KILOVAC High Voltage DC Contactors
KILOVAC CAP200 Series Contactor with 1 Form A (SPST-NO)
Contacts Rated up to 500 Amps, 12-900 Vdc
Product Facts
Performance Data
n
Designed to be the
smallest, lightest weight,
lowest cost sealed contactor
in the industry with its
current rating
n
Built-in coil economizer —
only 1.7W hold power @
12VDC and it limits back
EMF to 0V. (models
requiring external
economizer also available)
n
Optional auxiliary contact
for easy monitoring of
power contact position
n
Hermetically sealed —
intrinsically safe, operates
in explosive/harsh
environments with no
oxidation or contamination
of coil or contacts, including
long periods of nonoperation
n
Versatile coil and power
connections
n
RoHS versions available
Coil Operating Voltage (Valid Over Temperature Range)
9-36VDC
32-95VDC
48-95VDC
Voltage (Will Operate)
Voltage (Max.)
36VDC
95VDC
95VDC
Pickup (Close) Voltage Max.
9VDC
32VDC
48VDC
Hold Voltage (Min.)
7.5VDC
22VDC
34VDC
Dropout (Open) Voltage (Min.)
6VDC
18VDC
27VDC
Inrush Current (Max.)
3.8A
1.3A
0.7A
0.13A@12V,
Holding Current (Avg.)
0.03A@48V
0.02A@72V
0.07A@24V
Inrush Time (Max.)
130ms
130ms
130ms
Ordering Information
Typical Part Number 䊳
CAP200 A A A N A
Series:
CAP200 = 500 Amp, 12-900VDC Contactor
Contact Form:
A = Normally Open
H = Normally Open with Aux. Contacts
Coil Voltage:
A = 9-36VDC (1 = requires external coil economizer)
D = 32-95VDC (2 = requires external coil economizer)
J = 48-95VDC (3 = requires external coil economizer)
Contact Arrangement, Power
Contacts — 1 Form A (SPST-NO)
Rated Operating Voltage —
12 - 900 VDC
Continuous (Carry) Current,
Typical — 500 A @ 85°C, 400 mcm
conductors
Consult Factory for required conductors
for higher currents
Make/Break Current at Various
Voltages 1 — See graph next page
Break Current at 320VDC 1 —
2,000 A, 1 cycle 3
Contact Resistance, Typ.
(@200A) — 0.2 mohms
Load Life — See graph next page
Mechanical Life — 1 million cycles
Contact Arrangement, Auxiliary
Contacts — 1 Form A (SPST-NO)
Aux. Contact Current, Max. —
2A @ 30VDC / 3A @ 125VAC
Aux. Contact Current, Min. —
100mA @ 8V
Aux. Contact Resistance, Max. —
0.417 ohms @ 30VDC /
.150 ohms @ 125VAC
Dielectric Withstanding Voltage —
2,200 Vrms @ sea level
Insulation Resistance @ 500VDC —
100 megohms 2
Shock, 11ms 1/2 Sine, Peak,
Operating — 20 G
Vibration, Sine, 80-2000Hz.,
Peak — 20 G
Operating Temperature —
-40°C to +85°C
Weight, Nominal — .95 lb. (.43 kg)
Notes:
1 Main power contacts
2 50 at end of life
3 Does not meet dielectric & IR after
test, 1700 amp for unit with Aux.
Contacts
R = 28 Vdc with mechanical economizer
Coil Wire Length:
A = 15.3 in (390 mm)
D = Coil connector on relay (requires option
“E” or “X” in next step)
Coil Terminal Connector:
N = None
E = 9-pin subminiature “D” plug mounted on
contactor housing
F = 9-pin subminiature “D” plug mounted on 15.3 in
(390 mm) flying leads.
X = Special configuration (consult factory)
For factory-direct application assistance,
dial 800-253-4560, ext. 2055, or
805-220-2055.
Mounting & Power Terminals:
A = Bottom Mount & Male 10mm x 8 Terminals
7–16
Catalog 5-1773450-5
Revised 3-13
www.te.com
Dimensions are shown for
reference purposes only.
Specifications subject
to change.
Dimensions are in millimeters
unless otherwise specified.
USA: +1 800 522 6752
Asia Pacific: +86 0 400 820 6015
UK: +44 800 267 666
For additional support numbers
please visit www.te.com
KILOVAC High Voltage DC Contactors
KILOVAC CAP200 Series (Continued)
Outline Dimensions
M8 x 1.25 POWER TERMINALS
(HARDWARE SUPPLIED):
2 X M8 WASHER, STAINLESS
2 X M8 LOCKWASHER – SPLIT RING, STAINLESS
2 X M8 x 1.25 NUT, STAINLESS
TORQUE 80 TO 100 IN-LB (8.8 TO 11 NM)
1.05 ± .01
(26.67 ± .26)
2.29 ± .02 DIA
(58.19 ± .51)
A1 "+" POSITIVE TERMINAL
A2 "–" NEGATIVE TERMINAL
.225 ± .01DIA
(5.72 ± .26)
MOUNTING HARDWARE (NOT SUPPLIED):
2 X M5 BOLT
2 X M5 LOCKWASHER
2 X M5 NARROW WASHER
TORQUE 15 TO 30 IN-LB (1.7 TO 3.3 NM)
1.65 ± .01
(42.0 ± .26)
2.688 ± .01
(68.28 ± .26)
AUXILIARY CONTACT LEADS
WHITE = AUXILIARY CONTACT
(WHEN ORDERED)
BLACK = – COIL
RED = + COIL
COIL LEADS
SEE COIL WIRE
LENGTH IN P/N
2.20 ± .025
(55.81 ± .63)
2.85 ± .025
(72.3 ± .63)
STAINLESS
2.04 ± .02 DIA
(51.94 ± .51)
.55 ± .025
(14.04 ± .63)
2.05 ± .02
(52 ± .51)
2.58 ± .02
(65.6 ± .51)
3.17 ± .01
(80.48 ± .26)
.5 ± .01
(12.6 ± .26)
Estimated Make & Break Power Switching Ratings
Make and Break Power Switching Region
650A Break Only Above 650A
100,000
10,000
900
VDC
120
C
VD
100
400
VDC
Estimated Life (Cycles)
28 VDC
C
VD
DC
VDC
0V
270
600
18 0
1,000
7
10
KILOVAC High Voltage
DC Contactors
1
1
10
100
Load Current (A)
1,000
10,000
NOTES:
1) For resistive loads with 300µH maximum inductance. Consult factory for inductive loads.
2) Estimates based on extrapolated data. User is encouraged to confirm performance in application.
3) End of life when dielectric strength between terminals falls below 50 megohms @ 500VDC.
4) The maximum make current is 650A to avoid contact welding.
For factory-direct application assistance,
dial 800-253-4560, ext. 2055, or
805-220-2055.
7–17
Catalog 5-1773450-5
Revised 3-13
www.te.com
Dimensions are shown for
reference purposes only.
Specifications subject
to change.
Dimensions are in millimeters
unless otherwise specified.
USA: +1 800 522 6752
Asia Pacific: +86 0 400 820 6015
UK: +44 800 267 666
For additional support numbers
please visit www.te.com