to 60 °C [40 °F to 140 °F]
less than 1 psi
10 °C to 45 °C [50 °F to 110 °F]
1 psi and less than 5 psi
5 °C to 50 °C [40 °F to 120 °F]
TEMPERATURE, OPERATING
TEMPERATURE, OPERATING
-40 °C to 116 °C
[-40 °F to 240 °F]
-29 °C to 85 °C
[-20 °F to 185 °F]
Unamplified Output:
Option 2U
Voltage Output:
Option 2D,2E,2F,2G
Current Output:
Option 2P,2Y,2N
5 psi and above
5 °C to 60 °C [40 °F to 140 °F]
0.10 % accuracy
±0.5 % full scale
–
–
0.25 % accuracy
±1.0 % full scale
–
–
2 sensing.honeywell.com
DIFFERENTIAL PRESSURE TRANSDUCER, MODEL FP2000
TABLE 5. INTERNAL AMPLIFIERS
AMPLIFIER
SPECIFICATIONS
UNAMPLIFIED
OUTPUT: OPTION 2U
VOLTAGE OUTPUT:
OPTION 2D
VOLTAGE OUTPUT:
OPTION 2G
CURRENT TWO-WIRE:
OPTION 2P
Output signal at null
0 Vdc
0 Vdc
0 Vdc
4 mA
Output signal at full scale output
50 mV
5 Vdc
10 Vdc
20 mA
Input power (voltage)
10 Vdc
9 Vdc to 28 Vdc
15 Vdc to 28 Vdc
9 Vdc to 32 Vdc
Input power (current)
2 mA @ 10 Vdc
10 mA
15 mA
4 mA to 24 mA
Frequency response
Natural frequency
300 Hz
300 Hz
300 Hz
Power supply rejection
N/A
60 dB
60 dB
60 dB
Operating temperature
-40 °C to 116 °C
[-40 °F to 240 °F]
-29 °C to 85 °C
[-20 °F to 185 °F]
-29 °C to 85 °C
[-20 °F to 185 °F]
-29 °C to 85 °C
[-20 °F to 185 °F]
Reverse voltage protection
N/A
Yes
Yes
Yes
Short circuit protection
N/A
Momentary
Momentary
Yes
AMPLIFIER
SPECIFICATIONS
VOLTAGE OUTPUT:
OPTION 2E
VOLTAGE OUTPUT:
OPTION 2F
INTRINSICALLY SAFE
AMP: OPTION 2N (2N)***
CURRENT TWO-WIRE:
OPTION 2Y
Output signal at null
0 Vdc
0 Vdc
4 mA
4 mA
Output signal at full scale output
5 Vdc
10 Vdc
20 mA
20 mA
Input power (voltage)
9 Vdc to 28 Vdc
15 Vdc to 28 Vdc
9 Vdc to 28 Vdc
9 Vdc to 32 Vdc
Input power (current)
10 mA
15 mA
4 mA to 24 mA
4 mA to 24 mA
Frequency response
2000 Hz
2000 Hz
2000 Hz
2000 Hz
Power supply rejection
60 dB
60 dB
60 dB
60 dB
Operating temperature
-29 °C to 85 °C
[-20 °F to 185 °F]
-29 °C to 85 °C
[-20 °F to 185 °F]
-29 °C to 85 °C
[-20 °F to 185 °F]
-29 °C to 85 °C
[-20 °F to 185 °F]
Reverse voltage protection
Yes
Yes
Yes
Yes
Short circuit protection
Momentary
Momentary
Yes
Yes
Sensing and Internet of Things
3
DIFFERENTIAL PRESSURE TRANSDUCER, MODEL FP2000
FIGURE 2. MOUNTING DIMENSIONS
ELECTRICAL TERMINATION
Code 6a: 6-pin, vented, Bendix
style
Code 6m: 4-pin, vented, standard DIN (43650)
Code 6q: 4-conductor, vented,
integral cable, 1,52 m [5 ft]
FDW
Code 6r: 4-conductor, vented,
integral cable, conduit fitting 1,52
m [5 ft]
FDD
PRESSURE PORTS
Code 5a
1/4-18 NPT
female
Code 5b
1/4-18 NPT
male
Code 5c
7/16-20 UNF
female
Code 5d
7/16-20 UNF
male
Code 5f
G 1/4 B female
Code 5g
G 1/4 B male
Code 5h
1/8-27 NPT
female
Code 5i
1/8-27 NPT
male
Code 5p
M12-1.5 male
Code 5q
M12-1.5 female
Code 5r
9/16-18 SAE
male
Code 5s
9/16-18 SAE
female
Up to
1000 psi
Up to
1000 psi
4 sensing.honeywell.com
DIFFERENTIAL PRESSURE TRANSDUCER, MODEL FP2000
TABLE 7. WIRING CODES
UNAMPLIFIED OUTPUT: OPTION 2U
VOLTAGE OUTPUT:
OPTION 2D/2E
VOLTAGE OUTPUT:
OPTION 2G/2F
CURRENT TWO-WIRE:
OPTION 2P/2Y
INTRINSICALLY SAFE
AMP: OPTION 2N (2N)***
BENDIX PTIH-10-6P (OPTION 6A)
No shunt cal
A
B
C
D
E
F
(+) Excitation
(+) Excitation
(-) Excitation
(-) Excitation
(-) Output
(+) Output
A
B
C
D
E
F
(+) Supply
(-) Supply return
(-) Output 0 Vdc to
5 Vdc
(+) Output
No connection
No connection
A
B
C
D
E
F
(+) Supply
(-) Supply return
(-) Output 0 Vdc to
10 Vdc
(+) Output Vdc
No connection
No connection
A
B
C
D
E
F
(+) Supply
No connection
No connection
(+) Output 4 mA to
20 mA
No connection
No connection
A
B
C
D
E
F
(+) Supply
No connection
No connection
(+) Output 4 mA to
20 mA
Case ground
No connection
With shunt
cal (option
3d)
A
B
C
D
E
F
(+) Excitation
(-) Excitation
(+) Output
(-) Output
No connection
Shunt Cal
A
B
C
D
E
F
(+) Supply
(-) Supply return
(-) Output 0 Vdc to
5 Vdc
(+) Output
No connection
Shunt cal
A
B
C
D
E
F
(+) Supply
(-) Supply return
(-) Output 0 Vdc to
10 Vdc
(+) Output
No connection
Shunt cal
A
B
C
D
E
F
(+) Supply
No connection
No connection
(+) Output 4 mA to
20 mA
No connection
Shunt cal
A
B
C
D
E
F
(+) Supply
No connection
No connection
(+) Output 4 mA to
20 mA
No connection
Shunt cal
1
2
3
GND
(+) Supply
(+) Output
Supply/ output com.
No connect. to case
1
2
3
GND
(+) Supply
(+) Output
Supply/ output com.
No connect. to case
1
2
3
GND
(+) Supply
(+) Output 4 mA to
20 mA
No connection
No connection
1
2
3
GND
(+) Supply
(+) Output
Case ground
No connection
1
2
3
GND
(+) Supply
(+) Output
Supply/output com.
Shunt cal
1
2
3
GND
(+) Supply
(+) Output
Supply/output com.
Shunt cal
1
2
3
GND
(+) Supply
(+) Output 4 mA to
20 mA
No connection
Shunt cal
1
2
3
GND
(+) Supply
(+) Output
Case ground
Shunt cal
STD. DIN 43650 (OPTION 6M)
No shunt cal
1
2
3
4
(+) Excitation
(+) Output
(-) Output
(-) Excitation
With shunt
cal (option
3d)
Not Applicable
1.83 M [5 FT] INTEGRAL CABLE (OPTION 6Q)
No shunt
cal
R
Bl
G
W
(+) Excitation
(-) Excitation
(-) Output
(+) Output
With shunt
cal (option
3d)
Not Applicable
R
Bl
G
W
(+) Supply
(-) Supply return
(-) Output
(+) Output 0 Vdc to
5 Vdc
R
Bl
G
W
(+) Supply
(-) Supply return
(-) Output
(+) Output 0 Vdc to
10 Vdc
R
Bl
(+) Supply
(+) Output 4 mA to
20 mA
R
Bl
W
(+) Supply
(+) Output 4 mA to
20 mA
Case ground
R
Bl
G
W
(+) Supply
(-) Supply return
Shunt cal
(+) Output 0 Vdc to
5 Vdc
R
Bl
G
W
(+) Supply
(-) Supply return
Shunt cal
(+) Output 0 Vdc to
10 Vdc
R
Bl
G
(+) Supply
(+) Output 4 mA to
20 mA
Shunt cal
R
Bl
W
G
(+) Supply
(+) Output 4 mA to
20 mA
Case ground
Shunt cal
R
Bl
G
W
(+) Supply
(-) Supply return
(-) Output
(+) Output 0 Vdc to
5 Vdc
R
Bl
G
W
(+) Supply
(-) Supply return
(-) Output
(+) Output 0 Vdc to
10 Vdc
R
Bl
(+) Supply
(+) Output 4 mA to
20 mA
R
Bl
W
(+) Supply
(+) Output 4 mA to
20 mA
Case ground
R
Bl
G
W
(+) Supply
(-) Supply return
Shunt cal
(+) Output 0 Vdc to
5 Vdc
R
Bl
G
W
(+) Supply
(-) Supply return
Shunt cal
(+) Output 0 Vdc to
10 Vdc
R
Bl
G
(+) Supply
(+) Output 4 mA to
20 mA
Shunt cal
R
Bl
W
G
(+) Supply
(+) Output 4 mA to
20 mA
Case ground
Shunt cal
CONDUIT FITTING (OPTION 6R)
No shunt
cal
R
Bl
G
W
(+) Excitation
(-) Excitation
(-) Output
(+) Output
With shunt
cal (option
3d)
Not Applicable
Note: For wiring codes, R=red; Bl = black; W = white; G = green. Color specifies cable and letter or number specifies connection
*** See Honeywell’s Web site (http://measurementsensors.honeywell.com) for most up-to-date information regarding Intrinsically Safe approvals ref. #008-0547-00.
Sensing and Internet of Things
5
DIFFERENTIAL PRESSURE TRANSDUCER, MODEL FP2000
HOW TO ORDER
The FP2000 Order Code is an easy way for you to order exactly what you want the factory to build. Simply make one selection in each of the six
required categories. Choose adders and accessories only if you require them. By visiting our Web site at www.honeywell.com/sensing you can
view complete technical specifications for the FP2000.
Step 1
TRANSDUCER TYPE
o
o
Unit type
o psi
o torr
o mBar
o kPa
o bar
o in Hg
o mm Hg
o in H2O
Step 4
ADDERS
o Enhanced thermals
Differential: 0 °F to 180 °F
o Shunt cal
o CE rating
o Zero and span adjustments
Adder code
1y
o mV/V
o 5 Vdc
o 10 Vdc
o 4 mA to 20 mA (CE only)
o 4 mA to 20 mA (IS and CE)
2u
2e
2f
2y
2n (2N)
Step 3
PRESSURE RANGE
OUTPUT
Differential
Range code
Range code
o 0.5 psi
AN
o 100 psi
BR
o 1 psi
AP
o 150 psi
CJ
o 2 psi
AR
o 200 psi
CL
o 2.5 psi
AS
o 250 psi
CN
o 5 psi
AT
o 300 psi
CP
o 10 psi
AV
o 400 psi
CQ
o 15 psi
BJ
o 500 psi
CR
o 25 psi
BL
o 600 psi
CS
o 30 psi
BM
o 750 psi
CT
o 50 psi
BN
o 1000 psi
CV
o 75 psi
BP
Type Code
FDW
FDD
Differential - wet/wet
Differential - wet/dry
Step 2
ACCURACY
o 0.10 %
o 0.25 %
3d
9e
14c
Accuracy code
1
2
Basic
output
code
2u
2d
2g
2p
2N
If adding
1y, 3d, 9e
or 14c
2u
2e
2f
2y
2y
NOTE: If any ADDERS are required, the output code must be
revised. See step 4.
PRESSURE PORT
o 1/4-18 NPT female
o 1/4-18 NPT male
o 7/16-20 UNF female
o 7/16-20 UNF male
o G 1/4 B female
o G 1/4 B male
o 1/8-27 NPT female
o 1/8-27 NPT male
o M12 x 1.5 male
o M12 x 1.5 female
o 9/16-18 UNF SAE male
o 9/16-18 UNF SAE female
Port code
5a
5b
5c
5d
5f
5g
5h
5i
5p
5q
5r
5s
ELECTRICAL CONNECTOR
o Bendix PTIH-10-6P
o DIN 43650
o Mini DIN (40050)
o Integral polyurethane 5-ft cable
o 1/2 x 14 NPT conduit 5-ft cable exit
NOTE: If you choose any adder output from step 4, you must
revise your output code selection using this output code
chart. IS outputs available only on ranges up to 5000 psi.
ACCESSORIES
Mating connectors only
o Mini DIN
o Bendix
o mV/V
o 5 Vdc
o 10 Vdc
o 4 mA to 20 mA
o 4 mA to 20 mA (IS)
Acc. code
AA161
AA111
Connector code
6a
6m
6n
6q
6r
Step 5
Mating conn. with 15 ft. cable for Bendix connector (6A)
Without
With
shunt
shunt (3d)
o mV/V
AA113
AA513
o 4 mA to 20 mA
AA116
AA516
o 0 to 5/0 to 10 Vdc
AA117
AA517
EXAMPLE ORDER CODE FDW 1 CN 1Y 2Y 5B 6A
Selection Description
Transducer type
Accuracy
Pressure range
Adders
Output
Pressure port
Electrical output connections
Code
Differential wet/wet
0.10 %
250 psi
Enhanced temperature range
4 mA to 20 mA
1/4-18 NPT male
Bendix PTIH-10-6P
FDW
1
CN
1y
2y
5b
6a
There must be a code in each of the six basic code boxes. If there are no adders or accessories chosen, leave the boxes blank.
DESCRIPTION
Order code
BASIC CODE
Type
Accuracy
ADDER CODE (SEE STEP 4)
Range
Output
Pressure
Elect. conn.
Accessory code
Zero and span adjustments are located on the side. See drawing for details. No zero and span adjustments are available on mV/V output option.
6 sensing.honeywell.com
Extended
Shunt cal.
IS/CE rated
Pots
NOTES
WARRANTY/REMEDY
1. Accuracies stated are expected for best-fit
straight line for all errors, including linearity,
hysteresis, and non-repeatability through zero.
2. For low pressure ranges, temperature effects
may vary.
3. The wet/wet differential pressure transducer
has two separate, welded Hastelloy diaphragms.
In wet/dry unit, the wet port (high port) has
all-welded stainless steel and Hastelloy
construction. The dry port (low port) has no
isolation diaphragm.
4. For differential pressure ranges at 0.10 %
accuracy, non-amplified output @ 10 Vdc
excitation = 100 mV.
Honeywell warrants goods of its manufacture as being free of defective materials and faulty workmanship during the
applicable warranty period. Honeywell’s
standard product warranty applies unless agreed to otherwise by Honeywell in
writing; please refer to your order acknowledgment or consult your local sales
office for specific warranty details. If warranted goods are returned to Honeywell
during the period of coverage, Honeywell
will repair or replace, at its option, without
charge those items that Honeywell,
in its sole discretion, finds defective.
The foregoing is buyer’s sole remedy
and is in lieu of all other warranties,
expressed or implied, including those
of merchantability and fitness for a
particular purpose. In no event shall
Honeywell be liable for consequential,
special, or indirect damages.
While Honeywell may provide application assistance personally, through our
literature and the Honeywell web site, it
is buyer’s sole responsibility to determine
the suitability of the product in the application.
Specifications may change without
notice. The information we supply is
believed to be accurate and reliable as of
this writing. However, Honeywell assumes
no responsibility for its use.
FOR MORE INFORMATION
Honeywell Sensing and Internet of
Things services its customers through a
worldwide network of sales offices and
distributors. For application assistance,
current specifications, pricing or the
nearest Authorized Distributor, visit
sensing.honeywell.com or call:
International
+815 618 3231
USA/Canada
+302 327 8920
Honeywell
Sensing and Internet of Things
9680 Old Bailes Road
Fort Mill, SC 29707
008835-6-EN | 6 | 09/19
© 2019 Honeywell International Inc. All rights reserved.
m WARNING
PERSONAL INJURY
DO NOT USE these products as safety
or emergency stop devices or in any
other application where failure of the
product could result in personal injury.
Failure to comply with these
instructions could result in death or
serious injury.
m WARNING
MISUSE OF
DOCUMENTATION
•
•
The information presented in this
product sheet is for reference only.
Do not use this document as a
product installation guide.
Complete installation, operation,
and maintenance information
is provided in the instructions
supplied with each product.
Failure to comply with these
instructions could result in death or
serious injury.