Corcom Product Guide
Catalog: 1654001 Issue Date: 06.2011
High Performance 3-phase RFI Filters for WYE Applications
A Series
UL Recognized CSA Certified VDE Approved
A Series
• For 3-phase, four wire, WYE Applications • Filters each of the three lines plus the neutral and ground line • Both common mode and differential mode suppression from 50kHz to 30MHz • Effective for both balanced and unbalanced loads • Ground choke included • Optional end bell kits available to shield input and output terminals • AYP single stage for lower noise environments • AYT dual stage provides highest performance
Specifications
Maximum leakage current, each Line to Ground: @ 120 VAC 60 Hz: 1.4 mA @ 250 VAC 50 Hz: 3.4 mA Hipot rating (one minute): Line to Ground: Neutral to Ground: Line to Neutral: Rated Voltage (max): Phase to Phase: Phase to Neutral / Ground: Operating Frequency: Rated Current: 1500 VAC 1500 VAC 1450 VDC 440 VAC 250 VAC 50/60 Hz 20 to 60A
Ordering Information 45 AYT 6 C
S u ffix C – Ground Choke Input / Output Style 6 – Threaded 1/4 – 20 bolt Series designation AYP – Single Stage AYT – Dual Stage Current Rating 20, 30, 45 or 60A
Operating Ambient Temperature Range (at rated current Ir): -10°C to +40°C In an ambient temperature (Ta) higher than +40°C the maximum operating current (Io) is calculated as follows: Io = Ir (85-Ta)/45
Electrical Schematics AYP6C Models
LINE A B C N LOAD A B C N LINE GND LOAD GND
98
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.
For email, phone or live chat, please go to te.com/help corcom.com
Corcom Product Guide
Catalog: 1654001 Issue Date: 06.2011
(continued)
High Performance 3-phase RFI Filters for WYE Applications
A Series
Electrical Schematics (continued) AYT6C Models
LINE A B C N LINE GND LOAD GND LOAD A B C N
D B C E A
Case Style
2
Three Phase Filters
Mounting studs: No. 8-32 (8)
Available Part Numbers
20AYP6C 30AYP6C 45AYP6C 60AYP6C 20AYT6C 30AYT6C 45AYT6C 60AYT6C
Terminals: 1/4 x 20 (10)
Torque: 56 lbf-in ± 2 6.33 N-m ±.23
Accessories
Mounting bracket kit with captive nuts: AA400: 20A & 30A versions AA405: 45A & 60A versions
AA406A AA407A
Case Dimensions
Part No. 20AYP6C A*
B
C
AA400
AA405
30AYP6C 45AYP6C 60AYP6C 20AYT6C 30AYT6C
Protective cover for use with mounting bracket: (For Europe only. Limited availability in other regions) AA406A: 20A & 30A versions AA407A: 45A & 60A versions End bell kit (bracket and cover) with captive nuts: AA406: 20A & 30A versions AA407: 45A & 60A versions
AA406 / AA407 Kits includes both bracket and cover
45AYT6C 60AYT6C
D
E
Additional captive nuts: AA401: 10 nuts
99
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.
For email, phone or live chat, please go to te.com/help corcom.com
Corcom Product Guide
Catalog: 1654001 Issue Date: 06.2011
(continued)
High Performance 3-phase RFI Filters for WYE Applications
A Series
Performance Data Typical Insertion Loss
Measured in closed 50 Ohm system
20AYP6C
db 100 90 80 70 60 50 40 30 20 10 0 0.01 0.1 0.15 1 10 30 Frequency in MHz
30AYP6C
db 100 90 80 70 60 50 40 30 20 10 0 0.01 0.1 0.15 1 10 30 Frequency in MHz
45AYP6C
db 100 90 80 70 60 50 40 30 20 10 0 0.01 0.1 0.15 1 10 30 Frequency in MHz
60AYP6C
db 100 90 80 70 60 50 40 30 20 10 0 0.01 0.1 0.15 1 10 30 Frequency in MHz
20AYT6C
db 100 90 80 70 60 50 40 30 20 10 0 0.01 0.1 0.15 1 10 30 Frequency in MHz
30AYT6C
db 100 90 80 70 60 50 40 30 20 10 0 0.01 0.1 0.15 1 10 30 Frequency in MHz
45AYT6C
db 100 90 80 70 60 50 40 30 20 10 0 0.01 0.1 0.15 1 10 30 Frequency in MHz
60AYT6C
db 100 90 80 70 60 50 40 30 20 10 0 0.01 0.1 0.15 1 10 30 Frequency in MHz
Common Mode / Asymmetrical (L-G) Differential Mode / Symmetrical (L-L)
Minimum Insertion Loss
Measured in closed 50 Ohm system
AYP6C
Common Mode / Asymmetrical (Line to Ground) Differential Mode / Symmetrical (Line to Line)
AYT6C
Common Mode / Asymmetrical (Line to Ground) 100
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.
For email, phone or live chat, please go to te.com/help corcom.com
Differential Mode / Symmetrical (Line to Line)
很抱歉,暂时无法提供与“30AYP6C”相匹配的价格&库存,您可以联系我们找货