Protective Relays
WUV/WOV Series
Product Facts
Product Specifications
TERMINAL STRIPS
#6 - 32 SCREWS
n
Function 27/59
n
ANSI/IEEE C37.90-1978
n
UL File No. E58048
n
CSA File No. LR61158
R
R
3.0
3.0
1 /2
3 7 /8
3
2
3/4
1 /2
3
11 / 64" DIA.
4 MTG. HOLES
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
Notes:
1. Remove black screw for access to
the voltage trip adjustment.
2. Clockwise rotation of the adjustment potentiometer will raise the
voltage trip point.
11
Protective Relays
Voltage sensitive relays are
available for both AC and
DC applications for
over/undervoltage protection. Combination
over/undervoltage relays
provide bandpass capabilities. AC relays are either
single or three-phase type.
Three phase models are
designed to sense the average of the three phases or
the highest single phase.
Voltage trip points are
screwdriver adjustable, and
operation is time-delayed so
that momentary voltage
transients will not cause nuisance tripping.
Nominal Voltage — 120 VAC to 575
VAC
Phase — Single or Three
Line Frequency — 50-400 Hz
Pick-up to Drop-out Differential —
2.5% maximum
Drop-out Point (u/v models) —
70-100% of nominal voltage,
screwdriver adjustable
Pick-Up Point (o/v models) —
100-125% of nominal voltage,
screwdriver adjustable
Output Contacts — One set N.O.,
One set N.C.
Contact Ratings —
5 amp resistive at 120 VAC or 28 VDC
Operating Temperature Range —
-20˚C to +65˚C
Power Consumption —
2 VA maximum
Time Delay — 150-300 ms (UV Model)
Minimum Life — 500,000 operations
Single Phase
Three Phase
Typical Time Curve
Ordering Information
40.0
WUV
-1
-120
Voltage Above Set Point
Sample Part Number 䊳
Type:
WUV - Undervoltage
WOV - Overvoltage
No. Phases
1 = Single
3 = Three
Line Voltage VAC
120 416
208 440
220 460
230 480
240 525
380 575
30.0
Overvoltage Relays
WOV Series
20.0
10.0
0.0
-10.0
0
Options
P - Transient Protection
A - Two Normally Open Contacts
B - Two Normally Closed Contacts
H - 125VDC, 3A Contacts
0.05
0.1
0.15
0.2
Pick-Up Time Delay
0.25
0.3
Transient Protection — All voltage
relays will withstand momentary voltage
surges of twice the nominal rated input
voltage (standard).
Option “P” provides additional transient protection which complies with the
requirements of ANSI/IEEE C37.90-1978
Consult factory for additional
models.
11–13
Catalog 5-1773450-5
Revised 3-13
www.te.com
Dimensions are shown for
reference purposes only.
Specifications subject
to change.
Dimensions are in millimeters
unless otherwise specified.
USA: +1 800 522 6752
Asia Pacific: +86 0 400 820 6015
UK: +44 800 267 666
For additional support numbers
please visit www.te.com
很抱歉,暂时无法提供与“2-1618112-9”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格 香港价格
- 1+17802.551051+2283.36840