General Purpose Relays
Industrial Relays
Potter & Brumfield
W6/W9 Series Magnetic Hydraulic P&B Circuit Breakers
n Designed
for the international market. UL Recognzied (UL1077 and
UL1500), CSA Accepted and VDE approved.
n Ratings to 50 amps.
n Heavy duty #10-32 stud connections. (W9)
n Quick-connect or screw terminals. (W6)
n Several delay curve options.
n Trip-free operation.
Agency Approvals
UL:
Recognized as Supplementary Protector under UL 1077. Available
models meet Ignition Protection requirements in accordance with
UL1500. File E69543
CSA: Accepted as a Supplementary Protector. File LR15734.
VDE: Approved to VDE 0642/EN 60 934 (Circuit Breakers for Equipment)
License No. 73782
Users should thoroughly review the technical data before selecting a product part number.
It is recommended that users also seek out the pertinent approvals files of the agencies/
laboratories and review them to confirm the product meets the requirements for a given
application.
Electrical Data
Calibration:
Breakers will hold 100% of rated current.
Breakers may trip between 101% and 124% of rated load (134% for AC/
DC units).
Breakers must trip at 125% of rated load and above (135% for AC/DC
units).
Dielectric Strength: 50/60 Hz., 1500V: DC, 1100V
Insulation Resistance: 100 Megaohms at 500VDC
Endurance:
10,000 on/off cycles - 6000 at rated load, 4000 at no load.
Units tested at six cycles per minute, 1 second on and 9 seconds off at
25°C ambient.
Typical Resistance and Impedance
Current
DC
50/60
(Amps.) Resistance
Impedance
(Ohms)
(Ohms)
0.2
90
90
1.0
1.2
1.2
2.0
0.28
0.28
5.0
0.04
0.04
10.0
0.013
0.013
20.0
0.004
0.005
30.0
0.0027
0.004
40.0
0.002
0.002
50.0
0.0015
0.0015
Tolerance: 0.1 - 4.99 ± 15%; 5 - 9.99 ± 20%; 10 - 15 ± 25%; 16 - 30 ± 50%.
Mechanical/Environmental Data
Operating Temperature: -40°C to +85°C.
Humidity: Meets requirements of Mil-STD-202 method 103.
Shock: Tested per Mil-STD-202, method 213, test condition C
(100g @ 6 ms)
Vibration: Tested per Mil-STD-202, method 201, 10-55 Hz., 0.06”
(1.52mm) total excursion in 2 planes.
11-2015, Rev. 1115
www.te.com
© 2014 Tyco Electronics Corporation,
a TE Connectivity Ltd. company
Datasheets and product specification
according to IEC 61810-1 and to be used
only together with the ‘Definitions’ section.
Mechanical/Environmental Data (continued)
Fungus and Moisture Resistance:
Special moisture resistant finish applied to all ferrous parts.
Plastic parts are made of inherently fungus resistant material.
Marking:
International “1” and “0” symbols are marked on the toggle for both W6 and
W9. W9 units have “ON” and “OFF” molded into the area at the base of the
toggle.
Mounting:
Units are mounted with two #6-32 screws from the front of the panel.
Metric models for use with M3 x 0.5 screws are available. To maintain
published performance specifications, units should not be mounted more
than 90° from their normal upright position.
Weight: Approximately 2.5 ounces per pole.
Approvals and Ratings Table 1
W6 Series
Maximum
Voltage
65
277
277
277/480
UL1077/CSA (All Circuit Functions)
Current Interrupting
Frequency
Phase
Rating
Capacity
(Hz)
(Amps)
(Amps)
DC
0.2 - 50
2,000
50/60
1
0.2 - 20
5,000
50/60
1
21 - 50
2,500
50/60
3Ø-Wye
0.2 - 20
5,000
W9 Series
UL1077/CSA (All Circuit Functions)
Maximum
Voltage
Frequency
(Hz)
Phase
65
277
277/480
DC
50/60
50/60
1
3Ø-Wye
W6 or W9 Series
Current
Rating
(Amps)
0.2 - 50
0.2 - 50
0.2 - 20
Interrupting
Capacity
(Amps)
2,000
5,000
5,000
VDE (Circuit Function X)
Maximum
Voltage
Frequency
(Hz)
Phase
65
250
250
415/240
DC
50/60
50/60
50/60
1
1
3Ø
W6 or W9 Series
Current
Rating
(Amps)
0.2 - 50
0.2 - 30
31 - 50
0.2 - 30
Interrupting
Capacity
(Amps)
2,000
5,000
2,000
5,000
UL1500 (Circuit Function X)
Maximum
Voltage
Frequency
(Hz)
Phase
48
125/250
250
DC
50/60
50/60
1
3Ø-Wye
Datasheets and product data is subject to the
terms of the disclaimer and all chapters of
the ‘Definitions’ section, available at
http://relays.te.com/definitions
Current
Rating
(Amps)
0.2 - 50
0.2 - 50
0.2 - 50
Interrupting
Capacity
(Amps)
3,000
1,000
1,000
Datasheets, product data, ‘Definitions’ section, application notes and all specifications
are subject to change.
1
General Purpose Relays
Industrial Relays
Potter & Brumfield
W6/W9 Series Magnetic Hydraulic P&B Circuit Breakers (Continued)
Time vs Current Trip Curves For W6 Series and W9 Series
AC 50/60 Hz.
DC & 50/60 Hz.
125%
150%
200%
400%
600%
800%
TIME IN SECONDS
100
10
1
100 ms max.
55 ms max.
30 ms max.
15 ms max.
12 ms max.
12 ms max.
.1
100
10
1
300
MOTOR START / LONG DELAY
CURVE 10 HIGH INRUSH 50/60 Hz. AC
10,000
10
1
CURVE 12 HIGH INRUSH 50/60 Hz.
OVERLOAD
100 200
125 150
300
125%
200%
400%
600%
800%
1000%
10
1
10 - 150
3 - 25
.5 - 2.5
.15 - 1
.015 - .7
.009 - .35
.1
100 200
125 150
300
400 500 600 700 800 900 1000 1100 1200
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
CURVE 13 HIGH INRUSH 50/60 Hz.
OVERLOAD
(SEC.)
1000
TRIP TIMES
125%
200%
400%
600%
800%
1000%
100
10
1
.8 - 30
.15 - 2.5
.03 - .3
.02 - .15
.009 - .12
.009 - .09
(SEC.
.1
.01
.001
0
400 500 600 700 800 900 1000 1100 1200
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
1
1 - 15
.15 - 1.5
.03 - .25
.007 - .15
.003 - .08
.003 - .04
.1
10,000
TRIP TIMES
.01
.01
10
.001
0
400 500 600 700 800 900 1000 1100 1200
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
100
.1
.001
0
300
1000
TIME IN SECONDS
100
100 200
125 150
10,000
OVERLOAD TRIP TIMES
(SEC.)
125%
40 - 500
200%
9 - 100
400%
2 - 20
600%
.8 - 10
800%
.1 - 4.5
1000%
.009 - 2
1000
TIME IN SECONDS
.001
0
400 500 600 700 800 900 1000 1100 1200
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
125%
200%
400%
600%
800%
1000%
100
.01
.01
100 200
125 150
OVERLOAD TRIPTIMES
(SEC.)
1000
10 - 150
2.2 - 20
.2 - 2
.03 - .75
.007 - .15
.005 - .04
.1
.01
.001
0
125%
200%
400%
600%
800%
1000%
CURVE 3 SHORT DELAY 50/60 Hz.
10,000
OVERLOAD TRIP TIMES
(SEC.)
1000
May Trip
100 ms max.
30 ms max.
15 ms max.
12 ms max.
12 ms max.
TIME IN SECONDS
1000
CURVE 2 STANDARD DELAY 50/60 Hz.
10,000
TRIP TIMES
OVERLOAD @ 50/60 Hz. & DC @ 400 Hz.
TIME IN SECONDS
CURVE 0 INSTANTANEOUS
TIME IN SECONDS
400 Hz.
10,000
100
125
200
150
300
400
500
600
700
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
800
900
1000
.0011200
1100
100
0
125
200
150
300
400
500
600
700
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
800
900
1000
1100
DC
125%
200%
400%
600%
800%
1000%
100
10
1
2 - 55
.60 - 8
.1 - 1.5
.02 - .5
.004 - .05
.004 - .025
.1
125%
200%
400%
600%
800%
1000%
100
10
1
.6 - 7
.16 - 1.5
.03 - .25
.01 - .13
.004 - .05
.003 - .015
.1
.01
.01
.001
0
OVERLOAD TRIP TIMES
(SEC.)
1000
TIME IN SECONDS
TIME IN SECONDS
1000
CURVE 3 SHORT DELAY DC
10,000
OVERLOAD TRIP TIMES
(SEC.)
100 200
125 150
300
.001
0
400 500 600 700 800 900 1000 1100 1200
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
CURVE 53 DC HIGH INRUSH
10,000
OVERLOAD
1000
TRIP TIMES
125%
200%
400%
600%
800%
1000%
100
TIME IN SECONDS
CURVE 2 STANDARD DELAY DC
10,000
10
80 - 700
15 - 150
2 - 20
.70 - 10
.10 - 3
.01 - .1
1
.1
.01
100 200
125 150
300
400 500 600 700 800 900 1000 1100 1200
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
.001
0
100
125
200
150
300
400
500
600
700
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
800
900
AC/DC
10,000
CURVE 34 DC, 50/60 Hz. STANDARD DELAY
OVERLOAD
1000
135%
200%
400%
600%
800%
1000%
TIME IN SECONDS
100
10
1
TRIP TIMES
1 - 90
.60 - 20
.095 - 2
.02 - .95
.002 - .45
.002 - .09
(SEC.)
.1
.01
.001
0
100
125
135
200
150
300
400
500
600
700
LOAD CURRENT AS A PERCENT
OF BREAKER RATING
800
900
1000
1100
1200
Note:
For instantaneous curves for all voltages refer to Curve 0 instananeous under the AC 50/60 Hz. heading
2
11-2015, Rev. 1115
www.te.com
© 2014 Tyco Electronics Corporation,
a TE Connectivity Ltd. company
(SEC.)
Datasheets and product specification
according to IEC 61810-1 and to be used
only together with the ‘Definitions’ section.
Datasheets and product data is subject to the
terms of the disclaimer and all chapters of
the ‘Definitions’ section, available at
http://relays.te.com/definitions
Datasheets, product data, ‘Definitions’ section, application notes and all specifications
are subject to change.
1000
1100
12
General Purpose Relays
Industrial Relays
Potter & Brumfield
W6/W9 Series Magnetic Hydraulic P&B Circuit Breakers (Continued)
Product code structure
W
Typical product code
67-
X
2
Q
1
2-
20
W6 Series
Circuit Breaker Mounting
W #6-32 mounting threads
M
M3.0 x 0.5 mounting threads
Number of Poles
67 Single Pole
68 Two Pole
69 Three Pole
70 Four Pole
Circuit Function (Only X is VDE approved)
X Series trip
Actuator
One actuator per pole
1 Black toggle
9
2 White toggle
Red toggle
One actuator per unit
7 Black toggle
8
White toggle
Termination
Q .250“ QC (DIN 46 244) [30A Max. UL/CSA; 25A Max. VDE]
S #8-32 screw [30A Max.]
T #10-32 screw [50A Max.]
U #8-32 screw, nickel plated, bent inward 30° [30A Max.]
V #10-32 screw, nickel plated, bent inward 30° [30A Max.]
Notes:
#10-32 termination must be used for all ratings of greater than 30 amps.
#10-32 termination must be specified for circuit function D, but relay trip pole will be equipped
with .250“ QC.
Maximum Line Voltage (see Table 1 for current ranges)
UL/CSA 1 277VAC, 50/60 Hz.
Types 2 277/480VAC, 50/60 Hz. [20A Max.] (Requires insulating barriers,
see outline dimension drawing)
5 65VDC
7 AC/DC 277VAC, 50/60 Hz. or 65VDC
(Time delay curve 34 must be specified)
8 AC/DC 120VAC, 120/240VAC, 48VDC
(Agency Approval M [UL1500] and time delay curve 34 must be specified)
VDE
Types
1
5
7
250VAC, 415/240VAC
65VDC
AC/DC 250VAC, 415/240VAC, 65VDC
(Time delay curve 34 must be specified)
Time Delay Curve
0 Instantaneous
2 Standard delay
3 Short delay
53 DC high inrush
Amp Rating
0.2 0.50
0.25 0.75
1.0
1.5
2.0
2.5
10 AC high inrush motor start / long delay
12 AC high inrush version of #2
13 AC high inrush version of #3
34 Combination AC/DC standard delay
3.0
3.5
4.0
5.0
6.0
7.0
7.5
8.0
9.0 11.0
10.0 12.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
Consult factory for
other values
Agency Approval
Blank UL1077/CSA breaker
V
VDE approved breaker
M
UL1077/UL1500 ignition protected breaker
Authorized distributors are more likely to stock the following items.
W67-X2Q10-3
W67-X2Q10-5
W67-X2Q12-2
W67-X2Q12-3
W67-X2Q12-5
W67-X2Q12-7
W67-X2Q12-10
W67-X2Q12-15
W67-X2Q12-20
W67-X2Q12-30
W67-X2Q13-1
W67-X2Q13-2
11-2015, Rev. 1115
www.te.com
© 2014 Tyco Electronics Corporation,
a TE Connectivity Ltd. company
W67-X2Q13-3
W67-X2Q13-10
W67-X2Q13-15
W67-X2Q13-20
W67-X2Q13-25
W67-X2Q13-30
W67-X2Q50-5
W67-X2Q50-10
W67-X2Q52-5
W67-X2Q52-10
W67-X2Q52-15
W67-X2Q52-20
Datasheets and product specification
according to IEC 61810-1 and to be used
only together with the ‘Definitions’ section.
W67-X2Q52-30
W67-X2Q110-15
W67-X2Q110-20
W68-X2Q12-3
W68-X2Q12-5
W68-X2Q12-7
W68-X2Q12-10
W68-X2Q12-15
W68-X2Q12-20
W68-X2Q12-25
W68-X2Q12-30
W68-X2Q13-15
Datasheets and product data is subject to the
terms of the disclaimer and all chapters of
the ‘Definitions’ section, available at
http://relays.te.com/definitions
W68-X2Q110-10
W68-X2Q110-20
W69-X2Q12-5
W69-X2Q12-10
W69-X2Q12-15
W69-X2Q12-20
W69-X2Q12-25
W69-X2Q12-30
W69-X2Q110-20
W69-X2Q110-30
Datasheets, product data, ‘Definitions’ section, application notes and all specifications
are subject to change.
3
General Purpose Relays
Industrial Relays
Potter & Brumfield
W6/W9 Series Magnetic Hydraulic P&B Circuit Breakers (Continued)
Product code structure
W
Typical product code
91-
X
1
1
2-
20
W9 Series
Circuit Breaker Mounting
W #6-32 mounting threads
M
M3.0 x 0.5 mounting threads
Number of Poles
91 Single Pole
92 Two Pole
93 Three Pole
94 Four Pole
Circuit Function (Only X is VDE approved)
X Series trip
Actuator
One actuator per pole
1 Black toggle
2 White toggle
Maximum Line Voltage (see Table 1 for current ranges)
UL/CSA 1 277VAC, 50/60 Hz.
Types 2 277/480VAC, 50/60 Hz. [20A Max.]
5 65VDC
7 AC/DC 277VAC, 50/60 Hz. or 65VDC
(Time delay curve 34 must be specified)
8 AC/DC 120VAC, 120/240VAC, 48VDC
(Agency Approval M [UL1500] and time delay curve 34 must be specified)
VDE
Types
1
5
7
250VAC, 415/240VAC
65VDC
AC/DC 250VAC, 415/240VAC, 65VDC
(Time delay curve 34 must be specified)
Time Delay Curve
0 Instantaneous
2 Standard delay
3 Short delay
53 DC high inrush
Amp Rating
0.20 0.75
0.25 1.00
0.50 1.50
2.0
2.5
3.0
10 AC high inrush motor start / long delay
12 AC high inrush version of #2
13 AC high inrush version of #3
34 Combination AC/DC standard delay
3.5
4.0
5.0
6.0
7.0
7.5
8.0 11.0
9.0 12.0
10.0 15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
Consult factory for other values
Agency Approval
Blank UL1077/CSA approved breaker
V
VDE approved breaker
M
UL1077/UL1500 ignition protected breaker
Authorized distributors are more likely to stock the following items.
W91-X112-1
W91-X112-2
W91-X112-3
W91-X112-5
W91-X112-7
W91-X112-10
4
W91-X112-15
W91-X112-20
W91-X112-40
W91-X112-50
W91-X113-5
W91-X113-10
11-2015, Rev. 1115
www.te.com
© 2014 Tyco Electronics Corporation,
a TE Connectivity Ltd. company
W91-X113-15
W91-X150-5
W91-X152-10
W91-X152-15
W91-X152-20
W91-X152-30
W91-X152-40
W91-X152-50
W91-X1110-20
W92-X112-1
W92-X112-2
W92-X112-3
Datasheets and product specification
according to IEC 61810-1 and to be used
only together with the ‘Definitions’ section.
W92-X112-5
W92-X112-7
W92-X112-10
W92-X112-15
W92-X112-20
W92-X112-25
W92-X112-30
W92-X112-40
W92-X112-50
W92-X113-15
W92-X113-20
W92-X1110-20
Datasheets and product data is subject to the
terms of the disclaimer and all chapters of
the ‘Definitions’ section, available at
http://relays.te.com/definitions
W92-X1110-30
W93-X112-5
W93-X112-10
W93-X112-15
W93-X112-20
W93-X112-25
W93-X112-30
W93-X112-40
W93-X112-50
W93-X1110-20
W93-X1110-30
Datasheets, product data, ‘Definitions’ section, application notes and all specifications
are subject to change.
General Purpose Relays
Industrial Relays
Potter & Brumfield
W6/W9 Series Magnetic Hydraulic P&B Circuit Breakers (Continued)
Outline Dimensions - Toggle Actuator Models
W6 Series
Panel Mounting Cutout
2.043
(51.89)
.235
(5.97)
1.640
(41.66)
LINE
.66
(16.8)
.245
(6.22)
(15.88 +0.25
)
-0.00
ON
A
.750
(19.05)
Ø .625 +.010
-.000
1 PER POLE
29°
1.520
(38.61)
1.660
(42.16)
1.048
(26.62)
30°
OFF
B
Ø .156 [2 PLACES PER POLE]
(3.96)
LOAD
W6 Series - One Actuator Per Pole
1 Pole
Ø .590
(15.00)
2 Pole
.750
(19.05)
3 Pole
4 Pole
3.000
(76.20)
2.250
(57.15)
1.500
(38.10)
1.660
(42.16)
2.000
(50.80)
1.05
(26.67)
1.22
(31.00)
6.32 TH'D. .14 (3.56) DP. TYP.
M3 X 0.5 OPTIONAL
Note: Multi-pole models furnished with seperate handle tie hardware
W6 Series - One Actuator Per Unit
1 Pole
2 Pole
Ø .590
(15.00)
.750
(19.05)
3 Pole
4 Pole
2.250
(57.15)
1.500
(38.10)
3.000
(76.20)
1.660
(42.16)
2.000
(50.80)
1.22
(31.00)
1.05
(26.67)
6.32 TH'D. .14 (3.56) DP. TYP.
M3 X 0.5 OPTIONAL
Note: 4-pole models furnished with sperate
handle tie hardware
480V Model with Barriers
2.250
(57.15)
.269
(6.83)
2.778
(70.56)
2.530
(64.26)
.235
2.032
Termination
Options
(5.97)
(51.61)
Note: 3-pole model shown
LINE
.266
(6.76)
Notes:
1. Terminal protrusion dimensions are referenced from back of mounting panel
2. Main terminals are male quick connect type .250 (6.35) wide x .031 (.79) thick x
.377 (9.58) long. Optional 8-32 x .250 (6.35) or 10-32 x .250 (6.35) screw type
3. Panel mounting cutout detail mtg. detail tol.: ± .005 (.13) unless noted. Add
additional cutouts to correspond to number of poles. Outline drawing tolerance ±
.015 (.35) unless noted
11-2015, Rev. 1115
www.te.com
© 2014 Tyco Electronics Corporation,
a TE Connectivity Ltd. company
LINE
A
A
Datasheets and product specification
according to IEC 61810-1 and to be used
only together with the ‘Definitions’ section.
LINE
A
1.520
(38.61)
B
LOAD
B
LOAD
Datasheets and product data is subject to the
terms of the disclaimer and all chapters of
the ‘Definitions’ section, available at
http://relays.te.com/definitions
LOAD
.416
(10.56
1.058
(26.97) .827
(21.00)
B
Datasheets, product data, ‘Definitions’ section, application notes and all specifications
are subject to change.
5
General Purpose Relays
Industrial Relays
Potter & Brumfield
W6/W9 Series Magnetic Hydraulic P&B Circuit Breakers (Continued)
Outline Dimensions - Optional Toggle Guards
W6 Series
.03
(.76)
.95
(24.1)
.08
(2.03)
2x
.27 DIA.
(6.86)
.53
(13.46)
.313
(7.95)
2.185 INSIDE
(55.50)
1.093
(27.76)
.75
(19.05)
.75
(19.05)
.2 x
R1.0
(25.4)
.47
(11.94)
.17
(4.32)
2.00
(50.8)
1.375 INSIDE
(34.92)
.313
(7.95)
.75
(19.05)
.625 INSIDE
(15.88)
.78
(19.8)
.17 REF.
(4.32)
.625
(15.88)
1.66
(42.16)
.44
(11.18)
2 x .16 DIA.
(4.06)
84-004
(for 1 Pole
Breaker)
4 x .16 DIA.
(4.06)
84-005
(for 2 Pole
Breaker)
.20
(5.08)
6 x .16 DIA.
(4.06)
84-006
(for 3 Pole
Breaker)
84-004 toggle guard shown with
W67 series circuit breaker
mounted in a panel.
Optional toggle guards may be ordered seperately for use on W6 toggle actuator models.
These guards help to prevent accidental operation and allow the breaker to be locked in the “off” position.
6
11-2015, Rev. 1115
www.te.com
© 2014 Tyco Electronics Corporation,
a TE Connectivity Ltd. company
Datasheets and product specification
according to IEC 61810-1 and to be used
only together with the ‘Definitions’ section.
Datasheets and product data is subject to the
terms of the disclaimer and all chapters of
the ‘Definitions’ section, available at
http://relays.te.com/definitions
Datasheets, product data, ‘Definitions’ section, application notes and all specifications
are subject to change.
General Purpose Relays
Industrial Relays
Potter & Brumfield
W6/W9 Series Magnetic Hydraulic P&B Circuit Breakers (Continued)
Outline Dimensions
W9 Series
Series Trip Model
Series Trip Model
.060
(1.52)
.375
.281
(9.52)
(7.14)
1.845
(46.86)
1.15
(29.21)
LINE
.313
(7.95)
ON
29°
1.940
(49.28)
.060
(1.52)
30°
.14
2.10 (3.56)
(53.34)
2.50
(64.00)
ON ON
OFF OFF
OFF
LOAD
#10-32
STUD
TERMINATION
.750
(19.05)
.375
(9.53)
.218
(5.54)
2.065
(52.45)
ON ON
OFF OFF
.750
(19.05)
ON ON
TAPPED #6-32 X .16 (4.06)
DEEP
M3 X 0.5 OPTIONAL
.750
(19.05)
ON ON
.398
(10.11)
ON ON
OFF OFF OFF OFF OFF OFF
2 POLE
1.500
(38.10) 2.250
(57.15)
1 POLE
.74
(18.8)
.750
(19.05)
.375
(9.53)
3POLE
3.000
(76.20)
1.438
(36.53)
2.50
(63.5)
4 POLE
Note:
1. Top mounted plate (shown with broken line)
is present only on UL1500 models
Panel Mounting Cutout Detail
.732
(18.59)
.750
(19.05)
.750
(19.05)
.750
(19.05)
.385
(9.78)
.907
(23.04)
1.450
(36.83)
2.065
(52.45)
2X Ø .156
(3.96)
PER POLE
3.04
(77.2)
2.28
(57.9)
1.52
(38.6)
.76
(19.3)
1 POLE
2 POLE
3 POLE
4 POLE
Notes:
1. Terminal protrusion dimensions are referenced from
the back of the mounting panel
2. Mounting detail tolerance ± .005 (13) unless noted
3. Outline drawing tolerance ± .015 (.38) unless noted
Dimensions in brackets ( ) are in milimeters.
Disclaimer:
While TE and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this document, TE
cannot assure that this information is error free. For this reason, TE does not make any representation or offer any guarantee that such information is
accurate, correct, reliable or current. TE reserves the right to make any adjustments to the information at any time. TE expressly disclaims any implied
warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular
purpose. TE‘s only obligations are those stated in TE’s Standard Terms and Conditions of Sale. TE will in no case be liable for any incidental, indirect or
consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on
their own judgment to evaluate the suitability of a product for a certain purpose and test each product for its intended application.
In case of any potential ambiguities or questions, please don’t hesitate to contact us for clarification.
11-2015, Rev. 1115
www.te.com
© 2014 Tyco Electronics Corporation,
a TE Connectivity Ltd. company
Datasheets and product specification
according to IEC 61810-1 and to be used
only together with the ‘Definitions’ section.
Datasheets and product data is subject to the
terms of the disclaimer and all chapters of
the ‘Definitions’ section, available at
http://relays.te.com/definitions
Datasheets, product data, ‘Definitions’ section, application notes and all specifications
are subject to change.
7