Protective Relays
WUVT/WOVT Series
Product Specifications
Product Facts
n
Function 27/59
n
ANSI/IEEE C37.90-1978
n
UL File No. E58048
n
CSA File No. LR61158
TERMINAL STRIPS
#6 - 32 SCREWS
R
R
3.0
4
1 /8
1 /2
5 /8
4
Overvoltage Models
The relay is de-energized at
normal voltages, N.C. contacts are closed and N.O.
contacts are open. The
relay will energize, when the
voltage rises and remains
above the O/V set point for
the duration of the set time
delay.
3
Undervoltage Models
The relay is energized at
normal voltage, N.C. contacts will open and N.O.
contacts will close. The
relay will de-energize when
the voltage drops and
remains below the U/V set
point for the duration of the
set time delay.
3
1 /2
4
1 /4
11 / 64" DIA.
4 MTG. HOLES
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
Single Phase
Three Phase
Ordering Information
Sample Part Number 䊳
WUVT -1
-120
Type:
WUVT - Undervoltage
WOVT - Overvoltage
Nominal Voltage — 100 VAC to 575
VAC
Phase — Single or Three
Line Frequency — 50-400 Hz
Pick-up to Drop-out Differential —
1% typical
Drop-out Point (u/v models) —
70-100% of nominal voltage,
screwdriver adjustable
Pick-Up Point (o/v models) —
100-125% of nominal voltage,
screwdriver adjustable
Output Contacts — One set N.O.,
One set N.C.
Contact Ratings —
5 amp resistive at 120 VAC or 28 VDC
Operating Temperature Range —
-40˚C to +70˚C
Power Consumption —
3 VA maximum
Time Delay — 0.5 to 20 seconds,
screwdriver adjustable
Voltage Reset — The reset is automatic when voltage returns to normal.
Notes:
1. Remove black screws for access
to the voltage and time delay
adjustment potentiometer.
2. Clockwise rotation of the voltage
adjust potentiometer will raise the
voltage trip point.
3. Clockwise rotation of the time
adjust potentiometer will increase
the time delay (Pick-up time for
O/V models, drop-out time for U/V
models).
4. The adjustments are single turn
potentiometers, use a small
screwdriver and do not force
beyond the limit stops.
5. On U/V models, when the voltage
falls to approximately 33% of
nominal or below, the relay will
drop out in 0.150 to 0 .300 seconds, regardless of the time delay
setting.
No. Phases
1 = Single
3 = Three (line to line)
Line Voltage VAC
100 240
115 380
120 416
150 440
200 460
208 480
220 525
230 575
Transient Protection — All voltage
relays will withstand momentary voltage
surges of twice the nominal rated input
voltage (standard).
Option “P” provides additional transient protection which complies with the
requirements of ANSI/IEEE C37.90-1978
Consult factory for additional
models.
Options:
Blank - Standard
A = 2 Form A Contacts
B = 2 Form B Contacts
H = 125VDC 3A Contacts
P = Transient Protection
11–14
Catalog 5-1773450-5
Revised 3-13
www.te.com
Dimensions are shown for
reference purposes only.
Specifications subject
to change.
Dimensions are in millimeters
unless otherwise specified.
USA: +1 800 522 6752
Asia Pacific: +86 0 400 820 6015
UK: +44 800 267 666
For additional support numbers
please visit www.te.com