HAS600-P

HAS600-P

  • 厂商:

    LEM(莱姆)

  • 封装:

    Module

  • 描述:

    SENSORCURRENTHALL600AAC/DC

  • 数据手册
  • 价格&库存
HAS600-P 数据手册
Current Transducers HAS 50..600-P For the electronic measurement of currents: DC, AC, pulsed, mixed, with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit). IPN = 50..600 A VOUT = ± 4 V Electrical data Primary nominal current rms IPN (A) 50 100 200 300 400 500 600 Primary current, measuring range IPM (A) ± ± ± ± ± ± ± 150 300 600 900 900 900 900 Type RoHS since date code 46065 46062 planned planned 46131 46216 planned HAS HAS HAS HAS HAS HAS HAS 50-P 100-P 200-P 300-P 400-P 500-P 600-P Features • Hall effect measuring principle • Galvanic isolation between primary • Isolation voltage 3000 V~ • Low power consumption • Extended measuring range (3 x IPN) • Insulated plastic case made of polycarbonate PBT recognized according to UL 94-V0 • Right angle pins for direct PCB mounting and secondary circuit VC IC ÎP Vd Vb RIS VOUT ROUT RL Supply voltage (± 5 %) Current consumption Overload capability Rms voltage for AC isolation test, 50 Hz, 1 min Rated isolation voltage rms, safe separation Isolation resistance @ 500 VDC Output voltage (Analog)@ ± IPN, RL = 10 kΩ, TA = 25°C Output internal resistance approx. Load resistance 6) ± 15 V ± 15 mA 30,000 At 3 kV 5001) V > 1000 MΩ ± 4 V ± 40 mV 100 Ω >1 kΩ Accuracy - Dynamic performance data X Advantages
HAS600-P 价格&库存

很抱歉,暂时无法提供与“HAS600-P”相匹配的价格&库存,您可以联系我们找货