Corcom Product Guide
Catalog: 1654001 Issue Date: 06.2011
High Performance High Current 3-phase Delta RFI Filters
ADT Series
UL Recognized
ADT Series
• Designed for very high insertion loss for Delta three phase, three wire applications • Available with common or differential mode coils
Specifications
Maximum leakage current at 277 VAC 60 Hz, each Line to Ground: ADT6: 63ADT6S: 100, 160, 200ADT6S Hipot rating (one minute): Line to Ground: Line to Line: Rated Voltage (max): Phase to Phase: Phase to Ground: 1.3 A 2.6 A 4.6 A
2
Three Phase Filters
2210 VDC 2158 VDC 480 VAC 277 VAC 50/60 Hz 63 to 200A
Ordering Information 100 ADT 6 S
S u ffix S – Differential mode coils Omit if none Input / Output Style 6 – Threaded bolt ADT Series Current Rating 63, 100, 160 or 200A
Operating Frequency: Rated Current:
Operating Ambient Temperature Range (at rated current Ir): -10°C to +40°C In an ambient temperature (Ta) higher than +40°C the maximum operating current (Io) is calculated as follows: Io = Ir (85-Ta)/45
Electrical Schematics 63ADT6
LINE A LOAD A
Available Part Numbers
63ADT6 100ADT6 160ADT6 200ADT6 63ADT6S 100ADT6S 160ADT6S 200ADT6S
B
B
C
C
101
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.
For email, phone or live chat, please go to te.com/help corcom.com
Corcom Product Guide
Catalog: 1654001 Issue Date: 06.2011
(continued)
High Performance High Current 3-phase Delta RFI Filters
ADT Series
Electrical Schematics (continued) 100, 160 & 200 ADT6
LINE A B C LOAD A
G G
Case Style
A
2.00
F
1.00
B C
1.18 x 0.56 Slot (2x)
E
2.0 Max. (6x) 0.69 Typ.
0.75 x 0.44 Slot (2x)
C
See Note
3/8-16 Thread (7x) Mounting Bracket
ADT6S
LINE A LOAD A
D (2x) K (2x)
0.75 (2x)
H
0.75 0.75
J
C L
C L
B
B
B
C
C
C L
C L
Line
Load
Case Dimensions
Part No. 63ADT6 63ADT6S 100ADT6 100ADT6S 160/200ADT6 160/200ADT6S A
B
C
D
E
F
G
H
J
K
102
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.
For email, phone or live chat, please go to te.com/help corcom.com
Corcom Product Guide
Catalog: 1654001 Issue Date: 06.2011
(continued)
High Performance High Current 3-phase Delta RFI Filters
ADT Series
Performance Data Typical Insertion Loss
Measured in closed 50 Ohm system
63ADT6
db 100 90 80 70 60 50 40 30 20 10 0
0.01 0.1 1 10 100 300 Frequency in MHz
100ADT6
db 100 90 80 70 60 50 40 30 20 10 0
0.01 0.1 1 10 100 300 Frequency in MHz
160ADT6
db 100 90 80 70 60 50 40 30 20 10 0
0.01 0.1 1 10 100 300 Frequency in MHz
200ADT6
db 100 90 80 70 60 50 40 30 20 10 0
0.01 0.1 1 10 100 300 Frequency in MHz
2
Three Phase Filters
63ADT6S
db 100 90 80 70 60 50 40 30 20 10 0
0.01 0.1 1 10 100 300 Frequency in MHz
100ADT6S
db 100 90 80 70 60 50 40 30 20 10 0
0.01 0.1 1 10 100 300 Frequency in MHz
160ADT6S
db 100 90 80 70 60 50 40 30 20 10 0
0.01 0.1 1 10 100 300 Frequency in MHz
200ADT6S
db 100 90 80 70 60 50 40 30 20 10 0
0.01 0.1 1 10 100 300 Frequency in MHz
Common Mode / Asymmetrical (L-G) Differential Mode / Symmetrical (L-L)
Minimum Insertion Loss
Measured in closed 50 Ohm system
Common Mode / Asymmetrical (Line to Ground)
Differential Mode / Symmetrical (Line to Line)
103
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.
For email, phone or live chat, please go to te.com/help corcom.com
很抱歉,暂时无法提供与“63ADT6_11”相匹配的价格&库存,您可以联系我们找货