Current Transducers HAS 50..600-P
For the electronic measurement of currents: DC, AC, pulsed, mixed, with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).
IPN
= 50..600 A
VOUT = ±4 V
E lectrical data
Primary nominal r.m.s. current IPN (A) 50 100 200 300 400 500 600 Primary current measuring range IP (A) ±150 ±300 ±600 ±900 ±900 ±900 ±900 Type
HAS HAS HAS HAS HAS HAS HAS
50-P 100-P 200-P 300-P 400-P 500-P 600-P
Features
• Hall effect measuring principle • Galvanic isolation between primary • Isolation voltage 3000 V~ • Low power consumption • Extended measuring range (3 x IPN) • Insulated plastic case made of
polycarbonate PBT recognized according to UL 94-V0 • Right angle pins for direct PCB mounting and secondary circuit
VC IC IOC Vd Vb RIS VOUT ROUT RL
Supply voltage (± 5 %) Current consumption Overload capacity R.m.s. voltage for AC isolation test, 60 Hz, 1 mn R.m.s. rated voltage, safe separation Isolation resistance @ 500 VDC Output voltage @ ± IPN, RL = 10 kΩ, TA = 25°C Output internal resistance approx. Load resistance
±15 ±15 30,000 3 5001) > 1000 ±4V ±40 100 >1
V mA At kV V MΩ mV Ω kΩ
Advantages Accuracy - Dynamic performance data
X Accuracy @ IPN, TA = 25°C (without offset) Linearity 2) (0 .. ± IPN) Electrical offset voltage, TA = 25°C Hysteresis offset voltage @ IPN→ 0 Thermal drift of VOE HAS 50-P
HAS 100..600-P
ε
L
VOE VOH VOT TCε G tr di/dt f
Thermal drift of the gain (% of reading) Response time @ 90% of IP di/dt accurately followed Frequency bandwidth (small signal, -1dB) 3) 4)
< ±1 % < ±1 % of IPN < ±40 mV < ±20 mV < ±2 mV/K < ±1 mV/K < ±0.1 %/K 50 A/µs DC .. 25 kHz
• Easy mounting • Small size and space saving • Only one design for wide current • High immunity to external
interference. ratings range
Applications
• AC variable speed drives • Static converters for DC motor drives • Battery supplied applications • Uninterruptible Power Supplies • Switched Mode Power Supplies • Power supplies for welding
applications. (SMPS) (UPS)
General data
TA TS m Ambient operating temperature Ambient storage temperature Mass Standards 5)
1) 2) 3)
- 25 .. + 85 °C - 25 .. + 85 °C approx. 80 g EN 50082-2
Notes :
4) 5)
Pollution class 2, overvoltage category III. Linearity data exclude the electrical offset. Please refer to derating curves in the technical file to avoid excessive core heating at high frequency. Amorphous core option for high frequency application. Please consult characterisation report for more technical details and application advice.
040406/0
LEM Components
www.lem.com
HAS 50..600-P Dimensions (in mm)
PINS ARRANGEMENT 1. 2. 3. 4. +15V –15V OUTPUT 0V
LEM reserves the right to change limits and dimensions.