TECC0019C7
Issue 8
15-Apr-21
Page 1 of 2
SPECIFICATION CONTROL DRAWING
COMMUNICATION CABLE - FOUR PAIR 22AWG S/FTP CAT7 LSZH
The complete requirements for procuring the wire described herein shall consist of this document and the
issue in effect of the referenced specifications. This document takes precedence over documents referenced herein.
PRODUCT DETAILS
DESCRIPTION
Application:
100BASE-T4, 100BASE-TX, 100VG-AnyLAN,
1000Base-T (1 Gb Ethernet), 1000Base-TX
PHYSICAL CHARACTERISTICS
Structure
22 AWG
Conductor material
Stranded Annealed Cooper
(7/0.245) ± 0.02mm
Insulation
Conductor dimension(mm)
Insulation material
Insulation dimension(mm)
Nom. Thickness (mm)
0.42 mm
Twisting lay length
≤ 30 mm
Cabling lay length
≤ 200 mm
Filler
Material
N/A
Binder
Shield
Material
N/A
Individual shield & material
AL-Foil
Cabling
Stranded Tinned Copper Conductor
Colour-coded PE Insulation
LSFRZH Jacket
Packaging: Per customer request
4 Pairs
Conductor
75°C
61156-6,ISO/IEC 11801
IEC 60332-3-25 & IEC 60332-1-2
S/FTP
Number of Pairs
AWG
155Mbps ATM, 622Mbps ATM, 10Gb Ethernet
Rated temperature:
Reference Standard:
Flammability Rating:
Construction
Foamed PE
1.65 ± 0.05 mm
Primary overall shield & material Stranded Tinned Copper
Outer Jacket
CROSS SECTION
Shield nom. Coverage
35% Min.
Drainwire
N/A
Outer Jacket material
LSFRZH
Outer Jacket Thickness (mm)
1.0 mm Nom
Overall Nom Dimension (mm)
9.90 ± 0.30 mm
Outer Jacket Rip cord
N/A
Outer Jacket Colour
Per Customer Request
MECHANICAL CHARACTERISTICS
Outer Jacket
Operating Temp Range
-20°C to +75°C
Bulk Cable weight
94 kg/km
80 N
Max. recommended pulling tension
Min. bend radius (Install)
Tensile Strength
8 x O.D.
Elongation
Ageing Condition
≧100%
100°C x 168hrs
After Ageing Tensile Strength
≧70% of Unaging
After Ageing Elongation
≧50% of Unaging
No cracks -20°C/4hrs
≧9 Mpa
Cold Bend
ELECTRICAL CHARACTERISTICS
1
2
3
4
5
Jacket
Braid
AL-Foil
Insulation
Conductor
Finished Cable
Nom. Mutual Capacitance
≦ 5.6 nF/100m (@1kHz)
Pair-Ground Unbalance
≦160 pF/100m
Nom. Velocity of Propagation
65%
Max. Delay Skew
25 ns/100m
Max Conductor DC Resistance
Resistance Unbalance
145 Ω/km (@ 20°C)
Min. Insulation Resistance
5000 MΩ·km
Max. Operating Voltage - UL
300 V
2%
JACKET MARK
"TE CONNECTIVITY - TECC0019C7 - 4PR 22AWG STRANDED CAT 7
CABLE - YEAR OF MANUFACTURE - BATCH NUMBER - "
Tyco Electronics UK Ltd.
Faraday Road
Dorcan
SWINDON
SN3 5HH
Tel: +44 (0)1793 528171
Fax: +44 (0)1793 572516
TE Connectivity is a trading name of Tyco Electronics UK Ltd,
Which is registered in England and Wales, number 550926.
Registered office: Faraday Road, Dorcan, Swindon, SN3 5HH
Website : www.te.com
This drawing and the information set forth hereon are the property of Tyco Electronics
UK Ltd, and are to be held in trust and confidence. Publication, duplication, disclosure or
use for any purpose not expressly authorised in writing by Tyco Electronics UK Ltd is
prohibited.
This specification sheet takes precedence over
documents referenced herein. As Tyco
Electronics UK Ltd. reserve the right to make
changes in construction without notice please
contact Tyco Electronics UK Ltd to ensure that
this document is the latest issue.
©2021 Tyco Electronics UK Ltd, a TE Connectivity Ltd. company. All Rights Reserved.
TECC0019C7
Issue 8
15-Apr-21
Page 2 of 2
SPECIFICATION CONTROL DRAWING
COMMUNICATION CABLE - FOUR PAIR 22AWG S/FTP CAT7 LSZH
The complete requirements for procuring the wire described herein shall consist of this document and the
issue in effect of the referenced specifications. This document takes precedence over documents referenced herein.
ELECTRICAL CHARACTERISTICS CONTINUED
Frequency
Impedance
Upper Limit
Impedance
LowerLimit
ATT
RL
NEXT
PS NEXT
FEXT
PD
(MHz)
Zu (Ω)
ZI (Ω)
(Db/100m)
(dB Min)
(dB Min)
(dB Min)
(dB Min)
(ns/100m Max)
1
-
-
3.0
20.0
78.0
75.0
70.0
570.0
4
115.2
86.8
5.6
23.0
78.0
75.0
70.0
552.0
8
112.6
88.8
7.9
24.5
78.0
75.0
70.0
546.7
10
111.9
89.4
8.8
25.0
78.0
75.0
70.0
545.4
16
111.9
89.4
11.1
25.0
78.0
75.0
70.0
543.0
20
111.9
89.4
12.4
25.0
78.0
75.0
70.0
542.0
25
113.2
88.3
13.9
24.2
78.0
75.0
70.0
541.2
31.25
114.6
87.2
15.6
23.3
78.0
75.0
70.0
540.4
62.5
120.2
83.2
22.3
20.7
75.5
72.5
70.0
538.6
100
125.3
79.8
28.5
19.0
72.4
69.4
70.0
537.6
200
135.7
73.7
41.2
16.4
67.9
64.9
70.0
536.5
250
140.0
71.4
46.5
15.6
66.4
63.4
70.0
536.3
300
139.8
71.5
51.3
15.6
65.2
62.2
70.0
536.1
600
139.8
71.5
75.1
15.6
60.7
57.7
70.0
535.5
Remark : Cable that meet the requirements of the template are not required to be measured for return loss; alternately
cables that meet the return loss requirements are not required to be measured for characteristic impedance.
Approval
Tyco Electronics UK Ltd.
Faraday Road
Dorcan
SWINDON
SN3 5HH
Tel: +44 (0)1793 528171
Fax: +44 (0)1793 572516
Electronic sign off - no signatures will appear.
TE Connectivity is a trading name of Tyco Electronics UK Ltd,
Which is registered in England and Wales, number 550926.
Registered office: Faraday Road, Dorcan, Swindon, SN3 5HH
Website : www.te.com
This drawing and the information set forth hereon are the property of Tyco Electronics
UK Ltd, and are to be held in trust and confidence. Publication, duplication, disclosure or
use for any purpose not expressly authorised in writing by Tyco Electronics UK Ltd is
prohibited.
This specification sheet takes precedence over
documents referenced herein. As Tyco
Electronics UK Ltd. reserve the right to make
changes in construction without notice please
contact Tyco Electronics UK Ltd to ensure that
this document is the latest issue.
©2021 Tyco Electronics UK Ltd, a TE Connectivity Ltd. company. All Rights Reserved.
很抱歉,暂时无法提供与“2297801-1”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格 香港价格
- 17995+38.3306317995+4.96904