Input signal
Applications
•
•
•
•
•
•
•
•
•
•
•
•
Accuracy Class 0.5 (IEC 61869-2) [1].
Linearity error ≤ 0.10 %.
Protection degree IP2X.
35 mm DIN rail mounted.
Push-in terminals.
4 selectable true RMS output signals:
0…20 mA, 4…20 mA, 0…5 V, 0…10 V.
2 selectable instantaneous output signals:
225 mV, 333 mV.
6 selectable sensitivities depending on Rogowski coil:
22.5, 70, 80, 85, 100, 120 mV/kA at 50 Hz.
12 selectable ranges: 100, 200, 300, 400, 500, 600,
800, 1000, 1500, 2000, 4000, 5000 A.
Ambient operating temperature −25...+70 °C.
•
•
•
Standards
•
•
Safety: IEC 61010-1: 2010.
EMC: IEC 61326-1: 2012.
Options
Advantages
•
•
•
•
•
MV/LV substations: transformer condition monitoring.
Power measurement: current measurement for
active power calculation.
Building sub-metering: energy efficiency monitoring,
consumption analysis and cost allocation.
Power quality monitoring: electrical loads and
distribution system equipment.
Fault Detection, Isolation and Repair (FDIR).
Remote Terminal Units (RTU).
Compact design for DIN rail assembly.
High accuracy Class 0.5 (IEC 61869-2).
Setup by user via Select / Edit buttons.
Clear status indication via bi-color led.
•
Cross Power Plug-in: side contacts to stack up to 3
Integrator modules and use only one power supply.
[1] AI-PMUL Integrators fulfill accuracy class limits defined by IEC 61869-2 even if this standard does not apply to Rogowski integrators.
See detailed curve of accuracy given in this document.
N° 97.T5.99.000.0
19March2020/Version 1
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
1/12
AI-PMUL series
CONFIGURABLE ROGOWSKI COIL SIGNAL CONDITIONER
Material and Insulation coordination
Parameter
Symbol
Unit
Value
Comment
RMS voltage for AC insulation test,
50 Hz, 1 min
Ud
kV
1.5
Between power supply 24 V and
Rogowski connection + output
Flammability according to UL94
-
-
V0
-
Material
-
-
Polyamide
Halogen free
Parameter
Symbol
Unit
Value
Comment
Ambient operating temperature
TA
°C
−25...+70
Ambient storage temperature
TS
°C
−40...+85
Relative humidity (non-condensing)
RH
%
95
Altitude above sea level
-
m
2000
Mass
m
g
58
Parameter
Symbol
Unit
Value
General dimensional tolerance
-
mm
±1
Dimensions
-
mm³
100 × 78 × 15
Mounting on DIN rail (IEC 60715)
-
-
TH35-7.5
TH35-15
Parameter
Symbol
Unit
Value
24 V DC Supply voltage
UC DC
V
+10...+32
Current consumption
IC
mA
max. 100
at 24 V
V
5
For product configuration only
Environmental characteristics
Mechanical characteristics
Comment
Power Supply
Auxiliary supply through micro-USB
2/12
Comment
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
N° 97.T5.99.000.0
19March2020/Version 1
AI-PMUL series
CONFIGURABLE ROGOWSKI COIL SIGNAL CONDITIONER
Input Signal
Parameter
Symbol Unit
Data
Comment
Rogowski coil sensitivity selection
With push buttons
See product configuration
description
Selection indication
bi-color LED
Green: Current range
Red: Sensitivity & Output
Rogowski coil sensitivities
mV/kA 22.5, 70, 80, 85, 100,
120
Typical input impedance
kΩ
10
At 50 Hz
Rated frequency
ƒr
Hz
50…60
Automatic recognition of grid
frequency
Frequency bandwidth (at 3 dB)
BW
Hz
10…1500
Measurement bandwidth
Current measurement range selection
With push buttons
Current measurement range
A
100, 200, 300, 400, 500,
600, 800, 1000, 1500,
2000, 4000, 5000
Overcurrent measurement range
%
120
Overcurrent based on maximum
value of the range selected
Short time withstand current
on primary for 3 s [1]
kA
130
Worst case scenario with a Rogowski
coil sensitivity of 120mV/kA
Output Signal
Parameter
Symbol Unit
Min
Typ
Max
Comment
0...20 mA true RMS current output mode
Iout
mA
0
-
24
20 mA @ 100% I range
4...20 mA true RMS current output mode
Iout
mA
4
-
23.2
20 mA @ 100% I range
0...5 V true RMS voltage output mode
Uout
V
0
-
6
5 V @ 100% I range
0...10 V true RMS voltage output mode
Uout
V
0
-
12
10 V @ 100% I range
225 mV instantaneous voltage output mode Uout
mV
0
-
270
225 mV rms @ 100% I range
333 mV instantaneous voltage output mode
Uout
mV
0
-
400
333 mV rms @ 100% I range
Load resistance (all current output mode)
RL
Ω
0
-
500
Load resistance (all voltage output mode)
RL
kΩ
1
-
-
Temperature drift (all output mode)
TCS
ppm/K -
-
150
Phase displacement @ 50 Hz or 60 Hz [2]
Δφ
-
-
-
0.5°
Accuracy class
-
-
0.5 [3]
-
Linearity error
ɛL
%
0.1
Response time 10% (true RMS) current rise tD10
ms
45
Response time 90% (true RMS) current rise tD90
ms
160
Response time 10% (true RMS) current fall
tD10
ms
65
Response time 90% (true RMS) current fall
tD90
ms
190
From −25 °C … +70 °C
[1] Maximum AI-PMUL input voltage of 16 V for 3 s equivalent of measurement of short time current of 130 kA for 3 s with a Rogowski coil of
120 mV/kA sensitivity. For higher short time current rated network please consult our technical team.
[2] Value for instantaneous signal output and steady state primary current.
[3] AI-PMUL Integrators fulfill accuracy class limits defined by IEC 61869-2 even if this standard does not apply to Rogowski integrators.
See detailed curve of accuracy given in this document.
N° 97.T5.99.000.0
19March2020/Version 1
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
3/12
AI-PMUL series
CONFIGURABLE ROGOWSKI COIL SIGNAL CONDITIONER
Definition of typical, minimum and maximum values
Minimum and maximum values for specified limiting and safety conditions have to be understood as such as
well as values shown in “typical” graphs.
On the other hand, measured values are part of a statistical distribution that can be specified by an interval
with upper and lower limits and a probability for measured values to lie within this interval.
Unless otherwise stated (e.g. “100 % tested”), the LEM definition for such intervals designated with “min” and
“max” is that the probability for values of samples to lie in this interval is 99,73 %.
For a normal (Gaussian) distribution, this corresponds to an interval between −3 sigma and +3 sigma.
If “typical” values are not obviously mean or average values, those values are defined to delimit intervals with
a probability of 68,27 %, corresponding to an interval between −sigma and +sigma for a normal distribution.
Typical, minimum and maximum values are determined during the initial characterization of the product.
Compatibility between current range selected and Coil sensitivity selected
Current range and coil sensitivity should be chosen according to the table below.
Coil sensibility selected
100
200
Current Range Selected
300
400
500
600
800
1000
1500
2000
4000
5000
4/12
22.5
70
80
85
100
120
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
N° 97.T5.99.000.0
19March2020/Version 1
AI-PMUL series
CONFIGURABLE ROGOWSKI COIL SIGNAL CONDITIONER
Typical performance characteristics, Range 100 A
Output 0 … 20 mA, Sensitivity 22.5 mV/kA
2
0,15
0,1
1
0,5
εL (% of Ipn)
Measurement error (%)
1,5
0
-0,5
0,05
0
-0,05
-1
-0,1
-1,5
-2
5
25
45
65
85
-0,15
105
5
25
45
65
85
105
65
85
105
65
85
105
IP (A)
IP (A)
Output 0 … 10 V, Sensitivity 22.5 mV/kA
2
0,15
0,1
1
0,5
εL (% of Ipn)
Measurement error (%)
1,5
0
-0,5
0,05
0
-0,05
-1
-0,1
-1,5
-2
5
25
45
65
85
-0,15
105
5
25
45
IP (A)
IP (A)
Output 0 … 225 mV, Sensitivity 22.5 mV/kA
0,15
2
0,1
1
0,5
εL (% of Ipn)
Measurement error (%)
1,5
0
-0,5
0,05
0
-0,05
-1
-0,1
-1,5
-2
5
25
45
65
85
105
-0,15
5
25
Class 0,5
Full scale error 0,5%
Class 0,5
Sample results
Full scale error 1%
Sample results
N° 97.T5.99.000.0
19March2020/Version 1
45
IP (A)
IP (A)
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
5/12
AI-PMUL series
CONFIGURABLE ROGOWSKI COIL SIGNAL CONDITIONER
Typical performance characteristics, Range 1000 A
Output 0 … 20 mA, Sensitivity 22.5 mV/kA
2
0,15
0,1
1
0,5
εL (% of Ipn)
Measurement error (%)
1,5
0
-0,5
0,05
0
-0,05
-1
-0,1
-1,5
-2
50
250
450
650
850
-0,15
1050
50
250
450
650
850
1050
650
850
1050
650
850
1050
IP (A)
IP (A)
Output 0 … 10 V, Sensitivity 22.5 mV/kA
2
0,15
0,1
1
0,5
εL (% of Ipn)
Measurement error (%)
1,5
0
-0,5
0,05
0
-0,05
-1
-0,1
-1,5
-2
50
250
450
650
850
-0,15
1050
50
250
450
IP (A)
IP (A)
Output 0 … 225 mV, Sensitivity 22.5 mV/kA
0,15
2
0,1
1
0,5
εL (% of Ipn)
Measurement error (%)
1,5
0
-0,5
0,05
0
-0,05
-1
-0,1
-1,5
-2
50
250
450
650
850
1050
-0,15
50
250
6/12
450
IP (A)
IP (A)
Class 0,5
Full scale error 0,5%
Class 0,5
Sample results
Full scale error 1%
Sample results
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
N° 97.T5.99.000.0
19March2020/Version 1
AI-PMUL series
CONFIGURABLE ROGOWSKI COIL SIGNAL CONDITIONER
Example of application
Product configuration:
•
•
•
Range (green LED): 5000 A
Output signal (red LED): 0 … 10 V
Sensitivity (red LED): 22.5 mV/kA
The graph hereafter give conversion between the primary current, the voltage output of Rogowski coil and
the output voltage of the AI-PMUL.
Output voltage (V)
Measure on 1 kΩ
12
20 %
10
20 %
2
0
22,5
0
112,5
1
5
135
6
Rogowski coil signal (mV)
22.5 mV / kA sensitivity
Primary current (kA)
Saturation - Range LED is blinking
N° 97.T5.99.000.0
19March2020/Version 1
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
7/12
AI-PMUL series
CONFIGURABLE ROGOWSKI COIL SIGNAL CONDITIONER
Example of typical transient response output 0 … 10 V
Current (A)
15
10
5
0
-5
t
D10
-10
t
D90
-15
-0,05
0
0,05
0,1
0,15
0,2
0,25
0,3
0,35
Time (s)
Grid
AI-PMUL Output
Current rise
• tD 10 < 45 ms
• tD 90 < 160 ms
Current (A)
15
10
5
0
-5
t
D10
-10
t
D90
-15
-0,05
0
0,05
0,1
0,15
0,2
0,25
Grid
0,3
0,35
Time (s)
AI-PMUL Output
Current fall
•
•
8/12
tD 10 < 65 ms
tD 90 < 190 ms
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
N° 97.T5.99.000.0
19March2020/Version 1
AI-PMUL series
CONFIGURABLE ROGOWSKI COIL SIGNAL CONDITIONER
Connections and Interfaces
A
RC+
RCOUT+
OUT-
0A
400
0A
150
5V
0A
0A
800
A
600
A
500
A
400
A
300
A
200
A
1500
1000
0-20
mA
A
mA
5V
A
10V
A
A
600
A
500
A
400
A
300
A
200
A
E
4-20
A
225m
V
333m
V
22.5
70
80
85
100
A
120
SELE
mA
CT
EDIT
10V
225
mV
V+
VNC
333
mV
22.5
70
80
85
C
A
MA Input for Rogowski coil (optional)
S
Section: 0.13 ... 1.5 mm2
B
Terminal input coil and output signal
Section: 0.13 ... 1.5 mm2
C
A
800
100
mA
4-20
100
2000
0-20
200
0A
4000
mV/kA @ 50Hz
500
5000
mV/kA @ 50Hz
RC+
RCOUT+
OUT-
B
D
Cross Power plug-in
Side contacts to stack up to 3 Integrator
modules and use only 1 power supply.
E
Micro USB
Energise AI-PMUL for configuration
without connecting 24 V DC supply.
Power supply terminals (DC, 24 V)
Section: 0.13 ... 1.5 mm2 (24 ... 16 AWG)
Third pin not connected
Parameter
Unit
Min
Type
Typ
Max
Comment
Push-in
Clamping range
mm
Cross section
Stripping length
N° 97.T5.99.000.0
19March2020/Version 1
D
0.13
-
1.5
AWG
24
-
16
mm
9.5
10
10.5
2
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
9/12
AI-PMUL series
CONFIGURABLE ROGOWSKI COIL SIGNAL CONDITIONER
AI-PMUL series: name and codification
AI-PMUL
Family:
AC Integrator
Case type / Output signal:
P: DIN RAIL mounting / MUL: Multiple output
Description
Item Number
Comment
AI-PMUL
90.T5.99.000.0
Integrator Low Power standard
for automation applications
AI ACCESSORY KIT M1 CROSS POWER PLUG-IN
90.T8.98.000.0
Cross Power plug-in accessory:
Kit to connect 2 integrators power supplies
Dimensions (in mm)
7
6
5
4
5000 A
0-20mA
4000 A
4-20mA
2000 A
10V
1000 A
225mV
800 A
333mV
600 A
22.5
500 A
70
400 A
80
300 A
85
200 A
100
100 A
120
mV/kA @ 50Hz
100
5V
1500 A
SELECT
EDIT
3
2
1
15
78
85.5
Installation, removal, wiring
100
200 A
100 A
120
CT
SELE
A
2000
A
1500
A
1000
A
800 A
600 A
500 A
400 A
300 A
200 A
100 A
EDIT
0-20mA
4-20mA
5V
10V
5000
A
4000
A
V
A
2000
V
225m
1500
A
22.5
1000
A
70
800 A
333m
80
85
600 A
500 A
100
400 A
120
300 A
200 A
100 A
0-20mA
4-20mA
5V
10V
V
225m
V
333m
22.5
70
80
85
mV/kA @ 50Hz
A
4000
mV/kA @ 50Hz
5000
100
120
SELECT
SELECT
EDIT
EDIT
To install, rotate terminal to mount
on the rail DIN
10/12
To remove the device, use a 4 mm
flat screwdriver
To remove wiring easily, use any
tools or a 2.5 mm flat screwdriver
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
N° 97.T5.99.000.0
19March2020/Version 1
AI-PMUL series
CONFIGURABLE ROGOWSKI COIL SIGNAL CONDITIONER
Safety and warning notes
In order to guarantee safe operation of the signal conditioner and to be able to make proper use of all
features and functions, please read these instructions thoroughly!
Safe operation can only be guaranteed if the signal conditioner is used for the purpose it has been
designed for and within the limits of the technical specifications.
Caution
Ignoring the warnings can lead to serious injury and/or cause damage! The electric measuring signal
conditioner may only be installed and put into operation by qualified personnel that have received an
appropriate training. The corresponding national regulations shall be observed during installation and
operation of the signal conditioner and any electrical conductor. The signal conditioner shall be used
in electric/electronic equipment with respect to applicable standards and safety requirements and in
accordance with all the related systems and components manufacturers’ operating instructions.
The product must be powered by a limited power source. The product shall be operated with Rogowski
Coil compliant with IEC 61010-2-032. Consistency of measurements during maintenance operations shall
be checked. Consistency of measurement during commissioning and maintenance shall be checked with
suitable means (clamp-on ammeter). Product shall not saturate .
Caution, possibility of electric shock
When operating the signal conditioner, certain parts next to the signal conditioner may carry hazardous
live voltage. The user shall ensure to take all measures necessary to be protected against electrical shock.
Certain parts may contain conducting parts that shall not be accessible after installation. A protective
enclosure or additional insulation barrier may be necessary. Installation and maintenance shall be done with
the main power supply disconnected except if there are no hazardous live parts in or in close proximity to the
system and if the applicable national regulations are fully observed.
Safe and trouble-free operation of this signal conditioner can only be guaranteed if transport, storage and
installation are carried out correctly and operation and maintenance are carried out with care. The signal
conditioner shall not be opened or modified. If not working, the signal conditioner shall be replaced by an
equivalent device. To avoid electrical burn, electric shock or arc flash, do not install Rogowski coils on or
remove them from hazardous live conductors. Any connection to the product shall fulfil the requirements for
safety extra low voltage (SELV) circuits.
N° 97.T5.99.000.0
19March2020/Version 1
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
11/12
LEM International SA
Chemin des Aulx 8,
1228 Plan-les-Ouates, Suisse
+41 22 706 11 11
www.lem.com
12/12
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
N° 97.T5.99.000.0
19March2020/Version 1