Corcom Product Guide
Catalog: 1654001 Issue Date: 06.2011
General Purpose RFI Power Line Filters – Ideal for High Impedance Load
K Series
UL Recognized CSA Certified VDE Approved**
VK6 VK7 / EK7
1
RFI Power Line Filters
VK1 / EK1 VK3 / EK3
K Series
• Suitable for high impedance loads • Well suited to applications where pulsed, continuous and/or intermittent RFI interference is present • EK models meet the very low leakage current requirements for VDE portable equipment and non-patient care medical equipment • Available with ground line inductor (choke)
Specifications
Maximum leakage current each Line to Ground:
VK Models EK Models
@ 120 VAC 60 Hz: @250 VAC 50 Hz: Hipot rating (one minute): Line to Ground: Line to Line: Rated Voltage (max): Operating Frequency: Rated Current:
.5 mA 1.0 mA
.21 mA .36 mA 2250 VDC 1450 VDC 250 VAC 50/60 Hz 1 to 60A*
Ordering Information 10 E K 7 M
Suffix M – Metric inserts (style 7 only) Omit for standard or none C – Ground choke (30, 40VK6 only) Input / Output Style 1 – .250 [6.3] spade terminals 3 – Wire leads 6 – Threaded bolt 7 – IEC inlet* (line side) .250 [6.3] spade terminals
(load side)
Operating Ambient Temperature Range (at rated current Ir): -10°C to +40°C In an ambient temperature (Ta) higher than +40°C the maximum operating current (Io) is calculated as follows: Io = Ir (85-Ta)/45
Available Part Numbers
1VK1 1VK3 2VK1 2VK3 3VK1 3VK3 3VK7 3VK7M 5VK1 5VK3 5VK7 5VK7M 10VK1 10VK3 10VK6 10VK7 10VK7M 20VK1 20VK6 20VK7* 30VK6 30VK6C 40VK6 40VK6C 60VK6 1EK1 1EK3 2EK1 2EK3 3EK1 3EK3 3EK7 3EK7M 5EK1 5EK3 5EK7 5EK7M 10EK1 10EK3 10EK7 10EK7M 20EK1
K Series Leakage current designation E – Low leakage (