1600~8000W 1U Distributed Power/Charger System
RHP-1U Rack System
Rack Dimension
* W * H
L
365 * 440 * 44 (1U)
14.4 * 17.3 * 1.73 (1U)
mm
inch
Bauar t gepruft
Sicherheit
egel ma ge
od
o s
be wac
g
www. tuv.com
ID 2000000000
■ Features
Universal AC input / Full range
1U profile 19 rack shelf, fitting five 1600W modules
up to 8000W with active current sharing
Output voltage and current programmable
Support hot swap (hot plug)
Built-in PMBus protocol
(Optional CANBus protocol)
■ Applications
Distributed power architecture system
Wireless/telecommunication solution
Electric vehicle or marine charger station
DC UPS or emergency backup
Wastewater treatment system
Electrolysis system
5 years warranty
■ Description
RHP-1U rack power system and RHB-1U rack charger system are the complete solution for the power
distribution utilizing the rack configuration with the 1U low profile. Starting with a single unit of 1600W,
RCP-1600 is the front end rectifier (or, power supply) and RCB-1600 is the charger module. With the active
current sharing function, up to 8000W is able to be provided by 1 stack of the 19 ” rack mountable shelf
RHP-1U, with either rectifier or charger, and 24000W by 3 stacks with rectifier.
■ Model Encoding
Rack Shelf:
RHP-1U I -A
Whole System:
RHP-8K1U I -12
Communication protocol option
Rack Shelf for 1600W unit
I: AC Inlet (IEC320-C14)
T: Terminal block
Profile of the system
Series name
Communication protocol option
Output voltage
I: AC Inlet (IEC320-C14)
T: Terminal block
8K: Maximum wattage with
fully-populated shelf
1U: Profile of the system
Series name
Type
Blank
CAN
Communication Protocol
PMBus protocol
CANBus protocol
Note
In Stock
By request
(RHP : Power supply system;
RHB : Charger system)
File Name:RHP-1U RACK SYSTEM-SPEC 2017- 09-12
RHP-1U Rack System
1600~8000W 1U Distributed Power/Charger System
SPECIFICATION - Power Supply System
MODEL
OUTPUT
RHP-8K1U
-12
RHP-8K1U
RECTIFIER
RCP-1600-12
RACK SHELF
RHP-1UI-A or RHP-1UT-A
OUTPUT VOLTAGE
MAX. OUTPUT CURRENT
RHP-8K1U
RCP-1600-24
RCP-1600-48
12V
24V
48V
625A
335A
167.5A
8040W
8040W
MAX. OUTPUT POWER Note.5 7500W
VOLTAGE RANGE
-24
Note.6 90 ~ 264VAC
-48
127 ~ 370VDC
FREQUENCY RANGE
INPUT
47 ~ 63Hz
AC CURRENT (Typ.) per RECTIFIER 14A/115VAC
LEAKAGE CURRENT per RECTIFIER
8A/230VAC
15A/115VAC
8.5A/230VAC
15A/115VAC
8.5A/230VAC
95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods
(Note 4)
EMC IMMUNITY
OTHERS
NOTE
DIMENSION
PACKING
Rack 365*482.6*44(L*W*H, with mounting bracket) ; 365*440*44(L*W*H, without mounting bracket)
5.5Kg; 3pcs/17.5Kg/2.11CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. Under parallel
operation of more than one rack connecting together, ripple of the output voltage may be higher than the SPEC at light load condition. It will go back to
normal ripple level once the output load is more than 5%.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a 1000mm*1300mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how
to perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
5. Output of all the RCP-1600 modules are connected in parallel in the rack.
6. Derating may be needed under low input voltages. Please check the static characteristics for more details.
7. Because of component tolerance, there is a possibility that some of units connected in parallel will reach an overcurrent limit then overloading the other
units when operating at full load condition. If overload conditions happen in parallel usage, it is suggested that derate the total output current by 10%.
8. The equivalent leakage current of the system is determined by the quantity of populated rectifiers.
9. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
File Name:RHP-1U RACK SYSTEM-SPEC 2017- 09-12
RHP-1U Rack System
1600~8000W 1U Distributed Power/Charger System
SPECIFICATION - Charger System
MODEL
OUTPUT
RHB-8K1U
-12
CHARGER
RCB-1600-12
RACK SHELF
RHP-1UI-A or RHP-1UT-A
-24
RHB-8K1U
RCB-1600-24
RCB-1600-48
BOOST CHARGE VOLTAGE(Vboost)(default) 14.4V
28.8V
57.6V
13.8V
0 ~ 500A
90 ~ 264VAC
47 ~ 63Hz
AC CURRENT (Typ.) per CHARGER 14A/115VAC
27.6V
0 ~ 275A
55.2V
0 ~137.5A
FLOAT CHARGE VOLTAGE(Vfloat)(default)
CURRENT RANGE
Note.2
VOLTAGE RANGE
FREQUENCY RANGE
INPUT
RHB-8K1U
LEAKAGE CURRENT per CHARGER
-48
127 ~ 370VDC
8A/230VAC
15A/115VAC
8.5A/230VAC
15A/115VAC
8.5A/230VAC