240W Single Output Industrial DIN RAIL with PFC Function
Features :
SDR-240 series
High efficiency 94% and low power dissipation 150% peak load capability Built-in active PFC function, PF>0.93 Protections: Short circuit / Overload / Over voltage / Over temperature Cooling by free air convection Can be installed on DIN rail TS-35/7.5 or 15 UL 508 (industrial control equipment) approved EN61000-6-2(EN50082-2) industrial immunity level Built-in DC OK relay contact 100% full load burn-in test 3 years warranty
SE
PQ
M
IF
47
GL
SPECIFICATION
MODEL DC VOLTAGE RATED CURRENT CURRENT RANGE RATED POWER PEAK CURRENT PEAK POWER Note.6 OUTPUT VOLTAGE ADJ. RANGE LINE REGULATION LOAD REGULATION SETUP, RISE TIME HOLD UP TIME (Typ.) VOLTAGE RANGE FREQUENCY RANGE POWER FACTOR (Typ.) INPUT EFFICIENCY (Typ.) AC CURRENT (Typ.) INRUSH CURRENT (Typ.) LEAKAGE CURRENT OVERLOAD PROTECTION OVER VOLTAGE OVER TEMPERATURE SDR-240-24 24V 10A 0 ~ 10A 240W 15A 360W (3sec.) 120mVp-p 48 ~ 55V 1.0% 0.5% 1.0% 3000ms, 60ms/115VAC at full load 20ms/115VAC at full load 124 ~ 370VDC 0.99/115VAC at full load 1.3A/230VAC 65A/230VAC SDR-240-48 48V 5A 0 ~ 5A 240W 7.5A
RIPPLE & NOISE (max.) Note.2 100mVp-p 24 ~ 28V VOLTAGE TOLERANCE Note.3 1.0% 0.5% 1.0% 1500ms, 60ms/230VAC 20ms/230VAC 88 ~ 264VAC 47 ~ 63Hz 0.93/230VAC
Note.8 94%
2.6A/115VAC 33A/115VAC 150% rated power, constant current limiting with auto-recovery within 2 seconds and may cause to shut down if over 2 seconds 56 ~ 65V 29 ~ 33V Protection type : Shut down o/p voltage with auto-recovery 95 5 (TSW : detect on heatsink of power switch) Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
FUNCTION DC OK REALY CONTACT RATINGS (max.) 60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load WORKING TEMP. Note.5 -25 ~ +70 (Refer to "Derating Curve") 20 ~ 95% RH non-condensing WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION SAFETY STANDARDS WITHSTAND VOLTAGE SAFETY & ISOLATION RESISTANCE EMC EMC EMISSION
(Note 4)
-40 ~ +85
, 10 ~ 95% RH
0.03%/ (0 ~ 50 Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 UL508, TUV EN60950-1 approved I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 / 70% RH Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3 Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A, SEMI F47, GL approved 169.3Khrs min. MIL-HDBK-217F (25 ) 63*125.2*113.5mm (W*H*D) 1.03Kg; 12pcs/13.4Kg/1.06CUFT
EMC IMMUNITY MTBF OTHERS
NOTE
DIMENSION PACKING
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended. 6. 3 seconds max., please refer to peak loading curves. 7. Derating may be needed under low input voltage. Please check the derating curve for more details. 8. After 30 minutes of burn-in.
File Name:SDR-240-SPEC 2011-08-23
240W Single Output Industrial DIN RAIL with PFC Function
Mechanical Specification
SDR-240 series
Case No. 979A Unit:mm
125.2
TB1
DC OK
TB2 1 2 3 4 5 6
1
63
2
DC OK
3
113.5
+V ADJ.
+
Terminal Pin No. Assignment (TB1)
Pin No. 1 2 3 Assignment FG AC/N AC/L
35
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
Terminal Pin No. Assignment (TB2)
Pin No. 1,2 3,4 5,6 Assignment Relay Contact DC OUTPUT +V DC OUTPUT -V
Block Diagram
DC OK
I/P
EMI FILTER & RECTIFIERS
PFC CIRCUIT
POWER SWITCHING
RECTIFIERS & FILTER O.C.P.
+V -V
U.V.P. FG PFC CONTROL
O.L.P. PWM & PFC CONTROL DETECTION CIRCUIT O.V.P.
DC OK Relay Contact
Contact Close Contact Open PSU turns on / DC OK. PSU turns off / DC Fail.
Contact Ratings (max.) 30V/1A resistive load.
File Name:SDR-240-SPEC 2011-08-23
240W Single Output Industrial DIN RAIL with PFC Function
Peak Loading
(1) 360W (2) 3 60W
SDR-240 series
240W 100 sec. 3 sec.
120W 10 sec. 3 sec.
Derating Curve
Output derating VS input voltage
150
100 90
112.5
For 3 sec. (typ.)
80 70
100
LOAD (%)
LOAD (%)
40 50 60 70 (VERTICAL)
75
Continuous
60 50 40
60
-25
0
10
20
30
88
100
110
135
155
230
264
AMBIENT TEMPERATURE ( )
INPUT VOLTAGE (V) 60Hz
File Name:SDR-240-SPEC 2011-08-23