CRIR E1
Commercial Carbon Dioxide (CO2) Sensor, 400 ppm to 2000 ppm,
up to 5000 ppm Extended Range
DESCRIPTION
VALUE TO CUSTOMERS
The CRIR E1 Commercial Carbon
Dioxide (CO 2) sensor is a single channel,
• Small size
non-dispersive infrared (NDIR) sensor.
• Maintenance free for normal indoor
applications
Within the CRIR E1 is a sensing chamber
• Enhanced long term stability
with an infrared source at one end and
• Higher accuracy: ±50 ppm ±5% of
a detector fitted with an optical filter
reading
at the other end. The source emits
• Consistency and repeatability
radiation at wavelengths which include
• Easy integration
the absorption band of CO 2 . The filter
FEATURES
blocks wavelengths which are not
POTENTIAL APPLICATIONS
sensitive to the presence of CO 2 , thereby
• HVAC, demand controlled ventilation
increasing selectivity and sensitivity.
• Indoor air quality (IAQ) measurement
• Automatic Baseline Correction
As the light passes through the sensing
• Air purification systems
• Temperature compensation
chamber, a fraction is absorbed if CO 2
• Smart /IoT (Internet of Things) systems
• UART digital interface
is present. The difference between the
light emitted by the source and received
by the detector can then be converted to
a CO 2 concentration reading.
The Automatic Baseline Correction
(ABC) function can automatically
calibrate the sensor’s lowest reading
over a pre-configured interval to
400 ppm CO 2 . This enhances long term
stability and may eliminate the need for
calibration.
• Single channel, non-dispersive infrared
technology
COMMERCIAL CARBON DIOXIDE SENSOR, 400 PPM TO 2000 PPM
CRIR E1
TABLE 1. SPECIFICATIONS
CHARACTERISTIC
PARAMETER
Target gas
carbon dioxide (CO2)
Operating principle
non-dispersive infrared (NDIR)
Standard range
400 ppm to 2000 ppm, up to 5000 ppm extended range
1, 2
Measurement interval
4s
Accuracy
±50 ppm ±5% of reading
Typical response time (T90)
97%
Operating voltage
4.5 V to 5.5 V unprotected against surges and reverse connection
Power consumption
300 mA peak, 30 mA average
Alarm output, open collector
1000 ppm/800 ppm normal state is conducting max 100 mA.
Transistor open at CO2 high or at sensor failure (see Figure 1).
Serial communication5
UART, Modbus protocol
Operating temperature range
0°C to 50°C
Storage temperature range
-40°C to 70°C
Operating humidity
0 %RH to 90 %RH non-condensed
Expected operating life
10 years
Maintenance
maintenance-free for normal indoor applications
3
6
Weight