230W Single Output Battery Charger
Features :
3 stage charging characteristic Universal AC input / Full range
PB-230
Built-in active PFC function, PF>0.95
series
Protection: Short circuit / Overload / Over voltage / Over temperature Built-in cooling Fan ON-OFF control Built-in remote ON-OFF control 2 color LED loading indicator Low cost, high reliability 2 years warranty
( for PB-230-xxAD1 only)
TUV Rheinland Product Safety
geprUfre Sicherheit
ORDER NO. PB-230-xx (standard model) PB-230-xxAD1 (optional model) PB-230-xx
MODEL BOOST CHARGE VOLTAGE FLOAT CHARGE VOLTAGE OUTPUT RECOMMENDED BATTERY CAPACITY(AMP HOURS)(Note 5) BATTERY TYPE OUTPUT CURRENT VOLTAGE RANGE FREQUENCY RANGE POWER FACTOR (Typ.) INPUT EFFICIENCY (Typ.) AC CURRENT (Typ.) INRUSH CURRENT (Typ.) LEAKAGE CURRENT OVERLOAD PROTECTION OVER VOLTAGE OVER TEMPERATURE
OUTPUT CONNECTOR 4pin power din Anderson connector =Blank, AD1
PB-230-12 14.4V 13.6V 50 ~ 160Ah Open & Sealed Lead Acid 16A 90 ~ 264VAC 47 ~ 63Hz PF>0.95/230VAC 81.5% 3A/115VAC 1.5A/230VAC COLD START 50A 0.98/115VAC at full load 85.5% 127 ~ 370VDC 8A PB-230-24 28.8V 27.2V 24 ~ 80Ah
SAFETY TUV / CE UL
xx=12,24,48 ;
SPECIFICATION
PB-230-48 57.6V 54.4V 12 ~ 40Ah
4A
86%
90 ~ 110% rated output current Protection type : Constant current limiting, recovers automatically after fault condition is removed 16 ~ 18V 31 ~ 35V Protection type : Shut down o/p voltage, re-power on to recover Protection type : Automatically derate charge current until zero Short: Stop Charging 45 Fan OFF (Typ.) 59 ~ 64V
REMOTE CONTROL (CN105) Open: Normal work FUNCTION FAN CONTROL RTH3 50 Fan ON, By NTC TEMPERATURE SENSE WORKING TEMP. -20 ~ +50
(Refer to "Derating Curve")
20 ~ 90% RH non-condensing WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85 , 10 ~ 95% RH TEMP. COEFFICIENT 0.03%/ (0 ~ 50 VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes UL1012(for PB-230-xxAD1 only), TUV EN60950-1 approved SAFETY STANDARDS SAFETY & WITHSTAND VOLTAGE ISOLATION RESISTANCE EMC (Note 4) EMC EMISSION EMC IMMUNITY OTHERS MTBF DIMENSION PACKING PLUG CABLE I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3 Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, light industry level, criteria A 244.5Khrs min. MIL-HDBK-217F (25 ) 190*96*49mm(L*W*H) 1.21Kg; 12pcs/15.5Kg/1.29CUFT See page 2 ; Other type available by customer requested See page 2 ; Other type available by customer requested
CONNECTOR
NOTE
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. This is Mean Well's suggested range. Please consult your battery manufacturer for their suggestions about maximum charging current limitation.
File Name:PB-230-SPEC 2011-08-18
230W Single Output Battery Charger
Mechanical Specification
115cm 5cm 3 4
PB-230
Case No.PB-230A
2 1
series
Unit:mm
AD1 (optional)
CN105 12
35 2mm
96
49
Plug Assignment
DC output connector (standard)
UNICABLE 89M103-4P or equivalent
3 4 2 1
Block Diagram
FAN ON/OFF CONTROL EMI FILTER & RECTIFIERS PFC CIRCUIT POWER SWITCHING RECTIFIERS & FILTER DETECTION CIRCUIT O.T.P. O.V.P.
REMOTE CONTROL
FG O.L.P.
Charging Curve
FUSE
Air flow direction
Remote Control (CN105) : JST B2B-XH or equivalent
Pin No. 1 2
190
Assignment RCRC+
Mating Housing JST XHP or equivalent
Terminal JST SXH-001T-P0.6 or equivalent
DC output connector (optional)
AD1 [ housing: Anderson 1327FP(red), 1327G6FP(black) contacts: Anderson 261G2 (45A) or equivalent ] Red(+V) Black(-V)
PIN NO. OUTPUT 1,2 3,4 +V -V
FAN
fosc : 90KHz
I/P
+V -V
PWM & PFC CONTROL
Derating Curve
Start
V boost V FLT
100 90 80
Charge Voltage
100%
70
LOAD (%)
Charge Current
Constant Current Constant Voltage stage 1 stage 2 stage 3
10%
60 40 30
Color of LED
Red
Green
-20
10
20
30
40 45 50
60
70
(HORIZONTAL)
AMBIENT TEMPERATURE ( )
State V boost V FLT PB-230-12 14.4V 13.6V PB-230-24 28.8V 27.2V PB-230-48 57.6V 54.4V
File Name:PB-230-SPEC 2011-08-18
很抱歉,暂时无法提供与“PB-230-24”相匹配的价格&库存,您可以联系我们找货