Catalog 1308242
Issued 3-03
P&B
CNM5 series
Multifunction Time Delay Relay For
Plug-In or Panel Mounting
•
•
•
•
•
•
Five timing functions selectable via rotary switch
0.1 sec. to 9,990 hr. timing range
Fixed input type (120VAC ± 15%)
10A output relay with DPDT contacts
1/16 DIN style enclosure with 11-pin plug-in base
Thumbwheel switches for programming delay time
File E22575
File LR15734
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Timing Functions
Initial Dielectric Strength
See the following page for a complete description of timing functions.
Between Output Poles: 1,500V rms, 60 Hz.
Between Input and Output: 1,500V rms, 60Hz.
Input Data @ 25°C
Timing Specifications
Timing Ranges: 0.1 to 99.9 / 1 to 999 sec.;
0.1 to 99.9 / 1 to 999 min.;
0.1 to 99.9 / 1 to 999 / 10 to 9,990 hr.
Timing Adjustment: Digital adjustment via thumbwheel switches.
Tolerance: ±0.05% ± 0.04 sec.*
Repeatability (Including first cycle of operation.): < ± 0.05% ± 0.04 sec.*
Reset Time (power interruption): 45 ms, typ.; 60 ms, max.
Minimum Pulse Width, Control: 50 ms.
* Timing is synchronized with input voltage frequency. Accuracy is dependent on input
voltage frequency. Tolerance shows maximum variation from utility companies.
Contact Data @ 25°C
Arrangement: 2 Form C (DPDT).
Material: Silver-cadmium oxide alloy.
Rating: 10A @ 30VDC or 277VAC, resistive;
1/2 HP @ 250VAC; 1/3 HP @ 120VAC.
Expected Mechanical Life: 10 million operations.
Expected Electrical Life: 100,000 operations, min., at rated load.
Voltage: 120VAC ± 15%, 60 Hz.
Power Requirement: 3VA @ 120VAC.
Transient Protection: 13 Joule MOV.
Input Voltage & Limits
Nominal
Voltage
Minimum
Voltage
Maximum
Voltage
120VAC
102VAC
138VAC
Environmental Data
Temperature Range: Storage: -40°C to +85°C.
Operating: -10°C to +55°C.
Humidity: 85% relative humidity, non-condensing.
Mechanical Data
Termination: 11-pin octal style plug.
Enclosure: Black plastic 1/16 DIN (48mm x 48mm) case.
Sockets: Fits either 27E123 or 27E892 (snap-on) screw terminal sockets.
Weight: 4.3 oz. (122g) approximate.
Ordering Information – Authorized distributors are more likely to stock boldface items listed below.
Time Delay Relay
Accessory
Input Voltage
Part Number
120VAC
CNM5
Outline Dimensions
Part Number
Name
Description
SSA-24C667
Mounting Clip
Ratchet-fit clip slides onto CNM5 from behind
to secure CNM5 in panel mount applications.
Mounting Clip Dimensions
1.88
(47.8)
.32
(8.1)
SSA-24C667
2.83
(71.9)
Mounting Clip
1.88
(47.8)
1.76
(44.7)
3 1 2 S
3.15
(80.0)
.560
(14.2)
.64
(16.3)
Fits 1.77 x 1.77 (45 x 45) panel cutout.
Wiring Diagrams (Bottom Views)
2.283 1.970
(58.0) (50.0)
2.047
(52.0)
.591
(15.0)
1.654
(42.0)
1.890
(48.0)
(pins numbered clockwise from keyway)
EXTERNAL CONTROL SWITCH**
CONTROL
1 11
INPUT
Optional Solid State Input Interface
1 11
INPUT
**Important: A dry circuit switch is recommended. A "dry circuit" switch is one rated to
reliably switch currents of less than 50mA. Use of a switch rated for other than dry circuit
may result in failure of the time delay relay to function properly.
Dimensions are shown for
reference purposes only.
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Specifications and availability
subject to change.
www.tycoelectronics.com
Technical support:
1215
Refer to inside back cover.
Catalog 1308242
Issued 3-03
P&B
Timer Function Descriptions
Repeat: Output relay is turned on at end of programmed time interval which is
started by application of input power. Relay stays on for equal time interval, then
turns off and cycle is repeated on a free-running basis with equal on and off times
until terminated by removal of input power. LED is flashing when output relay is
off and on continuously when the relay is on. Applying CONTROL input during
timing will have no effect on timing or the state of the relay.
LED to show time status.
See functional explanation for details.
One Shot: Output relay is turned on by applying CONTROL input with input
voltage present or application of input voltage with the CONTROL input on.
Immediately upon either, timing is initiated with the output relay turning off at the
completion of the selected time interval. Applying CONTROL input after time out
will reset the timer, turn on the output relay and initiate another time interval. LED
is on continuously when output relay is off and flashes when the relay is on.
Applying CONTROL input during timing will have no effect on timing or the state
of the relay.
REPEAT
ONE SHOT
OFF DELAY
INTERVAL
ON DELAY
3
1
2
TIME SET
000 TO 999
Off Delay: Output relay is turned on by applying CONTROL input with input
voltage present or application of input voltage with the CONTROL input on. The
time interval will be started by removing the CONTROL input with the output relay
turning off at completion of the time interval. Reapplying the CONTROL during
timing will reset the time to zero and inhibit timing until removed. LED is off when
CONTROL input is on, flashing during timing and on continuously when the output
relay is off.
S
TIME
BASE
Interval: Output relay is turned on for a programmed time interval by applying
input voltage. LED flashes when output relay is on and is on continuously when
the output relay is off. Applying CONTROL input will have no effect on timing or
the state of the relay.
Time Base:
.1 S
S
.1 M
M
.1 H
H
10 H
=
=
=
=
=
=
=
1/10 Seconds
Seconds
1/10 Minutes
Minutes
1/10 Hours
Hours
10 Hours
Dimensions are shown for
1216 reference purposes only.
Timing Range 0.1 to 99.9 Seconds
Timing Range 1 to 999 Seconds
Timing Range 0.1 to 99.9 Minutes
Timing Range 1 to 999 Minutes
Timing Range 0.1 to 99.9 Hours
Timing Range 1 to 999 Hours
Timing Range 10 to 9990 Hours
Dimensions are in inches over
(millimeters) unless otherwise
specified.
On Delay: Output relay is off for a programmed time interval which is started by
applying input voltage. LED flashes when output relay is off and is on continuously
when the output relay is on. Applying CONTROL input will have no effect on timing
or the state of the relay.
Specifications and availability
subject to change.
www.tycoelectronics.com
Technical support:
Refer to inside back cover.
很抱歉,暂时无法提供与“CNM5”相匹配的价格&库存,您可以联系我们找货
免费人工找货