Corcom Facility EMI Filters Product Guide
Catalog: 1654986 Issue Date: 06.2011
CDEUL Series - Extended Range Buffer Networks (Inductive Input)
CDEUL Series
Filter Cabinet
• Modified NEMA I, constructed of not less than #14 gauge CRS with galvanized bulkhead • Blue epoxy finish to all non-conductive surfaces • R.F. Radiation of the shielded (load) compartment greater than 100 dB from 14 kHz to 10 GHz • Front cover access, dual cover design • Filter inserts pre-wired to standoffs and lugs • Lifting hooks and mounting tabs • Legs for floor mount available (see page 24)
60 Hz Models Only
Individual Filters
• Sealed components with welded and/or soldered seams • Constructed of not less than #16 gauge steel with corrosion resistant plating • Bleeder resistor to eliminate shock hazard provided • HEMP Surge arrestors provided upon request‡
Electrical Characteristics
Voltage Drop:
Less than 1% @ unity power factor
Overload:
140% of rated current for 15 minutes
Harmonic Distortion:
Less than 2% @ full rated current
Dielectric Withstanding Voltage:
Per MIL-PRF-15733 and UL1283
D.C. Insulation Resistance:
Per MIL-STD-202, Method 302
Terminal Strength:
Per MIL-STD-202, Method 211, Condition E
Temperature Rise:
Per MIL-PRF-15733 and UL1283
Shown with optional legs Center mounting bracket not installed on all sizes
R.F. Radiation:
100 dB minimum shielding effectiveness
How to Order:
CDEUL 4 01000 A6 -S -L
Legs Surge Arrestors (optional) Voltage/Frequency
A6 - 120/208V, 60Hz B6 - 277/480V, 60Hz A4 - 120/208V, 400Hz
1
Insertion Loss:
100 dB from 14 kHz - 10 GHz per MIL-STD-220A, under load condition, using extended range buffer networks over the frequency range of 14 kHZ - 20 MHz
Applicable Publications:
MIL-PRF-15733 — Filters, radio interference MIL-STD-202 — Test methods for Components
Examples:
CDEUL401000A6-S-L =
Current Rating 2 # of Filtered Phases Series
MIL-STD-220A — Test method of Insertion Loss MIL-STD-188-125 — HEMP
MIL-STD-285 — Test method for Shielding Effectiveness NFPA 70-1987 — National Electric Code 486A - 1983 — Wire Connectors and Lug UL1283 — UL standard for EMI Filters
4, 1000A CDEUL, 120/280V filters in cabinet with surge arrestors and legs CDEUL300030B6 = 3, 30A CDEUL, 277/480V filters in cabinet
Note 1:
Surge Arrestor for A6/A4* Models: V251BA60 Surge Arrestor for B6 Models: V481BA60 Current configuration listed as 5 digits with leading zeros
Note 2:
‡ Intended for HEMP applications 225A refer to the new TECUL Series on page 14.
12
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.
USA Cust. Svc.: Corcom Prods:
1-800-468-2023 1-847-680-7400
te.com corcom.com
Corcom Facility EMI Filters Product Guide CDEUL Series - ERBN (Inductive Input) (continued)
Mounting Brackets E A C
Catalog: 1654986 Issue Date: 06.2011
Removable Cover
RF Gasket
2
Removable Individual Phase Filters D B
Corcom Facility EMI Filters — NEMA Cabinet Style
Center mounting bracket not installed on all sizes
Removable Cover
Area for Conduit Penetration
For optional legs, refer to page 24
Recommended torque for fasteners on removable cover: 25 in. lb. ± 3 in. lb. # Filtered phases @ rated current 2 @ 10A 3 @ 10A 4 @ 10A 2 @ 30A 3 @ 30A 4 @ 30A 2 @ 60 or 100A 3 @ 60 or 100A 4 @ 60 or 100A 2 @ 150A 3 @ 150A 4 @ 150A Dimensions B C D 30.0 6.0 22.0 762.0 152.4 558.8 30.0 6.0 22.0 762.0 152.4 558.8 30.0 6.0 22.0 762.0 152.4 558.8 38.0 8.0 26.0 965.2 203.2 660.4 38.0 8.0 26.0 965.2 203.2 660.4 38.0 8.0 26.0 965.2 203.2 660.4 44.0 10.0 32.0 1117.6 254.0 812.8 44.0 10.0 32.0 1117.6 254.0 812.8 44.0 10.0 32.0 1117.6 254.0 812.8 54.0 14.0 42.0 1371.6 355.6 1066.8 54.0 14.0 42.0 1371.6 355.6 1066.8 54.0 14.0 42.0 1371.6 355.6 1066.8 Weight E ( Pounds/KG) 16.0 95 406.4 43.1 22.0 100 558.8 45.4 28.0 1 20 711.2 54.4 18.0 170 457.2 77.1 25.0 240 635.0 108.9 32.0 300 812.8 136.1 18.0 240 457.2 108.9 25.0 310 635.0 140.6 32.0 400 812.8 181.4 18.0 320 457.2 145.1 25.0 430 635.0 195.0 32.0 65 0 812.8 294.8 # Filtered phases @ rated current Dimensions B C D 54.0 14.0 42.0 1371.6 355.6 1066.8 54.0 14.0 42.0 1371.6 355.6 1066.8 54.0 14.0 42.0 1371.6 355.5 1066.8 64.0 26.0 61.5 1625.6 660.4 1562.1 64.0 26.0 61.5 1625.6 660.4 1562.1 64.0 26.0 61.5 1625.6 660.4 1562.1 70.0 26.0 67.5 1778.0 660.4 1714.5 70.0 26.0 67.5 1778.0 660.4 1714.5 70.0 26.0 67.5 1778.0 660.4 1714.5 70.0 26.0 67.5 1778.0 660.4 1714.5 70.0 26.0 67.5 1778.0 660.4 1714.5 70.0 26.0 67.5 1778.0 660.4 1714.5 Weight E (Pounds/KG) 18.0 380 457.2 172.4 25.0 520 635.0 235.9 32.0 700 812.8 317.5 24.0 800 609.6 362.9 32.0 1100 812.8 498.9 40.0 1400 1016.0 635.0 40.0 1400 1016.0 635.0 5 8.0 2100 1473.2 952.5 74.0 2600 1879.6 1179.3 5 8.0 2000 1473.2 907.2 84.0 3000 2133.6 1360.8 108.0 3800 2743.2 1723.6
A 14.0 355.6 20.0 508.0 26.0 660.4 16.0 406.4 23.0 584.2 30.0 762.0 16.0 406.4 23.0 584.2 30.0 762.0 16.0 406.4 23.0 584.2 30.0 762.0
A 16.0 2 @ 225A 406.4 23.0 3 @ 225A 584.2 30.0 4 @ 225A 762.0 22.0 2 @ 400A 558.8 30.0 3 @ 400A 762.0 38.0 4 @ 400A 965.2 38.0 2 @ 800A 965.2 5 6.0 3 @ 800A 1422.4 72.0 4 @ 800A 1828.8 5 6.0 2 @ 1000 or 1200A 1422.4 82.0 3 @ 1000 or 1200A 2082.8 106.0 4 @ 1000 or 1200A 2692.4
Max. Operating Voltage A6: 120/208V, 60 Hz B6: 277/480V, 60 Hz A4*: 120/208V, 400 Hz
*400Hz filters available upon request. Will require external power factor correction coil. Please contact TE Connectivity Application Engineering 847-573-6517.