MM-0787-60B
LINE Operating Voltage = 250/480 V~, 50 / 60 Hz Operating Voltage = 125/208 V~, 50 – 400 Hz Operating Current = 60 A / Phase Temperature Range = -20 TO 50 Deg. C Diel. Withstand (L-CASE) = 1500 V~ FOR 1 MIN. Diel. Withstand (L-L) = 1500 Vdc For 1 Min. Leakage Current = 2.2 ma @ 250 V~, 60 Hz Discharge Volt after 1.0 second = 24 V Max. Maximum Capacitance each line to case = 0.016 ì F L1 1 2 3 N L2 Order P/N: MM-0787-60B GRD GRD 1 2 3 N LOAD
INSERTION LOSS (db)
INSERTION LOSS vs FREQUENCY MM-0787-60B 80 70 60 50 40 30 20 CM 10 0 .01 .02 .04 .07 .1 .2 .4 .7 1 2 4 7 10 20 40 70 100 DM
The Mm-0787-60B filter is designed for use with large computer or motor installations where heavy current is drawn continuously. This filter can handle large in-rush current typical of modern power supplies. When data lines or power is shared with other systems the ground coil helps breakup ground loops which can cause system errors and also increase conducted RF emissions.
FREQUENCY (MEGAHERTZ)
4.75 2.71 3.00 0.85 0.95 7.00 0.50 1.85
1.00
1.43
1
4.00
6.00
LOAD 3 2 GRD
1/4-20 UNC MOUNTING STUD (8 PL)
1/4-20UNC TH'D TERMINAL (10 PL) (.75 DIA BUSHING)
USA EUR
JMK Inc 15 Caldwell Dr. Amherst, NH 03031 JMK Inc Glasgow G13 1DN Scotland UK
PH: 603 886-4100 FX: 603 886-4115 email: info@jmkfilters.com PH: 44-(0) 7785310729 FX: 44-(0) 141 589 1884
N
1 2 3 GRD N LINE
1.05 6.00 1.05 1.05
C L
很抱歉,暂时无法提供与“MM-0787-60B”相匹配的价格&库存,您可以联系我们找货