Current Transducer LF 505-S For the electronic measurement of currents : DC, AC, pulsed..., with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit). IPN = 500 A 16137 Electrical data I PN IP RM Primary nominal rms current Primary current, measuring range Measuring resistance with ± 15 V with ± 18 V with ± 24 V ISN KN VC IC @ ± 500 A max @ ± 800 A max @ ± 500 A max @ ± 800 A max @ ± 500 A max @ ± 800 A max 500 0 .. ± 800 RM min RM max 0 0 0 0 5 5 60 11 92 30 149 65 A A Ω Ω Ω Ω Ω Ω Features • Closed loop (compensated) current • Insulated plastic case recognized according to UL 94-V0. transducer using the Hall effect Advantages • • • • • • • Excellent accuracy Very good linearity Low temperature drift Optimized response time Wide frequency bandwidth No insertion losses High immunity to external interference • Current overload capability. Secondary nominal rms current Conversion ratio Supply voltage (± 5 %) Current consumption 100 mA 1 : 5000 ± 15 .. 24 V 24 (@ ± 18 V) + IS mA Accuracy - Dynamic performance data XG ε L Overall accuracy @ IPN , T A = 25°C Linearity error Offset current @ IP = 0, T A = 25°C Thermal drift of IO - 40°C .. + 70°C Response time 1) @ 90 % of IPN di/dt accurately followed Frequency bandwidth (- 1 dB) ± 0.6 < 0.1 Typ Max ± 0.4 ± 0.4 % % mA mA µs A/µs kHz Applications • AC variable speed drives and servo motor drives Static converters for DC motor drives Battery supplied applications Uninterruptible Power Supplies (UPS) Switched Mode Power Supplies (SMPS) • Power supplies for welding applications. IO IOT tr di/dt f ± 0.1 100 DC .. 100 • • • • General data TA TS RS m Ambient operating temperature Ambient storage temperature Secondary coil resistance @ Mass Standards - 40 .. + 70 °C - 40 .. + 85 °C 70 Ω 230 g EN 50155 : 1995 EN 50178 : 1997 T A = 70°C Applications domain • Traction • Industrial. Note : 1) With a di/dt of 100 A/µs. page 1/3 060922/9 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice. www.lem.com Current Transducer LF 505-S Isolation characteristics Vd Vw R.m.s. voltage for AC isolation test, 50 Hz, 1 mn Impulse withstand voltage 1.2/50 µs 3.8 12.5 Min 15.2 14.5 175 kV kV dCp dCl CTI Creepage distance Clearance distance Comparative Tracking Index (Group IIIa) mm mm Application examples According to EN 50178 and CEI 61010-1 standards and following conditions : • Over voltage category OV 3 • Pollution degree PD2 • Non-uniform field EN 50178 dCp, dCI, VW Single isolation Reinforced isolation Rated isolation voltage 1250 V 690 V CEI 61010-1 Nominal voltage 1250 V rms 690 V rms Safety This transducer must be used in electric/electronic equipment with respect to applicable standards and safety requirements in accordance with the following manufacturer's operating instructions. Caution, risk of electrical shock When operating the transducer, certain parts of the module can carry hazardous voltage (eg. primary busbar, power supply). Ignoring this warning can lead to injury and/or cause serious damage. This transducer is a built-in device, whose conducting parts must be inaccessible after installation. A protective housing or additional shield could be used. Main supply must be able to be disconnected. page 2/3 060922/9 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice. www.lem.com Dimensions LF 505-S (in mm. 1 mm = 0.0394 inch) Bottom view Right view Back view Top view Connection Mechanical characteristics • General tolerance • Transducer fastening Vertical or flat lying position Recommended fastening torque or vertical position ± 0.5 mm 4 or 6 holes ∅ 4.3 mm 4 or 6 steel screws M4 3.2 Nm or 2.37 Lb.-Ft. 4 holes ∅ 1.9 mm, depth : 7.5 mm 4 screws PTKA 25, length: 6 mm 0.7 Nm or 0.52 Lb.-Ft. 4 holes ∅ 1.9 mm, crossing 4 screws PTKA 25, length:10 mm 0.75 Nm or 0.55 Lb.-Ft. ∅ 30.2 mm MOLEX 5045-03/A Remarks • IS is positive when IP flows in the direction of the arrow. • Temperature of the primary conductor should not exceed • Dynamic performances (di/dt and response time) are best • This is a standard model. For different versions (supply voltages, turns ratios, unidirectional measurements...), please contact us. with a single bar completely filling the primary hole. 100°C. Recommended fastening torque or flat lying position • Primary through-hole • Connection of secondary 060922/9 Recommended fastening torque page 3/3 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice. www.lem.com
LF505-S
### 物料型号 - 型号: LF 505-S

### 器件简介 - 简介: 该器件是一个闭环霍尔效应电流传感器,用于电子测量直流、交流、脉冲等电流,具有高绝缘性,能够在主电路(高功率)和次级电路(电子电路)之间提供电气隔离。

### 引脚分配 - 次级连接: 使用MOLEX 5045-03/A连接器。 - 主电路连接: 通过一个直径为30.2mm的通孔连接。

### 参数特性 - 初级额定电流: 500 A - 测量范围: 0 .. ±800 A - 测量电阻: - 在±15V下,±500A最大值为0.60Ω;±800A最大值为1.92Ω - 在±18V下,±500A最大值为0.11Ω;±800A最大值为0.30Ω - 在±24V下,±500A最大值为5.149Ω;±800A最大值为5.65Ω - 次级额定电流: 100 mA - 转换比: 1:5000 V - 电源电压: ±15 .. 24V - 电流消耗: 24mA (@ ±18V) - 整体精度: 在IPN,TA = 25°C时为±0.6% - 线性误差: <0.1% - 偏移电流: 在IP = 0, TA = 25°C时,热漂移为±0.1 ± 0.4 mA

### 功能详解 - 功能: - 闭环(补偿)电流传感器 - 使用霍尔效应 - 绝缘塑料外壳,符合UL 94-V0标准 - 优秀的精度和线性 - 低温度漂移 - 优化的响应时间 - 宽频带宽度 - 无插入损耗 - 高抗外部干扰能力 - 能够承受电流过载

### 应用信息 - 应用领域: - 交流变频驱动和伺服电机驱动 - 直流电机驱动的静态转换器 - 电池供电应用 - 不间断电源(UPS) - 开关模式电源(SMPS) - 焊接应用电源 - 应用示例: 根据EN 50178和CEI 61010-1标准,适用于过电压类别OV 3、污染程度PD2和非均匀场的条件。

### 封装信息 - 尺寸: LF 505-S的尺寸图示提供了详细的机械特性,包括安装孔和推荐扭矩。 - 安装: 提供了垂直或平躺位置的安装选项和推荐扭矩。