Catalog: 1654001
Issue Date: 06.2011
Corcom Product Guide
General Purpose RFI Power Line Filters – Ideal for High Impedance Load
K Series
UL Recognized
CSA Certified
VDE Approved**
VK6
VK7 / EK7
1
RFI Power Line Filters
VK1 / EK1
VK3 / EK3
K Series
Specifications
• Suitable for high impedance loads
• Well suited to applications where pulsed,
continuous and/or intermittent RFI interference
is present
Maximum leakage current each Line to Ground:
@ 120 VAC 60 Hz:
@250 VAC 50 Hz:
VK Models
EK Models
.5 mA
1.0 mA
.21 mA
.36 mA
• EK models meet the very low leakage current
requirements for VDE portable equipment and
non-patient care medical equipment
Hipot rating (one minute):
Line to Ground:
Line to Line:
• Available with ground line inductor (choke)
Rated Voltage (max):
250 VAC
Operating Frequency:
50/60 Hz
Rated Current:
1 to 60A*
Ordering Information
10 E K 7 M
Suffix
M – Metric inserts (style 7 only)
Omit for standard or none
C – Ground choke (30, 40VK6 only)
Input / Output Style
1 – .250 [6.3] spade terminals
3 – Wire leads
6 – Threaded bolt
7 – IEC inlet* (line side)
.250 [6.3] spade terminals
(load side)
K Series
Leakage current designation
E – Low leakage (