Axial Lead and Cartridge Fuses
Midget
AC Fast-Acting Type KLK Series
Fast-acting fuses designed for use in circuits with high AC fault current capacity or where military approval is required.
UL ®
®
QPL
ORDERING INFORMATION:
Cartridge Catalog Number KLK 1/10 KLK 1/8 KLK 2/10 KLK 1/4 KLK 3/10 KLK 1/2 KLK 3/4 KLK 1 KLK 11/2 KLK 2 KLK 21/2 KLK 3 KLK 31/2 KLK 4 KLK 5 KLK 6 KLK 7 KLK 8 KLK 9 KLK 10 KLK 12 KLK 15 KLK 20 KLK 25 KLK 30 Ampere Rating .100 .125 .200 .250 .300 .500 .750 1 1.5 2 2.5 3 3.5 4 5 6 7 8 9 10 12 15 20 25 30 Voltage Rating 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 Nominal Resistance Cold Ohms 85.5 65.0 30.9 22.0 16.2 7.99 .398 .249 .132 .129 .0989 .0773 .0613 .0511 .0357 .0261 .0205 .0194 .0166 .0128 .0103 .0073 .00421 .00302 .002816
ELECTRICAL CHARACTERISTICS:
% of Ampere Rating 135% 200 Ampere Rating 1/10 –30 1/10–30 Opening Time 1 hour, Maximum 2 minutes, Maximum
AGENCY APPROVALS: Listed by Underwriters Laboratories and Certified by CSA from 3/10 through 30 amperes. INTERRUPTING RATING:
100,000 amperes (capable of 200,000) at 600VAC.
MILITARY TYPE F60C INTERRUPTING RATINGS:
200,000 amperes at 500VAC 150,000 amperes at 500VDC
FUSES TO MIL SPEC: See F60C type in Military Section. PATENTED
Average Time Current Curves
1/8A 2/10A 1/4A 3/10A 1/2A 3/4A 1A 1 1/2A 2A 2 1/2A 3A 3 1/2A 4A 5A 6A 7A 8A 9A 10A 12A 15A 20A 25A 30A .1 10 CURRENT IN AMPERES 100
1000
100
TIME IN SECONDS
10
38.1 (1.50")
10.31 (.406")
1
0.1
0.01 1 1000
440
w w w. l i t t e l f u s e . c o m