Current Transducers HAZ 4000..20000-SRI/SP1
For the electronic measurement of currents: DC, AC, pulsed, mixed, with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).
IPN = 4000..20000 A IOUT = 4-20 mA (T-RMS DC)
Electrical data
Primary nominal r.m.s. current IPN (A) 4000 6000 10000 12000 14000 20000 Primary current measuring range IP (A) ± ± ± ± ± ± 4000 6000 10000 12000 14000 20000 Type
HAZ 4000-SRI/SP1 HAZ 6000-SRI/SP1 HAZ 10000-SRI/SP1 HAZ 12000-SRI/SP1 HAZ 14000-SRI/SP1 HAZ 20000-SRI/SP1
Features
• Hall effect measuring principle • Galvanic isolation between primary • True-rms, 4-20mA DC current output • Isolation voltage 12kV Rms/ 50 Hz • Low power consumption • Package in PBT meeting UL 94-V0
/ 1 min and secondary circuit
VC IC IOC RIS IOUT ROUT RL
Supply voltage (± 5 %) Current consumption Overload capacity Isolation resistance @ 500 VDC Output current @ ± IPN, TA = 25°C (+4 mA @ IP = 0) Output internal resistance approx. Load resistance
± 15 V ± 50 mA 30,000 A > 1000 MΩ + 4-20 mA DC 20 Ω < 300 Ω
Special Feature
• True-rms, 4-20mA DC current output
Accuracy - Dynamic performance data
X
ε
L
IOE IOM IOT TCε G tr f
Accuracy @ IPN, TA = 25°C (without offset) Linearity error 1) (0 .. ± IPN) Electrical offset current, TA = 25°C, @ IP = 0 Residual offset current @ IP = 0; after an excursion of 1 x IPN Thermal drift of IOE Thermal drift of the gain (% of reading) Response time @ 90% of IPN Frequency range, ±3 dB, small signal 2)
3 27 > 45 > 45 220
kV kV kV mm mm V
0 60428/4
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice. Page 2/3
LEM
www.lem.com
Dimensions HAZ 4000..20000-SRI/SP1 (in mm. 1 mm = 0.0394 inch)
FUJICON F2023A 6
1
Connection Circuit
HAZ XXX-SRI/SP1 HAZxxx-SRI
6
5
4
3
2
1
50
48
T.P.
GND OUTPUT
0V -Vc +Vc
HAZ 10000-SRI HAZ10000-SRI/SP1
1
250 +/-1.5 235
+Vc -Vc 0V OUTPUT GND RL< 300 Ohm
2 3
4-D6
4 5
160 +/-1.5 65
6
42 +/-1 41.5 ± 1.5 42 2
T.P. (Internal test point used during factory calibrations)
125
16 ± 1 161 2 ± 162 +/-12
75
Operation Principle
7.5
+Vc
200 M5
Terminal 1...+Vc 2...-Vc 3...0V 4...OUTPUT 5...GND 6...T.P.
Output 0V Ip -Vc
50 48 35
General tolerance +/-0.5
Mechanical characteristics
• General tolerance • Aperture for primary conductor
± 0.5 mm 162 mm x 42 mm (± 2 mm) • Transducer fastening 4 x M5 (not supplied) • Recommended fastening torque < 5 Nm • Connection of secondary Fujicon F2023A (6 terminals)
Safety
This transducer must be used in electric/electronic equipment with respect to applicable standards and safety requirements in accordance with the following manufacturer's operating instructions.
Caution, risk of electrical shock When operating the transducer, certain parts of the module can carry hazardous voltage (eg. primary busbar, power supply). Ignoring this warning can lead to injury and/or cause serious damage. This transducer is a built-in device, whose conducting parts must be inaccessible after installation. A protective housing or additional shield could be used. Main supply must be able to be disconnected. 060428/4
Remarks
• Temperature of the primary conductor should not exceed
120°C.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.