Current Transducers HAX 500 to 2500-S
For the electronic measurement of currents: DC, AC, pulsed, mixed, with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).
IPN
= 500 .. 2500 A ±4V
VOUT =
Electrical data
Primary nominal r.m.s. current IPN (A) 500 850 1000 1200 1500 2000 2500 Primary current measuring range IP (A) ± ± ± ± ± ± ± 1500 2550 3000 3600 4500 5500 5500 Type
HAX HAX HAX HAX HAX HAX HAX
500-S 850-S 1000-S 1200-S 1500-S 2000-S 2500-S
Features
• Hall effect measuring principle • Galvanic isolation between primary • Isolation voltage 5000 V~ • Low power consumption • Extended measuring range (3 x IPN) • Package in PBT meets UL 94-V0
and secondary circuit
VC IC IOC Vd Vb RIS VOUT ROUT RL
Supply voltage (± 5 %) Current consumption Overload capacity R.m.s. voltage for AC isolation test, 60 Hz, 1 mn R.m.s. rated voltage, safe separation Isolation resistance @ 500 VDC Output voltage @ ± IPN, RL = 10 kΩ, TA = 25°C Output internal resistance approx. Load resistance
± 15 ± 15 30,000 5 5001) > 1000 ± 4V ± 40 100 >1
V mA At kV V MΩ mV Ω kΩ
Advantages
• Easy mounting • Small size and space savings • Only one design for wide current • High immunity against external
interference ratings range
Accuracy - Dynamic performance data
X
ε
L
VOE VOH VOT TCε G tr di/dt f
Accuracy @ IPN, TA = 25°C (without offset) Linearity 2) (0 .. ± IPN) Electrical offset voltage, TA = 25°C Hysteresis offset voltage @ IP = 0; after an excursion of 1 x IPN Thermal drift of VOE Thermal drift of the gain (% of reading) Response time @ 90% of IP di/dt accurately followed Frequency bandwidth 3)(- 3 dB)
很抱歉,暂时无法提供与“HAX1200-S”相匹配的价格&库存,您可以联系我们找货
免费人工找货