Current Transducer LAH 100-P
For the electronic measurement of currents : DC, AC, pulsed ..., with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).
IPN = 100 A
Electrical data
IPN IP RM Primary nominal r.m.s. current Primary current, measuring range 1) Measuring resistance @ with ± 12 V 100 0 .. 160 TA = 70°C TA = 85°C RM min RM max RM min RM max A A
Features
• Closed loop (compensated) current
transducer using the Hall effect
ISN KN VC IC Vd Ve Vw X
@ IPN [± A DC ] 0 63 0 57 @ IPN [A RMS ] 2) 0 11 0 5 with ± 15 V @ IPN [± A DC ] 20 120 45 114 @ IPN [A RMS ] 2) 20 51 45 45 @ IP < IPN 3) Secondary nominal r.m.s. current 50 Conversion ratio 1 : 2000 Supply voltage (± 5 %) ± 12 .. 15 Current consumption 10 ( @ ± 15 V)+I S R.m.s. voltage for AC isolation test, 50/60 Hz, 1 mn 5 R.m.s. voltage for partial discharge extinction @ 10 pC > 2 Impulse withstand voltage 1.2/50 µs > 12
Ω Ω Ω Ω mA V mA kV kV kV
• Printed circuit board mounting • Insulated plastic case recognized
according to UL 94-V0.
Advantages
• • • • • • •
Excellent accuracy Very good linearity Low temperature drift Optimized response time Wide frequency bandwidth No insertion losses High immunity to external interference • Current overload capability.
Accuracy - Dynamic performance data
ε
L
Accuracy 4) @ IPN, TA = 25°C Linearity Offset current @ TA = 25°C Residual current @ IP = 0, after an overload of 5 x IPN Thermal drift of IO 0°C .. + 70°C - 25°C .. + 85°C Reaction time @ 10 % of IPN Response time 5) @ 90 % of IPN di/dt accurately followed Frequency bandwidth (- 1 dB)
± 0.25 < 0.15 Max ± 0.15 ± 0.10 ± 0.15 ± 0.10 ± 0.40 ± 0.10 ± 0.50 < 200 < 500 > 200 DC .. 200 Typ
% % mA mA mA mA ns ns A/µs kHz
Applications
• AC variable speed drives and servo
motor drives
IO IOM IOT tr a tr di/dt f
• Static converters for DC motor drives • Battery supplied applications • Uninterruptible Power Supplies
(UPS)
• Switched Mode Power Supplies
(SMPS)
General data
TA TS RS Ambient operating temperature Ambient storage temperature Secondary coil resistance Insulating material group Mass Standards 6)
1) 3)
• Power supplies for welding
- 25 .. + 85 - 40 .. + 90 115 121 I 24 EN 50178 °C °C Ω Ω g applications.
@ TA = 70°C @ TA = 85°C
m Notes :
6)
For 10 s, with R M ≤ 25 Ω (VC = ± 15 V) - 2) 50 Hz Sinusoidal The measuring resistance RM min may be lower (see "LAH Technical Information" leaflet) - 4) Without IO & IOM - 5) With a di/dt of 100 A/µs A list of corresponding tests is available.
010820/5
LEM Components
w w w.lem.com
Dimensions LAH 100-P (in mm. 1 mm = 0.0394 inch)
Bottom view
Primary turns : Secondary pins :
Front view
Left view
Secondary terminals
Terminal M : measure Terminal + : supply voltage + 15 V Terminal - : supply voltage - 15 V
IN OUT
Connection
Number of primary turns
Primary current nominal maximum
Nominal output current
Turns ratio
Primary resistance
Primary insertion inductance
IPN
[A]
IP
[A] 160
ISN
[ mA ] 50
KN 1 : 2000
RP
[ mΩ ] 0.08
LP 0.007
[ µH ]
1
100
Mechanical characteristics
• General tolerance • Fastening & connection of primary
Recommended PCB hole • Fastening & connection of secondary Recommended PCB hole ± 0.2 mm 6 pins 1.4 x 1 mm 2 mm 3 pins 0.7 x 0.6 mm 1.2 mm
Remarks
• IS is positive when IP flows from terminals "IN" to terminals
"OUT".
• This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...), please contact us.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
很抱歉,暂时无法提供与“LAH100-P”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格
- 1+91.34640
- 10+87.67440
- 30+81.31320