Airflow Sensors
Microbridge Mass Airflow/Amplified
AWM3000 Series
Figure 1
Heater control circuit
FEATURES
1 Laser trimmed for improved sensor
interchangeability
1 Flow sensing up to 1.0 SLPM
1 Low differential pressure sensing
Like the AWM2000 Series, the dual
Wheatstone bridges control airflow measurement. The AWM3000 Series is amplified; therefore, it can be used to increase
the gain and to introduce voltage offsets
to the sensor output. The schematic in
Figure 3 depicts the amplification circuitry
on board the sensor. Also, the heater control circuit (see Figure 1) and the sensing
bridge supply circuit (see Figure 2) are on
board the package.
Figure 2
Sensing bridge supply circuit
Airflow
Figure 3
Differential instrumentation amplifier circuit
Honeywell 1 Sensing and Control 1 1-800-537-6945 USA 1 F1-815-235-6847 International 1 1-800-737-3360 Canada
71
Airflow Sensors
Microbridge Mass Airflow/Amplified
AWM3000 Series
AWM3000 SERIES ORDER GUIDE (Performance Characteristics @ 10.01 ±0.01 VDC, 25°C)
Catalog Listings
AWM3100V
AWM3150V
Flow Range (Full Scale)
+200 sccm
+30 sccm
Pressure Range
(See Application Note 1)
AWM3200V
AWM3300V
+1000 sccm
+2.0N H2O (5 mBar)
Output Voltage @ Trim Point
5 VDC @ 200 sccm
3.4 VDC @ 25 sccm
5 VDC @ 2N H2O
5 VDC @ 1000 sccm
Null Voltage
1.00 ±0.05 VDC
1.00 ±0.10 VDC
1.00 ±0.08 VDC
1.00 ±0.10 VDC
Null Voltage Shift, Typ.
+25° to −25°C, 25° to +85°C
±25 mV
±100 mV
±25 mV
±25 mV
Output Voltage Shift, Max.
+25° to −25°C
+25° to +85°C
−4% Reading
+4% Reading
±5% Reading
±5% Reading
+24% Reading (Note 3)
−24% Reading
−5% Reading
+5% Reading
Repeatability & Hysteresis, Max.
±0.50% Reading
±1% Reading
±0.50% Reading
±1% Reading
Min.
Typ.
Max.
Excitation VDC (Note 2)
8.0
10±0.01
15
Power Consumption (mW)
—
50
60
Response Time (msec) (Note 1)
—
1.0
3.0
Common Mode Pressure (psi)
—
—
25
Temperature Range
Operating: −25° to +85°C (−13° to +185°F); Storage: −40° to +90°C (−40° to +194°F)
Termination
2,54 mm (.100N) centers, 0,635 mm (0.025N) square
Weight (grams)
10.8
Shock Rating
100 g peak (5 drops, 6 axes)
Notes:
1. Initial warm-up time for signal conditioned circuitry is 1 minute max.
2. Output Voltage is ratiometric to supply voltage.
3. Temperature shifts when sensing differential pressure correlates to the density change of the gas over temperature. (See Application Note 1.)
4. Maximum allowable rate of flow change to prevent damage: 5 SLPM/1 sec.
MOUNTING DIMENSIONS (for reference only)
Note: Positive flow direction is defined as proceeding from
Port 1 (P1) to Port 2 (P2) and results in positive output. Do not
exert a force greater than 4.54kg (10 lbs.) in any direction.
72
Honeywell 1 Sensing and Control 1 1-800-537-6945 USA 1 F1-815-235-6847 International 1 1-800-737-3360 Canada
Airflow Sensors
Microbridge Mass Airflow/Amplified
AWM3000 Series
OUTPUT FLOW VS INTERCHANGEABILITY (Note 1)
Performance Characteristics @ 10.0 ±0.01 VDC, 25 C
AWM3100V
AWM3150V
AWM3200V (Note 2)
AWM3300V
Press. Flow Nom. Tol.
mBar sccm VDC ± VDC
Press Flow Nom. Tol.
mBar sccm VDC ± VDC
Flow Press Nom. Tol.
sccm N H2O VDC ± VDC
Press. Flow Nom. Tol.
mBar sccm VDC ± VDC
0.49
200
5.00
0.15
2.50
30
3.75
0.70
60.0
2.00
5.00
0.15
3.40
1000
5.00
0.15
0.42
175
4.80
0.16
1.70
20
2.90
0.45
53.0
1.75
4.59
0.15
2.90
900
4.90
0.16
0.35
150
4.50
0.17
0.84
10
1.95
0.20
46.0
1.50
4.16
0.16
2.40
800
4.80
0.17
0.28
125
4.17
0.18
0.42
5
1.50
0.10
38.0
1.25
3.70
0.20
2.00
700
4.66
0.18
0.21
100
3.75
0.19
0.34
4
1.40
0.08
30.0
1.00
3.25
0.22
1.60
600
4.42
0.19
0.14
75
3.27
0.19
0.26
3
1.30
0.08
23.0
0.75
2.65
0.22
1.20
500
4.18
0.20
0.09
50
2.67
0.17
0.17
2
1.20
0.07
16.0
0.50
2.15
0.19
0.80
400
3.82
0.21
0.04
20
1.90
0.13
0.08
1
1.10
0.06
8.0
0.25
1.55
0.11
0.54
300
3.41
0.19
0.00
0
1.00
0.05
0.00
0
1.00
0.05
0.0
0.00
1.00
0.08
0.31
200
2.96
0.17
0.12
100
2.30
0.14
0.00
0
1.00
0.10
Notes:
1. Numbers in BOLD type indicate calibration type, mass flow or differential pressure.
Tolerance values apply to calibration type only.
2. Differential pressure calibrated devices are not recommended for flow measurement.
Use flow calibrated devices for flow measurement.
OUTPUT CURVES
Airflow
Honeywell 1 Sensing and Control 1 1-800-537-6945 USA 1 F1-815-235-6847 International 1 1-800-737-3360 Canada
73
Airflow Sensors
Microbridge Mass Airflow/Amplified
AWM3000 Series
AWM3000 SERIES ORDER GUIDE (Performance Characteristics @ 10.01 ±0.01 VDC, 25°C)
Catalog Listings
AWM3200CR*
AWM3201CR*
Differential Pressure Range
0 - 2N H2O (5 mBar)
0 - 0.5N H2O (1.25 mBar)
Output Type
4 - 20 mA DC (linear)
4 - 20 mA DC (linear)
1 - 5 VDC (Note 2)
Output @ Trim Point
20.0 ±1 mA DC @ 2N H2O
20.0 ±1 mA DC @ .05N H2O
5.00 ±0.150 VDC
Null Output
4.00 ±0.3 mA DC
4.00 ±0.4 mA DC
3.00 ±0.050 VDC
Null Shift
+25° to −25°C, +25° to +85°C
±2 mA DC (max.)
±2 mA DC (max.)
±.050 VDC (max.)
Output Shift
+25° to −25°C
+25° to +85°C
+24% Reading
−31% Reading (Note 3)
+32% Reading
−32% Reading (Note 3)
−5% Reading
+5% Reading
Linearity Error
±5% Reading
±5% Reading
N/A
External Output Load
100 - 300 Ω (Note 4)
100 - 300 Ω (Note 4)
N/A
Response Time (Note 1)
60 msec (max.)
60 msec (max.)
3 msec (max.)
Repeatability & Hysteresis, Max.
±0.50% Reading
±0.50% Reading
±1% Reading
Excitation VDC
10 ±0.01
10±0.01
8-15
Power Consumption (mW)
—
50
100
Common Mode Pressure (psi)
—
—
25
Calibration Gas
Nitrogen
Temperature Range
Operating: −25° to +85°C (−13° to +185°F); Storage: −40° to +90°C (−40° to +194°F)
Termination
2,54 mm (.100N) centers, 0,635 mm (0.025N) square
Flow Range (Full Scale)
AWM3303V
±1000 sccm (1 SLPM)
Weight (grams)
10.8
Shock Rating
100 g peak (5 drops, 6 axes)
Notes:
1. Initial warm-up time for signal conditioned circuitry is 1 minute max.
2. Output Voltage is ratiometric to supply voltage.
3. Temperature shifts when sensing differential pressure correlates to the density change of the gas over temperature.
4. Output load connected from VOUT to GND (current sinking).
5. Maximum allowable rate of flow change to prevent damage: 5.0 SLPM/1.0 sec.
* A 5 micron filter must be used on differential pressure sensors.
MOUNTING DIMENSIONS (for reference only)
Note: Positive flow direction is defined as proceeding from
Port 1 (P1) to Port 2 (P2) and results in positive output. Do not
exert a force greater than 4.54kg (10 lbs.) in any direction.
74
Honeywell 1 Sensing and Control 1 1-800-537-6945 USA 1 F1-815-235-6847 International 1 1-800-737-3360 Canada
Airflow Sensors
Microbridge Mass Airflow/Amplified
AWM3000 Series
OUTPUT FLOW VS INTERCHANGEABILITY (Note 1)
Performance Characteristics @ 10.0 ± 0.01 VDC, 25 C
AWM3200CR (Note 2)
AWM3201CR (Note 2)
AWM3303V
Flow
sccm
Press. Nom. Tol.
N H2O mA DC ± mA DC
Flow
sccm
Press. Nom. Tol.
N H2O mA DC ± mA DC
Press Flow Nom. Tol.
mBar sccm VDC ± VDC
0
0.00
4.00
0.3
0
0.00
4.0
0.4
3.49
1000
5.00
0.15
7
0.25
5.75
0.3
35
0.10
7.2
0.4
2.42
800
4.82
0.18
15
0.50
7.70
0.4
42
0.13
8.0
0.4
1.59
650
4.67
0.20
22
0.75
9.75
0.4
53
0.17
9.4
0.5
0.83
400
4.42
0.20
25
0.81
10.21
0.5
61
0.20
10.4
0.5
0.31
200
3.96
0.15
30
1.00
12.00
0.6
71
0.25
12.0
0.6
0.00
0
3.00
0.05
37
1.25
13.90
0.7
81
0.30
13.6
0.7
-0.31
-200
2.03
0.18
45
1.50
16.00
0.8
87
0.35
15.2
0.8
-0.83
-400
1.62
0.20
52
1.75
18.00
0.8
97
0.40
16.8
0.9
-1.59
-600
1.35
0.25
55
1.83
18.50
0.9
105
0.45
18.4
1.0
-2.42
-800
1.15
0.30
60
2.00
20.00
1.0
113
0.50
20.0
1.0
-3.44
-1000
1.00
0.35
Notes:
1. Numbers in BOLD type indicate calibration type, mass flow or differential pressure.
Tolerance values apply to calibration type only.
2. Differential pressure calibrated devices are not recommended for flow measurement.
Use flow calibrated devices for flow measurement.
OUTPUT CURVES
Airflow
Honeywell 1 Sensing and Control 1 1-800-537-6945 USA 1 F1-815-235-6847 International 1 1-800-737-3360 Canada
75
很抱歉,暂时无法提供与“AWM3200V”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格 香港价格
- 1+1299.955311+155.36810
- 5+1222.319415+146.08921