DPR SERIES
32347489
Issue B
TruStability™ Board Mount Pressure Sensors
Standard Accuracy, Compensated/Amplified
±1.6 mbar to ±25 mbar | ±160 Pa to ±2.5 kPa |
±0.5 H2O to ±10 inH2O
DESCRIPTION
The TruStability™ DPR Series is a
POTENTIAL INDUSTRIAL
APPLICATIONS
piezoresistive silicon pressure sensor
• Heating, ventilation, air conditioning
offering a ratiometric analog output for
(HVAC)
reading pressure over the specified full
• Variable air volume (VAV) control
scale pressure span and temperature
• Damper control and duct air flow
range. These sensors are fully calibrated
• Filter monitoring/clogged filter
and temperature compensated for
detection
sensor offset, sensitivity, temperature
• Modulated furnace controls
effects, and non-linearity using an on-
• Indoor air quality
board Application Specific Integrated
• Leak detection
Circuit (ASIC). Calibrated output
• Pneumatic control
values for pressure are updated at
• Burner control
approximately 1 kHz. The DPR Series is
• Fuel-to-air rationing
calibrated over the temperature range
• Gas analyzers and meters
of -20°C to 70°C [-4°F to 185°F].
• Fume hoods and clean rooms
The sensor is calibrated for operation
from a single power supply of 5.0 Vdc.
FEATURES
These sensors measure differential
• Pressure range: ±1.6 mbar to ±25 mbar |
or gage pressures. The robust and
±160 Pa to ±2.5 kPa | ±0.5 inH2O to
durable housing, with its industry-
±10 inH2O
standard mounting configuration,
• Pressure types: Differential and gage
along with a choice of flexible electrical
• Total Error Band: As low as ±1.25 %FSS
terminations, is designed to withstand
tough application environments. The
sensors’ internal diagnostic functions
detect most internal failures, including
depending on pressure range (after
auto zero)
• Accuracy: ±0.25 %FSS BFSL (Full
Scale Span Best Fit Straight Line)
burst sensors, and may reduce the
• Stable offset voltage
need for redundant sensors in the
• Compensated temperature range:
system. The DPR Series is intended
-20ºC to 70ºC [-4ºF to 158ºF]
for use with non-corrosive, non-
• Low sensitivity to mounting orientation
ionic gases, such as air and other dry
• Output: analog voltage
gases. Custom calibrations, additional
• Overvoltage and reverse polarity
pressure ranges or options to extend the
performance of these sensors to include
non-corrosive, non-ionic liquids is
protected
• Industry-standard mounting
configuration and barbed ports
possible. All products are designed and
• Robust and durable package
manufactured according to ISO 9001
• Internal diagnostic functions
standards.
• RoHS compliant
PORTFOLIO
Honeywell offers a variety of
board mount pressure sensors for
potential use in medical and industrial
applications. Our categories of
pressure sensor measurement include
absolute, differential, gage or vacuum
gage, with unamplified or amplified
sensors and covering a wide pressure
range. To view the entire product
portfolio, click here.
TRUSTABILITY™ BOARD MOUNT PRESSURE SENSORS, DPR SERIES
TABLE 1. ABSOLUTE MAXIMUM RATINGS1
CHARACTERISTIC
MIN.
MAX.
UNIT
Supply voltage (Vsupply)
-5.0
12.0
Vdc
Voltage on output pin
-0.3
6.0
Vdc
1
Absolute maximum ratings are the extreme limits the device will withstand without damage.
TABLE 2. ENVIRONMENTAL SPECIFICATIONS
CHARACTERISTIC
PARAMETER
Humidity
0 %RH to 95 %RH, non-condensing
Vibration
15 g, 10 Hz to 2 kHz
Shock
100 g, 6 ms duration
ESD susceptibility
3 kV min, human body model
Life
1 million pressure cycles minimum
1
1
Life may vary depending on the specific application in which the sensor is utilized.
TABLE 3. WETTED MATERIALS1
MATERIAL
COMPONENT
PORT 1 (PRESSURE PORT)
Ports and covers
high temperature polyamide
Substrate
alumina ceramic
Adhesives
epoxy, silicone
O-Ring
silicone rubber
Electronic components
1
PORT 2 (REFERENCE PORT)
ceramic, silicon, glass, solder
silicon, glass, gold
Contact Honeywell Customer Service for detailed material information.
TABLE 4. SENSOR PRESSURE TYPES
PRESSURE TYPE
DESCRIPTION
Differential
Output is proportional to the difference between the pressures applied to each port (Port 1 - Port 2).
Gage
Output is proportional to the difference between applied pressure and atmospheric (ambient) pressure.
FIGURE 1. TEB COMPONENTS FOR TRUSTABILITY™
BOARD MOUNT PRESSURE SENSORS
FIGURE 2. TRANSFER FUNCTION LIMITS
Sources of Error
Pressure Hysteresis
Pressure Non-Repeatability
Thermal Effect on Offset
Thermal Effect on Span
Thermal Hysteresis
Accuracy
BFSL
Total
Error
Band
Output (%Vsupply)
Offset
Full Scale Span
Pressure Non-Linearity
Compensated Pressure Range
100
90
80
70
60
50
40
30
20
10
0
Ideal
2% Total
Error Band
0
1
Pmin.
Output (V) =
2
sensing.honeywell.com
2
3
4
5
6
7
8
Pressure (example unit)
9
10
Pmax.
0.75 x Vsupply x (Pressure
applied - Pmin.) + 0.05 x Vsupply
Pmax. - Pmin.
TRUSTABILITY™ BOARD MOUNT PRESSURE SENSORS, DPR SERIES
TABLE 5. OPERATING SPECIFICATIONS
CHARACTERISTIC
MIN.
TYP.
MAX.
UNIT
Supply voltage (Vsupply)1
4.75
5.0
5.25
Vdc
Minimum operating voltage
3.0
—
—
Vdc
—
2.7
3.5
mA
-40 [-40]
—
85 [185]
°C [°F]
-20 [-4]
—
70 [158]
°C [°F]
Startup time (power up to data ready)
—
—
5
ms
Response time
—
1
—
ms
Clipping limits:
upper
lower
—
2.5
—
—
97.5
—
%Vsupply
Accuracy4
—
—
±0.25
%FSS BFSL6
Output resolution
—
0.033
—
%FSS6