60W Single Output with Battery Charger (UPS Function)
www.tuv.com
ID 2000000000
UL62368-1
‧
‧
‧
‧
‧
‧
‧
series
Bauar t gepruft
Sicherheit
egel ma ge
od
o s
be wac
g
LPS
■
‧
‧
‧
DRC-60
BS EN/EN62368-1
IEC62368-1
TPTC004
■
‧
‧
‧
‧
•
‧
■
■
℃℃
■
File Name:DRC-60-SPEC 2022-09-20
DRC-60
60W Single Output with Battery Charger (UPS Function)
series
SPECIFICATION
MODEL
OUTPUT
DRC-60A
DRC-60B
OUTPUT NUMBER
CH1
CH2
CH1
CH2
DC VOLTAGE
13.8V
13.8V
27.6V
27.6V
RATED CURRENT
2.8A
1.5A
1.4A
0.75A
CURRENT RANGE
0 ~ 4.3A
--------
0 ~ 2.15A
--------
RATED POWER
59.34W
59.34W
RIPPLE & NOISE (max.) Note.2 120mVp-p
VOLTAGE ADJ. RANGE
--------
VOLTAGE TOLERANCE Note.3 ±1.0%
--------
±1.0%
--------
LINE REGULATION
±0.5%
--------
±0.5%
--------
LOAD REGULATION
±0.5%
--------
±0.5%
--------
HOLD UP TIME (Typ.)
50ms/230VAC
VOLTAGE RANGE
90 ~ 264VAC
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
86%
AC CURRENT (Typ.)
1.3A/115VAC
INRUSH CURRENT (Typ.)
OVERLOAD
PROTECTION
FUNCTION
--------
CH1:24 ~ 30V
SETUP, RISE TIME Note.4 400ms, 50ms/230VAC
INPUT
200mVp-p
CH1:12 ~ 15V
OVER VOLTAGE
800ms, 50ms/115VAC at full load
10ms/115VAC at full load
127 ~ 370VDC
[DC input operation possible by connecting AC/L(+), AC/N(-)]
88%
0.8A/230VAC
COLD START 30A/115VAC
60A/230VAC
105 ~ 150% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
CH1:14.49 ~ 18.63V
CH1:28.98 ~ 37.26V
Protection type : Shut down o/p voltage, re-power on to recover
BATTERY CUT OFF
10±0.5V
AC OK
Relay contact output, ON : AC OK ; OFF : AC Fail ; max. rating : 30V/1A
BATTERY LOW
20±1V
Relay contact output, OFF : Battery OK ; ON : Battery Low ; max. rating : 30V/1A
Battery low voltage : < 11V
WORKING TEMP.
-30 ~ +70℃ (Refer to "Derating Curve")
WORKING HUMIDITY
20 ~ 90% RH non-condensing
Battery low voltage : < 22V
ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT
±0.03%/℃ (0 ~ 50℃) on CH1 output
VIBRATION
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY STANDARDS
UL62368-1, TUV BS EN/EN62368-1, EAC TP TC 004, AS/NZS 60950.1 approved
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
SAFETY & WITHSTAND VOLTAGE
EMC
ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
(Note 5)
EMC EMISSION
Compliance to BS EN/EN55032 (CISPR32) Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020
EMC IMMUNITY
Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN61204-3, light industry level,
EAC TP TC 020
MTBF
1854.1K hrs min.
OTHERS DIMENSION
PACKING
NOTE
Telcordia SR-332 (Bellcore) ; 504.1K hrs min.
MIL-HDBK-217F (25℃)
40*90*100mm (W*H*D)
0.3Kg; 42pcs/13.6Kg/0.82CUFT
℃
℃℃
※:https://www.meanwell.com/serviceDisclaimer.aspx
File Name:DRC-60-SPEC 2022-09-20
DRC-60
60W Single Output with Battery Charger (UPS Function)
series
Block Diagram
RL1
AC OK
RL2
Bat. Low
ALARM
CIRCUIT
EMI FILTER
&
RECTIFIER
I/P
POWER
SWITCHING
RECTIFIERS
&
FILTER
-V
Bat. +
DETECTION
CIRCUIT
PWM
CONTROL
O.L.P.
+V
Bat. Battery Charger
&
Back up Control
O.V.P.
Derating Curve
Static Characteristics
100
100
90
80
80
230VAC
Input only
70
LOAD (%)
LOAD (%)
60
40
20
-30
-20
0
15
30
40
50
AMBIENT TEMPERATURE (℃)
60
70 (VERTICAL)
60
50
40
90
100
125
135
145
155 165
175
180
200
230
264
INPUT VOLTAGE (V) 60Hz
File Name:DRC-60-SPEC 2022-09-20
DRC-60
60W Single Output with Battery Charger (UPS Function)
series
Suggested Application
1.Backup connection for AC interruption
(1) Please refer to Fig1.1 for suggested connection.
The power supply charges the battery and provides energy to the load at the same time when AC mains is OK.
The battery starts to supply power to the load when AC mains fails.
A : 12V
B : 24V
Battery
+
Bat+
Load
-
-
+
Bat-
V+
V-
DC OK
+
+V ADJ
Fig 1.1 Suggested system connection
2.Alarm signal for AC OK and battery low
(1) Alarm Signal is sent out through " AC OK " & " Battery Low " pins via relay contact.
(2) An external voltage source is required for this function. The maximum applied voltage is 30V and the maximum sink current is 1A. Please refer to Fig 2.2.
(3) Table2.1 explains the alarm function built in the power supply
(4) AC OK signal (RL1,referring to Block Diagram) will go into hiccup mode when the overload protecton is activated.
Function
Output of alarm
Description
The signal is "Low" when the power supply turns ON.
Low or short
The signal turns to be "High" when the power supply turns OFF.
High or open (External applied voltage 30V max.)
The signal is "Low" when the voltage of battery is under A:11V, B:22V.
Low or short
The signal is "High" when the voltage of battery is above A:11V, B:22V.
High or open (External applied voltage 30V max.)
AC OK
Battery Low
Table 2.1 Explanation of alarm signal
AC OK (Battery low)
R
V
External voltage sorece (V) and resistor (R)
(The max. Sink is 1A and 30V)
Fig 2.2 Internal circuit of AC OK (Battery Low), via relay contact
File Name:DRC-60-SPEC 2022-09-20
DRC-60
60W Single Output with Battery Charger (UPS Function)
Mechanical Specification
Case No.962A
series
Unit:mm
40
100
3.81×7
8 7 6 5 4 3 2 1
TB2
DC OK
90
+
+V ADJ
3
TB1
2 1
7.5 7.5
Terminal Pin No. Assignment (TB1):
Pin No.
1
2
3
Assignment
AC/L or DC+
AC/N or DCFG
Terminal Pin No. Assignment (TB2):
Pin No.
1
2
3
Assignment
-V
+V
Bat. +
Pin No.
4
5,6
7,8
Assignment
Bat. AC OK
Bat. Low
Installation Instruction
35
This series fits DIN rail TS35/7.5 or TS35/15.
For installation details, please refer to the Instruction manual.
ADMISSIBLE DIN rail:TS35/7.5 OR TS35/15
(For reference only. Not included with unit.)
Back View
Installation Manual
Please refer to : http://www.meanwell.com/manual.html
File Name:DRC-60-SPEC 2022-09-20