CORCOM Product Guide
The CHAMELEON Adaptable Module for General, High Performance or
Medical Applications
P Series
UL Recognized
CSA Certified
VDE Approved
PS Unfiltered
PS000SS30
PS Filtered
The P series power entry module offers fuller flexibility of
design in a more compact package.
H models provide susceptibility protection without leakage current associated with line-to-ground capacitors and
are designed to allow equipment to meet UL 544 for patient
care and non-patient care equipment.
As the first 10 amp module to provide all five power entry
functions in one compact design, the CHAMELEON
module readily adapts to its environment and the needs of
international markets.
Also available is an interconnection block, B models.
The block connects the voltage selection terminals of an
unfiltered CHAMELEON module with a switch and and IEC
connector to reduce external wiring.
• Snap-in or flange mounting
L Models – High performance medical filter versions that
are designed to help bring most digital equipment (including switching power supplies) into compliance with
EN55022, Level B (as well as FCC part 15J, Class B)
conducted emissions limits while additionally allowing
equipment to meet UL544, UL2601and EN60601 for patient
care equipment and non-patient care equipment. They are
available with current ratings of 6 and 10 amps. High
performance versions are available with horizontal mounting ears, single voltage, complete can shield with options
for switch, fuses and current ratings only. Extenders are
not available.
P Series
• IEC power line connector
• Both North American and European fusing capabilities
• Two voltage selections
• Optional DPST on/off switch
• Filtering options for general purpose, medical and
high-performance applications.
The CHAMELEON modules compact design and modular
construction will allow you to select the power entry
features you require — without altering the panel cutout.
And the Chameleon module, with adapters, will fit any
standard panel cutout.
The CHAMELEON module has four filter options.
S models offer protection for general purpose applications where line-to-ground and line-to-line noise must be
controlled. The filters are designed to meet low leakage
requirements of VDE portable equipment. They are
available in current ratings of 3, 6 and 10 amps.
Z Models – High performance filter versions are designed
to help bring most digital equipment (including switching
power supplies) into compliance with EN55022, Level B
(as well as FCC Part 15J, Class B) conducted emissions
limits. They are available with current ratings of 6 and 10
amps. High performance versions are available with
horizontal mounting ears, no extenders, single voltage,
complete can shield with options for switch, fuses and
current ratings only.
Tyco Electronics
CORCOM Products
PE Filter with "A" Shield
122
Catalog 1654001
Revised 03-04
Dimensions are in inches and
millimeters unless otherwise
specified. Values in italics
are metric equivalents.
Dimensions are shown for
reference purposes only.
Specifications subject
to change.
USA Cust. Svc.: 1-800-468-2023
CORCOM Prods: 1-847-680-7400
1-508-992-4495
Germany:
49-89-6089-0
www.cor.com
www.tycoelectronics.com
CORCOM Product Guide
The CHAMELEON Adaptable Module for General, High Performance or
Medical Applications (Continued)
P Series
P Series Part Number Schematic
Part numbers are constructed by selecting the alphanumeric character which represents the desired feature.
Mounting Extender
Style
Options*
Switch
Options
Voltage
Select
Fuse
Options
Filter
Type
Filter
Current
Shield
Options*
P S J 0 X S S 6 0
The part number PSJ0XSS60 would
represent the equivalent of CORCOM
J Series 6J4. The part would feature
the J extender to fit the current 6J4
panel cutout, and includes no switch,
dual voltage select, single fusing, and
a 6-amp general purpose filter.
Switch Option
0 = Blank
S = Double pole
single throw
(DPST)
Extender
Option
0 = None
C = FN260
J = J Series
L = L Series
Filter Current
0 = No filter
3 = 3 amps
6 = 6 amps
X = 10 amps
Fuse Options
D = Dual fuse
S = Single fuse
Input Voltage Select
0 = Single voltage
S = Dual voltage
select (SMPS)
X = Dual voltage
select (series/parallel)
Filter Type
0 = No filter
B = Interconnection
block✝
H = Medical Filter
L = High Performance
Medical
S = General purpose
Z = High Performance
Power Entry Modules
Mounting Style
E = Mounting ears
(Horizontal)
S = Snap-in
M = Mounting ears
(Vertical)
Shield Options
0 = No shield
A = Filter shield
B = Complete
Shield
C = Complete can
(for L & Z models)
Part Numbers (partial list)
PS000S000
PS0XSS000
PS0S0SBX0
PS000SH30
PS00SDH3A
PS0S0SH60
PS0SSDH6A
PS00SSHXA
PS0SSSHX0
PS000SS30
PS0S0SS30
PS0SSSS6B
PS0SXDS60
PSJ0XSS60
PSLS0SS60
PS0SXSS60
PS00SSSXA
PS0SSSSX0
PE000DL6C
PE000DLXC
PE000DZ6C
PE000DZXC
PE000SL6C
PE000SLXC
PE000SZ6C
PE000SZXC
PE000SS30
PE0S0SS30
PE000SS60
PE0SSSSX0
PE000SZXC
PE0SSS000
PE0SSSH60
PE0S0DL6C
PE0S0DLXC
PE0S0DZ6C
PE0S0DZXC
PE0S0SL6C
PE0S0SLXC
PE0S0SZ6C
PE0S0SZXC
Extender for
J-Series or others
Fuse holder
Optional switch
Optional filter
Additional extender which allows the P series to adapt to CORCOM's L
series product cutout, as well as the panel cutout of Schaffner and Delta
parts is available.
* Extenders cannot be added to units with B shields.
✝ When using the interconnection block, the last 3 digits of the part number
are BX(0, A, or B).
123
Catalog 1654001
Revised 03-04
Dimensions are in inches and
millimeters unless otherwise
specified. Values in italics
are metric equivalents.
Dimensions are shown for
reference purposes only.
Specifications subject
to change.
USA Cust. Svc.: 1-800-468-2023
CORCOM Prods: 1-847-680-7400
1-508-992-4495
Germany:
49-89-6089-0
www.cor.com
www.tycoelectronics.com
CORCOM Product Guide
The CHAMELEON Adaptable Module for General, High Performance or
Medical Applications (Continued)
P Series
Filter Options
Voltage Selection
The P series of power entry modules provides a dual
voltage selector which is integrated with the fuseholder.
To simplify the wiring in each individual application, Tyco
Electronics provides dedicated voltage selectors for
different voltage selection schemes. The two most popular
schemes are the parallel and serial for dual primary
transformers and the “DPST switch” for switching mode
power supplies (jumper types.) P series products with an
“S” as the fifth digit are specifically designed for “jumper”
type applications associated with switching mode power
supplies.
P series products with an “X” as the fifth digit are specifically designed for dual primary transformer applications.
The voltage selector installed will allow proper wiring from
these applications. No matter what voltage selection
scheme is used, wiring is always made to the same four
terminals.
Fuseholder
Another feature of the P series power entry module is a versatile fusing arrangement. Its fuseholder can hold two 1/4”
x 1-1/4” or 5 x 20mm fuses. It can also be converted to
accept one fuse with a conversion clip that bridges one of
the two fuse chambers.
The conversion clip is installed on the P Series power entry
modules set for single fusing (those with part numbers with
an “S” as the sixth digit). Units with a “D” as the sixth digit
do not include a conversion clip.
Four filtering options are available in three current ratings.
S models (those with an S as the seventh digit) provide
general purpose filtering for both line-to-ground and lineto-line noise. The increased inductance of the P series
allows better performance than most power entry modules
on the market. The S models will generally allow
compliance with FCC limits for linear power supplies.
The high-performance Z models are available for general
applications requiring higher attenuation.
The H models greatly reduce line-to-ground capacitance
in compliance with UL 544 low leakage current
specification.
The high-performance L models are available for medical
applications requiring higher attenuation.
Electrical Schematics
H Model
S Model
L Model
LINE
LOAD
Interconnection Block
Installation of the unfiltered versions of the P series involves
wiring of the IEC socket to the switch and the switch to the
fuseholder. Labor can be eliminated by ordering the
product with an interconnection block. This feature,
designated by a BX in the seventh and eighth digits,
prewires the module for easier installation. The wiring is
protected with the plastic case to better prevent access to
the terminals and connections.
Wiring can be further simplified by ordering a PA100
connector assembly. See page 131 for accessories.
The dimensions of this alternative are the same as the
filtered versions.
Z Model
LINE
LOAD
Shield
A new feature available on the P series is an RF shield.
The metal shield, available on filtered models, provides
shielding from radiated emissions and provides an
additional RF ground for the filter to the case.
The shield is available in two versions, a shield of the filter
components (designated by A as the ninth digit) and a
complete shield (designated by B as the ninth digit).
The A shield covers the filter portion of the module and
increases performance of the filter by protecting the
components from magnetic coupling. This shield improves
RF ground connection to the case while still allowing the
use of the P Series extender.
A Shield
B Shield
The B shield covers the entire power entry module with
metal, protecting the equipment from all radiated noise.
Used with the filter, the shield provides the most secure
protection from RFI noise problems. The B shield cannot
be used with any extender.
124
Catalog 1654001
Revised 03-04
Dimensions are in inches and
millimeters unless otherwise
specified. Values in italics
are metric equivalents.
Dimensions are shown for
reference purposes only.
Specifications subject
to change.
USA Cust. Svc.: 1-800-468-2023
CORCOM Prods: 1-847-680-7400
1-508-992-4495
Germany:
49-89-6089-0
www.cor.com
www.tycoelectronics.com
CORCOM Product Guide
The CHAMELEON Adaptable Module for General, High Performance or
Medical Applications (Continued)
P Series
Specifications – Unfiltered Models
Hipot rating (one minute):
line-to-ground
line-to-line
Operating frequency:
Specifications – Filtered Models
1500 VAC
1450 VDC
50/60 Hz
Rated voltage (max.):
250 VAC
Rated current, all unfiltered models:
10A @ 120 VAC
10A @ 250 VAC
Recommended use connector - no solder
Voltage Selection Schemes
1) Dual Primary Transformer Type:
115V
230V
Power on/off
Hot
G
Note 1
Note 2
Note 1
Note 2
A
B
Ground
Neutral
C
115V
115V
Transformer
primary
Provision for
single fusing
2) Jumper Type:
115V
230V
Power on/off
G
Note 1
Note 1
Neutral
A
B
Ground
Note 1
.187 x .032 [4.8 x .81] terminal tabs
Minimum insertion loss in dB:
Line-to-ground in 50 ohm circuit
Current
Frequency-MHz
Rating
.03 .1 .15 .5 1
3
5
H Models
03A
7 17 21 27 30 29 26
06A
8 11 15 17 19 18
10A
3
5
8 10 12 11 11
S Models
03A
7 17 21 27 33 40 44
06A
8 12 17 23 32 36
10A
3
5 10 13 23 27
C
Note 1
H
Power
input
Sel.
Jumpers
D
SMPS
Provision for
single fusing
Note 1: Jumpers are required if a filter or interconnection module is not
used.
Note 2: Location of optional filter. Jumpers are required if a filter or
interconnection module is not used.
Current
Rating
.01 .05
Z Models
06A
8 21
10A
5 17
L Models
06A
8 21
10A
5 17
30
23
16
10
15
13
10
50
44
35
32
30
27
Dimensions are in inches and
millimeters unless otherwise
specified. Values in italics
are metric equivalents.
.1
Frequency-MHz
.15 .5
1
5
10
30
27
22
30 37
24 27
43
32
49
52
52
47
42
40
27
22
29 34
23 24
35
25
25
21
21
18
16
14
10
30
48
40
40
41
35
32
50
55
55
45
45
45
Line-to-line in 50 ohm circuit
Current
Frequency-MHz
Rating
.10 .15 .5 1
3
5
H Models
03A
2
4 12 18 31 40
06A
2
4 12 16 26 35
10A
2
4 12 16 26 33
S Models
03A
2
4 12 15 30 48
06A
2
4 12 15 22 42
10A
2
4 12 15 22 42
Current
Rating
.01 .05
Z Models
06A
10 15
10A
10 20
L Models
06A
10 15
10A
10 20
Catalog 1654001
Revised 03-04
10
D
H
Hot
Terminals:
Power Entry Modules
Operating voltages: Selectable or fixed
115/230 VAC
Fuseholder:
Accepts one or two fuses
1/4 x 1-1/4 or 5 x 20 mm
Conversion clip provided on fuseholder
for single fuse models.
Switch:
Double-insulated rated for 10,000
operations at full load.
51 Amp inrush capability
Terminals:
.187 x .032 [4.8 x .81] terminal tabs
Maximum leakage current, each line-to-ground:
@ 120 VAC 60 Hz:
H Models
2 µA
S Models
0.25 mA
@ 250 VAC 50 Hz:
H Models
5 µA
S Models
.50 mA
Hipot rating (one minute):
line-to-ground
1500 VAC
line-to-line
1450 VAC
Operating voltages:
Selectable or fixed
115/230 VAC
Operating frequency:
50/60 Hz
Rated voltage:
120/250 VAC
Conversion clip provided on fuseholder
for single fuse models
Switch:
Double-insulated, rated
for 10,000 operations at full load.
51 Amp inrush capability.
Dimensions are shown for
reference purposes only.
Specifications subject
to change.
.1
Frequency-MHz
.15 .5
1
5
10
30
34
20
44 75
35 67
75
75
75
75
70
70
60
60
34
20
44 75
35 67
75
75
75
75
70
70
60
60
USA Cust. Svc.: 1-800-468-2023
CORCOM Prods: 1-847-680-7400
1-508-992-4495
Germany:
49-89-6089-0
www.cor.com
www.tycoelectronics.com
125
CORCOM Product Guide
The CHAMELEON Adaptable Module for General, High Performance or
Medical Applications (Continued)
P Series
Case Styles
PS/PSL
Filtered
Unfiltered
Panel Cutout
0.06 R Max.
1.52
C
C
E
(1) 0.02 R Min.
.508
.225 Max.
5.72
B1
.225
5.72
D
(1) For snap-in applications, the D
sides of the cutout must have a .02
[.508] radius on the installation side.
Note: Snap-in models allow front
mounting only. PS not recommended
for plastic panels.
B2
A
PE
Filtered
Unfiltered
Panel Cutout
.06 R Max
1.52
E
C
C
.020 R Min
.508
.225 Max.
5.72
D
B1
.225 Max.
5.72
D
B2
F
F
A
PM
Filtered
Unfiltered
Panel Cutout
A
D
D
F
E
C
.225 Max.
5.72
B1
.225 Max.
5.72
B2
F
.06
1.52
R Max
126
Catalog 1654001
Revised 03-04
ACTUAL
MEASUREMENTS
A = 1.2"
B = 2.13"
Dimensions are in inches and
millimeters unless otherwise
specified. Values in italics
are metric equivalents.
Dimensions are shown for
reference purposes only.
Specifications subject
to change.
USA Cust. Svc.: 1-800-468-2023
CORCOM Prods: 1-847-680-7400
1-508-992-4495
Germany:
49-89-6089-0
www.cor.com
www.tycoelectronics.com
CORCOM Product Guide
The CHAMELEON Adaptable Module for General, High Performance or
Medical Applications (Continued)
P Series
Case Styles
PSC/PSJ
Unfiltered
Filtered
Panel Cutout
0.06 R Max.
1.52
C
C
E
Power Entry Modules
(1) 0.02 R Min.
.508
D
.225 Max.
5.72
A
B1
Filtered Versions
.225
5.72
(1) For snap-in applications, the D
sides of the cutout must have a .02
[.508] radius on the installation side.
Note: Snap-in models allow front
mounting only. PS not recommended
for plastic panels.
B2
Case Dimensions
Part No.
"A" Shield
A
B1
B2
C
D
(max) (max) (max) (max)
PS
PSL
C
PE
PM
0.225 Max.
.508
B
PSC
PSJ
"B" Shield
1.24
31.49
1.24
31.49
1.98
50.29
1.24
31.49
1.24
31.49
1.24
31.49
1.93
49.02
1.93
49.02
1.93
49.02
1.93
49.02
1.93
49.02
1.93
49.02
2.13
54.1
2.13
54.1
2.13
54.1
2.13
54.1
2.13
54.1
2.13
54.1
2.31
58.67
2.31
58.67
2.31
58.67
2.9
73.66
2.51
63.75
2.72
69.09
E
F
+.008/-.000 +.008/-.000
+.20/-.00
+.20/-.00
1.06∆
26.93
1.12
28.45
1.122
28.5
1.06
26.93
1.06
26.93
1.06
26.93
2.201* —
55.91
2.201* —
55.91
2.201* 1.575
55.91 40.0
2.13 2.496
54.1 63.4
2.52
—
64.01
2.6+ —
66.0
* Panel cutout for thickness of .031 - .079 [0.8 - 2.0]. For panel thickness
at .083 - .114 [2.1 - 2.9] use 2.213 [56.21].
+ Panel cutout for thickness of 0.06 - 0.09 [0.76 - 2.29].
∆ For shielded models use D=1.12 +.008/-.000.
Shields can be used only with filtered models.
Shields add approximately 0.06" to depth.
B shield may not be used with J or C extender.
C
Rear View
Filtered
0.225 Max.
.508
B
Unfiltered
A B C D
A B C D
L
N
127
Catalog 1654001
Revised 03-04
Dimensions are in inches and
millimeters unless otherwise
specified. Values in italics
are metric equivalents.
Dimensions are shown for
reference purposes only.
Specifications subject
to change.
USA Cust. Svc.: 1-800-468-2023
CORCOM Prods: 1-847-680-7400
1-508-992-4495
Germany:
49-89-6089-0
www.cor.com
www.tycoelectronics.com