Current Transducer HAX 500..2500-S
For the electronic measurement of currents: DC, AC, pulsed, mixed, with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).
IPN = 500..2500 A VOUT= ± 4 V
Electrical data
Primary nominal rms current IPN (A) 500 600 850 1000 1200 1500 2000 2500 Primary current measuring range 5) IP (A) ± ± ± ± ± ± ± ± 1500 1800 2550 3000 3600 4500 5500 5500 Type RoHS since date code 46137 planned 45350 45348 46138 46017 46100 46143
HAX HAX HAX HAX HAX HAX HAX HAX
500-S 600-S 850-S 1000-S 1200-S 1500-S 2000-S 2500-S
Features
• Hall effect measuring principle • Galvanic isolation between primary • Isolation voltage 5000 V~ • Low power consumption • Package in PBT meets UL 94-V0
and secondary circuit
VC IC IOC RIS VOUT ROUT RL
Supply voltage (± 5 %) 5) Current consumption Overload capacity Isolation resistance @ 500 VDC Output voltage (Analog) @ ± IPN, RL = 10 kΩ, TA = 25°C Output internal resistance approx. Load resistance
± 15 ± 15 30,000 > 1000 ± 4V ± 40 100 >1
V mA At MΩ mV Ω kΩ
Advantages
• Easy mounting • Small size and space savings • Only one design for wide current • High immunity against external
interference ratings range
Accuracy - Dynamic performance data
X
ε
L
VOE VOH TCVOE TCG tr di/dt f
Accuracy @ IPN, TA = 25°C (without offset) Linearity error 2) (0 .. ± IPN) Electrical offset voltage, TA = 25°C Hysteresis offset voltage @ IP = 0; after an excursion of 1 x IPN Temperature coefficient of VOE Temperature coefficient of G (% of reading) Response time @ 90% of IP di/dt accurately followed Frequency bandwidth 3)(- 3 dB)