Current Transducer LTC 1000-SFC
For the electronic measurement of currents : DC, AC, pulsed..., with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).
IPN =
1000 A
Electrical data
IPN IP ÎP RM Primary nominal r.m.s. current Primary current, measuring range @ 24 V Max overload not measurable Measuring resistance with ± 15 V with ± 24 V ISN KN VC IC Vd Ve @ ± 1000 A max @ ± 1200 A max @ ± 1000 A max @ ± 2000 A max 1000 A 0 .. ± 2400 1) A 10 / 10 kA/ms RM min RM max 0 0 0 0 15 7 50 7 Ω Ω Ω Ω mA V mA kV kV kV
Features
• Closed loop (compensated) current
transducer using the Hall effect
• Insulated plastic case recognized
according to UL 94-V0
• Transducer delivered with feet and
clamps
Secondary nominal r.m.s. current Conversion ratio Supply voltage (± 5 %) Current consumption R.m.s. voltage for AC isolation test, 50 Hz, 1 mn R.m.s. voltage for partial discharge extinction
200 1 : 5000 ± 15 .. 24 < 30 (@±24V) +IS 13.4 2) 1.5 3) > 2.8 4)
• Railway equipment.
Advantages
• • • • • • •
Excellent accuracy Very good linearity Low temperature drift Optimized response time Wide frequency bandwidth No insertion losses High immunity to external interference • Current overload capability.
Accuracy - Dynamic performance data
XG Overall accuracy @ IPN , TA = 25°C @ IPN , TA = - 40°C .. + 85°C Linearity Offset current @ IP = 0, TA = 25°C Thermal drift of IO Response time 5) @ 90 % of IPN di/dt accurately followed Frequency bandwidth (- 1 dB) < ± 0.4 5 A/µs Between primary and secondary + shield Between secondary and shield Test carried out with a busbar ∅ 40 mm centred in the through-hole With a di/dt of 100 A/µs.
030528/0
LEM Components
w w w.lem.com
Dimensions LTC 1000-SFC (in mm. 1 mm = 0.0394 inch)
Front view Left view
Customer bar
Secondary terminals
Terminal + : supply voltage + 15 .. 24 V Terminal M : measure Terminal - : supply voltage - 15 .. 24 V Terminal E : shield
Connection
or
Top view Mechanical characteristics
• General tolerance • Fixing the transducer
Fastening torque max • Primary through-hole • Connection of secondary Fastening torque max ± 1 mm 4 slots ∅ 6 .5 mm 4 screws M6 5 Nm ∅ 4 2 mm M5 threaded studs 2.2 Nm or 1.62 Lb.-Ft. Faston 6.3 x 0.8 mm
Remarks
• IS is positive when IP flows in the direction of the arrow. • Temperature of the primary conductor should not exceed
100°C.
• Dynamic performances (di/dt and response time) are best
with a single bar completely filling the primary hole.
• This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...), please contact us.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.