SPLIT CORE ROGOWSKI COIL
ART Series
Ref: ART-B22-D70, ART-B22-D125, ART-B22-D175, ART-B22-D300
Flexible clip-around Rogowski coil for the electronic measurement of AC current with galvanic separation between
the primary circuit (power) and the secondary circuit (measurement). The patented Perfect Loop Technology
dramatically reduces both the error due to the position of the measured conductor within the aperture, and the error
due to the proximity of external conductors.
Accuracy Class 0.5
w
Ne s 0.5
as
Cl
IP
dip/dt
VS- VS+
A
mm 56.0
B
18.9
C
33.7
D
2.0
E
F
1500.0 6.1
Ø
70 - 125
175 - 300
Features
Applications
●●
●●
●●
●●
●●
●●
●●
●●
●●
●●
Rated insulation voltage 1000 V Cat III PD2
Accuracy Class 0.5 (IEC 61869-2)
Protection degree IP57
⌀ 70, ⌀ 125, ⌀ 175, ⌀ 300 mm sensing aperture
1.5 m output cable (other lengths available see page 8)
Ambient temperature −40 °C … +80 °C
Very flexible and thin coil: 6.1 mm
Slot for attaching the loop on the primary with a cable tie
⌀ 2 mm hole to pass a security seal tampering
An innovative patented clasp drastically reduces the
positioning error near the closing
●● Internal shield for enhanced measurement accuracy at low
primary currents.
●● MV/LV substations on LV side: Transformer Condition
Monitoring
●● Power metering: current measurement for active power
calculation
●● Building sub-metering: energy efficiency monitoring,
consumption analysis and cost allocation
●● Power quality monitoring: electrical loads and distribution
system equipment
●● Fault Detection, Isolation and Repair
(FDIR): isolate the site of the fault
●● Remote Terminal Units (RTU)
●● Phasor Measurement Units (PMU).
Advantages
●● IEC 61010-1: 2010; IEC 61010-2-32: 2012
●● 1) IEC 61869-1: 2007; IEC 61869-2: 2012
●● 1) IEC 61869-6: 2016; IEC 61869-10: 2017
●● UL 61010-1: 2012.
●●
●●
●●
●●
●●
Thin, flexible, and light weight solution
Very low positioning error
Quick, non-intrusive and easy setup
A single sensor for a large current range without overload
Less influenced by external fields
Standards
●● Adaptable for a large range of cable diameters.
Note:
1)
Performance standards: ART-B22 only partially fulfills these standards as a Rogowski coil has fundamental
differences compared to current transformers.
N°97.M4.99.000.0, N°97.M7.99.000.0, N°97.M8.99.000.0, N° 97.M4.99.003.0; N° 97.M4.99.004.0; N° 97.M4.99.006.0; N° 97.M7.99.003.0; N° 97.M7.99.004.0; N° 97.M7.99.006.0;
Page 1/12
N° 97.M8.99.003.0; N° 97.M8.99.004.0; N° 97.M8.99.006.0; N° 97.N3.99.000.0; N° 97.N3.99.003.0; N° 97.N3.99.004.0, N° 97.N3.99.006.0
18January2018/version 6
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
LEM City answers the demand for an accurate, reliable and easy to install energy sensor for future Smart Cities.
www.lem.com
www.lemcity.com
SPLIT CORE ROGOWSKI COIL
ART Series
Absolute maximum ratings
Parameter
Symbol
Unit
Value
Maximum secondary voltage
US max
V
30
Maximum primary conductor temperature
TB max
°C
105
Stresses above these ratings may cause permanent damage.
Exposure to absolute maximum ratings for extended periods may degrade reliability.
UL 61010-1: Ratings and assumptions of certification
File # E330077 , Vol.D1
Standards
●● UL 61010-1, Third Edition, May 11, 2012, Revised April 29 2016
●● CAN/CSA-C22.2 No. 61010-1-12, 3rd Edition, Revision dated April 29 2016
●● IEC 61010-2-032: 2012 (Third Edition), UL 61010-2-032 (IEC 61010-2-032:2012).
Ratings
Rated insulation voltage AC 1000 V, 50/60 Hz, CAT III, 2000 A.
Engineering conditions of acceptability
When installed in an end-product, consideration must be given to the following:
- ART series has been investigated as Type B current sensors according IEC 61010-2-032 3rd ed.
- The devices have been evaluated for overvoltage category III and pollution degree 2 environment use only.
For ART series, the need for the following shall be considered in the end-product:
- Markings and documentation that comply with Clause 5.
- The following tests shall be performed in the end-product evaluation: Dielectric Strength.
- The unit is considered acceptable for use in a max ambient of 80°C for ART series.
- A suitable enclosure shall be provided in the end-use application.
- The terminals have not been evaluated for field wiring.
- Primary conductor or busbar temperature should never exceed 100°C.
Page 2/12
18January2018/version 6
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
LEM City answers the demand for an accurate, reliable and easy to install energy sensor for future Smart Cities.
www.lem.com
www.lemcity.com
SPLIT CORE ROGOWSKI COIL
ART Series
Insulation coordination
Parameter
Symbol
Unit
Value
RMS voltage for AC insulation test, 50 Hz, 1 min
Ud
kV
7.4
Impulse withstand voltage 1.2/50 µs
ÛW
kV
12.8
Partial discharge RMS test voltage (qm < 10 pC)
Ut
kV
1.65
According to IEC 60664-1
Clearance (pri. - sec.)
dCI
mm
> 16
Shortest distance through
air
Creepage distance (pri. - sec.)
dCp
mm
> 16
Shortest path along device
body
-
--
V0
Case material
CTI
Comment
According to UL 94
600
Application example
-
1000 V CAT III Reinforced insulation
PD2
according to IEC 61010-1
Application example
-
1000 V CAT IV Basic insulation according
PD2
to IEC 61010-1
Environmental and mechanical characteristics
Parameter
Symbol
Unit
Min
Ambient operating temperature
TA
°C
−40
80
Ambient storage temperature
TS
°C
−40
80
Relative humidity (non-condensing)
RH
%
0
90
Altitude above sea level
Typ
m
Max
Comment
2000
Mass ⌀ 70
m
g
124
Cable length: 1.5 m
Mass ⌀ 125
m
g
130
Cable length: 1.5 m
Mass ⌀ 175
m
g
138
Cable length: 1.5 m
Mass ⌀ 300
m
g
155
Cable length: 1.5 m
Page 3/12
18January2018/version 6
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
LEM City answers the demand for an accurate, reliable and easy to install energy sensor for future Smart Cities.
www.lem.com
www.lemcity.com
SPLIT CORE ROGOWSKI COIL
ART Series
Electrical data ART-B22-D70
At TA = 25 °C, RL = 10 kΩ, unless otherwise noted.
Parameter
Symbol
Unit
Rated primary current
IPr
A
Rated short-time thermal current
Ith
kA
300
Rated transformation ratio
kra
kA/V
44.44
Rated frequency
fr
Hz
50/60
Symbol
Unit
Secondary voltage
US
mV
22.5
Mutual inductance
M
nH
71.98
Temperature coefficient of M
TCM
ppm/K
±30
Frequency bandwidth (−3 dB)
BW
kHz
420
3)
Phase displacement 4) @ 50/60 Hz
Δφ
°
0.004
3)
Coil inductance
LS
µH
180
Coil resistance
RS
Ω
56
Ratio error (centered)
ε
%
−0.5
0.5
Ratio error (all positions)
ε
%
−0.75
0.75
5)
Linearity error
εL
%
εI ext
%
±0.4
6)
Parameter
Influence of external current
Min
Value
Max
Comment
Not applicable 1)
Min
Typ
@ 50 Hz 2)
@ 50 Hz
Max
Comment
@ 50 Hz, IP = 1 kA
Cable length: 1.5 m
Class 0.5 accuracy according to
IEC 61869-2
Including positioning error
None
0
±0.2
Notes: 1) The Rogowski coil can measure any primary current as there is no saturation effect.
2)
Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power
remains low (< 2 Watts)
3)
Frequency bandwidth and phase shift modeling schematic can be provided on request.
4)
Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5)
Considering a primary conductor of at least ⌀ 15 mm, perpendicular and in contact with the Rogowski coil.
6)
Considering an external conductor of at least ⌀ 15 mm the same current level than internal conductor, perpendicular
and in contact with the Rogowski coil.
Page 4/12
18January2018/version 6
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
LEM City answers the demand for an accurate, reliable and easy to install energy sensor for future Smart Cities.
www.lem.com
www.lemcity.com
SPLIT CORE ROGOWSKI COIL
ART Series
Electrical data ART-B22-D125
At TA = 25 °C, RL = 10 kΩ, unless otherwise noted.
Parameter
Symbol
Unit
Rated primary current
IPr
A
Rated short-time thermal current
Ith
kA
300
Rated transformation ratio
kra
kA/V
44.44
Rated frequency
fr
Hz
50/60
Symbol
Unit
Secondary voltage
US
mV
22.5
Mutual inductance
M
nH
72.14
Temperature coefficient of M
TCM
ppm/K
±30
Frequency bandwidth (−3 dB)
BW
kHz
373
3)
Phase displacement 4) @ 50/60 Hz
Δφ
°
0.004
3)
Coil inductance
LS
µH
258
Coil resistance
RS
Ω
81
Ratio error (centered)
ε
%
−0.5
0.5
Ratio error (all positions)
ε
%
−0.75
0.75
5)
Linearity error
εL
%
εI ext
%
±0.4
6)
Parameter
Influence of external current
Min
Value
Max
Comment
Not applicable 1)
Min
Typ
@ 50 Hz 2)
@ 50 Hz
Max
Comment
@ 50 Hz, IP = 1 kA
Cable length: 1.5 m
Class 0.5 accuracy according to
IEC 61869-2
Including positioning error
None
0
±0.2
Notes: 1) The Rogowski coil can measure any primary current as there is no saturation effect.
2)
Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power
remains low (< 2 Watts)
3)
Frequency bandwidth and phase shift modeling schematic can be provided on request.
4)
Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5)
Considering a primary conductor of at least ⌀ 15 mm, perpendicular and in contact with the Rogowski coil.
6)
Considering an external conductor of at least ⌀ 15 mm the same current level than internal conductor, perpendicular
and in contact with the Rogowski coil.
Page 5/12
18January2018/version 6
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
LEM City answers the demand for an accurate, reliable and easy to install energy sensor for future Smart Cities.
www.lem.com
www.lemcity.com
SPLIT CORE ROGOWSKI COIL
ART Series
Electrical data ART-B22-D175
At TA = 25 °C, RL = 10 kΩ, unless otherwise noted.
Parameter
Symbol
Unit
Rated primary current
IPr
A
Rated short-time thermal current
Ith
kA
300
Rated transformation ratio
kra
kA/V
44.44
Rated frequency
fr
Hz
50/60
Symbol
Unit
Secondary voltage
US
mV
22.5
Mutual inductance
M
nH
72.31
Temperature coefficient of M
TCM
ppm/K
±30
Frequency bandwidth (−3 dB)
BW
kHz
350
3)
Phase displacement 4) @ 50/60 Hz
Δφ
°
0.004
3)
Coil inductance
LS
µH
343
Coil resistance
RS
Ω
105
Ratio error (centered)
ε
%
−0.5
0.5
Ratio error (all positions)
ε
%
−0.75
0.75
5)
Linearity error
εL
%
εI ext
%
±0.4
6)
Parameter
Influence of external current
Min
Value
Max
Comment
Not applicable 1)
Min
Typ
@ 50 Hz 2)
@ 50 Hz
Max
Comment
@ 50 Hz, IP = 1 kA
Cable length: 1.5 m
Class 0.5 accuracy according to
IEC 61869-2
Including positioning error
None
0
±0.2
Notes: 1) The Rogowski coil can measure any primary current as there is no saturation effect.
2)
Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power
remains low (< 2 Watts)
3)
Frequency bandwidth and phase shift modeling schematic can be provided on request.
4)
Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5)
Considering a primary conductor of at least ⌀ 15 mm, perpendicular and in contact with the Rogowski coil.
6)
Considering an external conductor of at least ⌀ 15 mm the same current level than internal conductor, perpendicular
and in contact with the Rogowski coil.
Page 6/12
18January2018/version 6
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
LEM City answers the demand for an accurate, reliable and easy to install energy sensor for future Smart Cities.
www.lem.com
www.lemcity.com
SPLIT CORE ROGOWSKI COIL
ART Series
Electrical data ART-B22-D300
At TA = 25 °C, RL = 10 kΩ, unless otherwise noted.
Parameter
Symbol
Unit
Rated primary current
IPr
A
Rated short-time thermal current
Ith
kA
300
Rated transformation ratio
kra
kA/V
44.44
Rated frequency
fr
Hz
50/60
Symbol
Unit
Secondary voltage
US
mV
22.5
Mutual inductance
M
nH
72.84
Temperature coefficient of M
TCM
ppm/K
±30
Frequency bandwidth (−3 dB)
BW
kHz
300
3)
Phase displacement 4) @ 50/60 Hz
Δφ
°
0.004
3)
Coil inductance
LS
µH
566
Coil resistance
RS
Ω
170
Ratio error (centered)
ε
%
−0.5
0.5
Ratio error (all positions)
ε
%
−0.75
0.75
5)
Linearity error
εL
%
εI ext
%
±0.4
6)
Parameter
Influence of external current
Min
Value
Max
Comment
Not applicable 1)
Min
Typ
@ 50 Hz 2)
@ 50 Hz
Max
Comment
@ 50 Hz, IP = 1 kA
Cable length: 1.5 m
Class 0.5 accuracy according to
IEC 61869-2
Including positioning error
None
0
±0.2
Notes: 1) The Rogowski coil can measure any primary current as there is no saturation effect.
2)
Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power
remains low (< 2 Watts)
3)
Frequency bandwidth and phase shift modeling schematic can be provided on request.
4)
Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer)
5)
Considering a primary conductor of at least ⌀ 15 mm, perpendicular and in contact with the Rogowski coil.
6)
Considering an external conductor of at least ⌀ 15 mm the same current level than internal conductor, perpendicular
and in contact with the Rogowski coil.
Page 7/12
18January2018/version 6
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
LEM City answers the demand for an accurate, reliable and easy to install energy sensor for future Smart Cities.
www.lem.com
www.lemcity.com
SPLIT CORE ROGOWSKI COIL
ART Series
Definition of typical, minimum and maximum values
Minimum and maximum values for specified limiting and safety conditions have to be understood as such as well as values
shown in “typical” graphs.
On the other hand, measured values are part of a statistical distribution that can be specified by an interval with upper and lower
limits and a probability for measured values to lie within this interval.
Unless otherwise stated (e.g. “100 % tested”), the LEM definition for such intervals designated with “min” and “max” is that the
probability for values of samples to lie in this interval is 99.73 %.
For a normal (Gaussian) distribution, this corresponds to an interval between −3 sigma and +3 sigma. If “typical” values are not
obviously mean or average values, those values are defined to delimit intervals with a probability of 68.27 %, corresponding to
an interval between −sigma and +sigma for a normal distribution.
Typical, minimum and maximum values are determined during the initial characterization of the product.
Accuracy class according to IEC 61869-2
Conductor centered
1.5
1.25
1
Current error (%)
0.75
0.5
Class 0.5
0.25
0
-0.25
-0.5
-0.75
-1
-1.25
-1.5
5
20
% of IPr
100
120
Accuracy class limit of IEC 61869-2
Accuracy class limit of ART-B22 Rogowski
Page 8/12
18January2018/version 6
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
LEM City answers the demand for an accurate, reliable and easy to install energy sensor for future Smart Cities.
www.lem.com
www.lemcity.com
SPLIT CORE ROGOWSKI COIL
ART Series
Performance parameters definition
Rated transformation ratio kra
Ratio of kra to the actual secondary voltage.
Ratio error ε
The current ratio error, expressed as a percentage, is defined
by the formula:
ε=
kra Us − IP
IP
× 100 %
Where:
kra: is the rated transformation ratio
IP: is the actual primary current
US: is the actual secondary voltage when IP is
flowing
Phase displacement Δφ
The Δφ is the difference in phase between the primary current
and the ideal secondary voltage phasors. The direction of
the phasors being that the angle is 90 ° (leading) for an ideal
Rogowski coil.
The phase displacement is said to be positive when the
secondary voltage phasor leads the primary current phasor.
Linearity error εL
The linearity error εL is the maximum positive or negative
difference between the measured points and the linear
regression line, expressed as a percentage of IPr.
Rated short-time thermal current Ith
Maximum value of the primary current which the Rogowski will
withstand for a specified short time without suffering harmful
effects.
Page 9/12
18January2018/version 6
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
LEM City answers the demand for an accurate, reliable and easy to install energy sensor for future Smart Cities.
www.lem.com
www.lemcity.com
SPLIT CORE ROGOWSKI COIL
ART Series
ART-B22-DXXX series: name and codification
ART-B22-DXXX
Family:
Rogowski coil
Output signal:
22.5: mV/kA
Other cable lengths available
Product name
Length (m)
Mass (g)
ART-B22-D70/SP3
3
192
ART-B22-D70/SP4
4.5
259
ART-B22-D70/SP6
6
327
ART-B22-D125/SP3
3
198
ART-B22-D125/SP4
4.5
265
ART-B22-D125/SP6
6
333
ART-B22-D175/SP3
3
206
ART-B22-D175/SP4
4.5
273
ART-B22-D175/SP6
6
341
ART-B22-D300/SP3
3
222
ART-B22-D300/SP4
4.5
290
ART-B22-D300/SP6
6
357
Aperture
D70: ⌀ 70 mm
D125: ⌀ 125 mm
D175: ⌀ 175 mm
D300: ⌀ 300 mm
Page 10/12
18January2018/version 6
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
LEM City answers the demand for an accurate, reliable and easy to install energy sensor for future Smart Cities.
www.lem.com
www.lemcity.com
SPLIT CORE ROGOWSKI COIL
ART Series
Safety and warning notes
In order to guarantee safe operation of the transducer and to be able to make proper use of all features and functions, please
read these instructions thoroughly!
Safe operation can only be guaranteed if the transducer is used for the purpose it has been designed for and within the limits of
the technical specifications.
Ensure you get up-to-date technical information that can be found in the latest associated datasheet under www.lem.com.
Caution! Risk of danger
Ignoring the warnings can lead to serious injury and/or cause damage! The electric measuring transducer may only be installed
and put into operation by qualified personnel that have received an appropriate training.
The corresponding national regulations shall be observed during installation and operation of the transducer and any electrical
conductor.
The transducer shall be used in electric/electronic equipment with respect to applicable standards and safety requirements and
in accordance with all the related systems and components manufacturers’ operating instructions.
Caution! Risk of electrical shock
When operating the transducer, certain parts of the module may carry hazardous live voltage (e.g. primary conductor). The user
shall ensure to take all measures necessary to protect against electrical shock. The transducer is a build-in device containing
conducting parts that shall not be accessible after installation. A protective enclosure or additional insulation barrier may
be necessary. Installation and maintenance shall be done with the main power supply disconnected except if there are no
hazardous live parts in or in close proximity to the system and if the applicable national regulations are fully observed.
Safe and trouble-free operation of this transducer can only be guaranteed if transport, storage and installation are carried out
correctly and operation and maintenance are carried out with care.
Caution! Risk of electrical shock
Do not apply around or remove from uninsulated hazardous live conductors which may result in electric shock, electric burn or
arc flash.
Page 11/12
18January2018/version 6
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
LEM City answers the demand for an accurate, reliable and easy to install energy sensor for future Smart Cities.
www.lem.com
www.lemcity.com
SPLIT CORE ROGOWSKI COIL
ART Series
Dimensions (in mm)
IP
Connection
diP/dt
IP
VS+
VS-
Mechanical characteristics
●● General tolerance
●● Output cable length
●● Termination
●● Cable tie maximum effort
±1 mm
See table page 8
or drawing above
2 stripped wires
50 N
Remarks
●● US = VS+ − VS- is positive when an increasing primary
current di/dt flows in the direction of the arrow (see fig. 1).
●● Due to low positioning error (εP), the device does not need
to be physically fastened around the primary conductor.
Should the device be secured, make sure no mechanical
stress is applied to the coil itself.
●● This product is not intended for outdoor use.
●● Installation of the transducer must be done unless
otherwise specified on the datasheet, according to LEM
Transducer Generic Mounting Rules. Please refer to
LEM document N°ANE120504 available on our Web site:
Products/Product Documentation.
Page 12/12
18January2018/version 6
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
LEM City answers the demand for an accurate, reliable and easy to install energy sensor for future Smart Cities.
www.lem.com