D2U5T-H3-5000-380-HU3C 数据手册
D2U5T-H3-5000-380-HU3C
AC-DC Three Phase Power Converter
PRODUCT OVERVIEW
The D2U5T-H3-5000-380-HU3C is a High Efficiency 3500/5000 watt, power factor corrected three phase
power supply for 230/480Vac lines with a 380V high voltage (HVDC) main output and a selectable 5V or
3.3V (20W) standby. The unit is provided with Droop Sharing and up to three (3) power modules may be
operated in parallel.
The power module is hot pluggable. The module is able to protect and recover from over temperature
faults, and has status LEDs on the front panel and additional logic and PMBus status signals.
Their 2U package and >16.5W/cubic inch power density make them ideal for delivering reliable,
efficient power to servers, workstations, storage systems and other 380V HVDC distributed power
systems. An optional power shelf is also available that accommodates up to three (3) power modules.
ORDERING GUIDE
FEATURES
5KW (480Vac), 3.5KW (230Vac) Output
Power
Very High Efficiency; 95.4% @ 50% FL
380V High Voltage Main Output
3.3V or 5V Standby Output
Nominal Dim’s: 5.1"(W) x 18"(L) x 3.3" (2U
16.5 watts/cubic inch power density
N+1 redundant (including hot docking)
Droop sharing on Main Output
Over-voltage, over-current, overtemperature protections
Internal cooling fan
I2C Bus Interface with status indicators
Optional 19" power shelf
RoHS compliant
Two-year warranty
Model Number
Power
Main Output
D2U5T-H3-5000-380-HU3C
5000W
380V
INPUT CHARACTERISTICS
Parameter
Input Frequency
Input Voltage Operating Range
Turn-on Voltage (Ramp-up)
Turn-off Voltage (Ramp-down)
Maximum Input Current
Inrush Current
Power Factor, Range 1, 60Hz
Power Factor, Range 2, 60Hz
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
Available now at:
www.murata-ps.com/en/3d/acdc.html
For full details go to
www.murata-ps.com/rohs
Standby Output
3.3V or 5V
(Selectable)
Conditions
Range 1
Range 2
Range 1
Range 2
Range 1
Range 2
Cold Start
600W, 230 Vac
1750W (50%), 230 Vac
3500W (100%), 230 Vac
600W, 480 Vac
2500W (50%), 480 Vac
5000W (100%), 480 Vac
Min
47
180
320
Airflow
Front to Back
Typ
50/60
Max
63
264
528
170
280
150
260
13
30
Units
Hz
Vac
Vac
Vac
Vac
Vac
Vac
Arms
Apk
0.992
0.998
0.998
0.910
0.995
0.995
OVERALL CHARACTERISTICS
Parameter
Conditions
Min
Typ
Max
Units
Range 1
3500
Output Power
W
Range 2
5000
700W (20%), 230Vac
89.5
Efficiency, Range 1
1750W (50%), 230Vac
93.6
3500W (100%), 230Vac
94.2
%
500W (20%), 230Vac
92.6
Efficiency, Range 2
2500W (50%), 230Vac
95.4
5000W (100%), 230Vac
95.4
The following curves represent the achieved efficiency performance for the D2U5T-H3-5000-380-HU3C
product compared against a recognized industry standard for efficiency rating.
The D2U5T-H3-5000-380-HU3C offers performance in excess of the industry standard limit as a required
percentage of loading.
Test methodology as per Ecova Generalized Test Protocol for Calculating the Energy Efficiency of Internal
AC-DC and DC-DC Power Supplies Revision 6.7
Test Certificate
and Test Report
www.murata-ps.com/support
D2U5T-H3-5000-380-HU3C.A04 Page 1 of 8
D2U5T-H3-5000-380-HU3C
AC-DC Three Phase Power Converter
EFFICIENCY PERFORMANCE CURVES
OUTPUT VOLTAGE CHARACTERISTICS
Output
Parameter
380V
Output Current
Voltage Set Point
Voltage Droop
3.3VSB
5VSB
Line Regulation
Ripple Voltage & Noise1
Load Capacitance
Voltage Set Point
Line and Load Regulation
Ripple Voltage & Noise2
Output Current
Load Capacitance
Voltage Set Point
Line and Load Regulation
Ripple Voltage & Noise2
Output Current
Load Capacitance
Min
0
0
Conditions
Range 1
Range 2
@4.6A Range 1
@6.67A Range 2
Min to Max Current, Range 1
Min to Max Current, Range 2
Typ
Max
9.2
13.34
380
380
7
11
0.1
1
100
Vdc
1000
3.3
3.14
3.46
75
6
1000
20MHz Bandwidth
0
20
5
4.76
20MHz Bandwidth
0
20
Units
Adc
5.24
100
4
1000
%
Vp-p
μF
Vdc
mVp-p
A
μF
Vdc
mVp-p
A
μF
1
Ripple and noise are measured with
22nF (U2J 630V) ceramic + 15 μF (UCC
KXJ) of electrolytic de-coupling
capacitors at the output connector load
side. A short coaxial cable with 50ohm
scope termination is used.
2
Ripple and noise are measured with
0.1 uF of ceramic capacitance and 10
uF of tantalum capacitance across the
power supply outputs at the output
connector load side. A short coaxial
cable with 50ohm scope termination is
used.
www.murata-ps.com/support
D2U5T-H3-5000-380-HU3C.A04 Page 2 of 8
D2U5T-H3-5000-380-HU3C
AC-DC Three Phase Power Converter
OUTPUT CHARACTERISTICS
Parameter
Startup Time
Transient Response
Current sharing accuracy (up to 3 in parallel)
Hot Swap Transients
Holdup Time
GENERAL CHARACTERISTICS
Parameter
Storage Temperature Range
Operating Temperature Range
Operating Humidity
Storage Humidity
Altitude
Shock
Sinusoidal Vibration
MTBF
Weight
Safety Approvals
Input Fuses
Material Flammability
PROTECTION CHARACTERISTICS
Output Parameter
Over-temperature (intake)
Over Voltage
Over Current Range 1
380V
Over Current Range 2
Over Voltage
3.3VSB
Over Current
Over Voltage
5VSB
Over Current
Conditions
AC ramp up
380V, 50-100% load step, 0.1A/μs di/dt
5VSB, 50-100% load step, 1A/μs di/dt
3.3VSB, 50-100% load step, 1A/μs di/dt
380V @100% load
All outputs within regulation
380V @100% load
VSB @100% Load
Conditions
Non-condensing
Non-condensing
(Without derating at 40°C)
(Without derating at 50°C)
30G non-operating
0.5G, 5 – 500 Hz
Calculated per Telcordia SR-332 @40°C
Min
Typ
Max
3
15
250
165
+/-10
25
500
Min
-40
-15
10
5
Units
s
Vp-p
mVp-p
mVp-p
%
ms
Typ
Max
70
50
90
90
3000
1800
Units
°C
°C
%
%
m
hrs
kg
220K
7
CAN/CSA C22.2 No 60950-1-07, Am.1:2011, Am 2:2014
ANSI/UL 60950-1-2014
IEC60950-1:2005 (2nd Ed.), Am 1:2009 + Am 2:2013
EN 60950-1:2006+A11:2009 +A1:2010 +A12:2011 +A2:2013
Power Supply has one internal 16A/500V fast blow fuse on each of the three AC line inputs.
UL 94V0
Conditions
Auto-restart
Latching
Hiccup or Latching
Hiccup or Latching
Latching
Hiccup
Latching
Hiccup
Min
57
418
105
105
3.9
6.3
5.6
4.2
Typ
60
Max
63
445
130
130
4.3
9
6.0
6
Units
°C
V
%
%
V
A
V
A
www.murata-ps.com/support
D2U5T-H3-5000-380-HU3C.A04 Page 3 of 8
D2U5T-H3-5000-380-HU3C
AC-DC Three Phase Power Converter
EMISSIONS AND IMMUNITY
Characteristic
Input Current Harmonics
Conducted Emissions
Radiated Emissions (in the application)
ESD Immunity
Radiated Field Immunity
Electrical Fast Transients/Burst Immunity
Surge Immunity
RF Conducted Immunity
Magnetic Field Immunity
Standard
IEC/EN 61000-3-2
FCC 47 CFR Parts 15
CISPR 22 EN55022
IEC/EN 61000-4-2
IEC/EN 61000-4-3
IEC/EN 61000-4-4
IEC/EN 61000-4-5
IEC/EN 61000-4-6
IEC/EN 61000-4-8
Voltage Dips & Interruptions
IEC/EN 61000-4-11
Voltage imbalance
(Circuit will stop when input voltage imbalance exceeds
8% for more than 100ms. Unit will restart when
imbalance returns below 8%)
ISOLATION CHARACTERISTICS
Parameter
Insulation Safety Rating/Test Voltage
Conditions
Input to Output – Reinforced
Input to Chassis – Basic
Output to Chassis – Basic
Compliance
Complies
Class A, 6dB margin
Class A, 6dB margin
Level 3 criteria A
Level 3 criteria B
Level 3 criteria A
Level 3 criteria A
Level 3 criteria A
3 A/m criteria B
400Vrms Input Voltage
Main & VSB Outputs, Performance a)
100% load, Phase 0°, Dip 100% Duration 10ms
50% load, Phase 0°, Dip 100% Duration 20ms
Main & VSB Outputs, Performance b)
100% load, Phase 0°, Dip 100% Duration >10ms
Any Load, Phase 0°, Dip 100% Duration >100ms
Any valid Input Voltage, any load
Main & VSB Outputs, Performance a)
Dip 30% on single Phase or Line, Duration 100ms
Main & VSB Outputs, Performance b)
Dip 30% on single Phase or Line, Duration >100ms
Min
3000
1500
1150
Typ
Max
Units
Vrms
Vrms
Vrms
www.murata-ps.com/support
D2U5T-H3-5000-380-HU3C.A04 Page 4 of 8
D2U5T-H3-5000-380-HU3C
AC-DC Three Phase Power Converter
STATUS INDICATORS (LEDs)
Status Indicators
AC input voltage is not present
AC present and within the required operational range
Standby – ON; Main Output – OFF (disabled)
Input OK (Green)
Output OK (Green)
Fault4 (Yellow)
Off
Off
Off
Solid Green
Blinking
Off
Blinking Green at 1Hz
rate
Off
(0.5s on, 0.5s off)
AC present, but its level is not within the required operational range
Off
Blinking Green at 1Hz
rate
Off
(0.5s on, 0.5s off)
When hot-unplugging the power supply from a power shelf
3
AC present and within the required operational range
Standby – ON and within the specified regulation range
Main Output – ON and within the specified regulation range
Solid Green
Off
Solid Green
Off
AC present and within the required operational range
Standby – ON and within the specified regulation range
Main Output – ON and within the specified regulation range
Main output overcurrent condition are indicated depending upon severity and application of
overload and specific detection mechanism responding:
Solid Green
Solid Green
Solid Green
Output power warning
Pout overpower fault
Iout overcurrent fault
Solid Green
Blinking 1Hz
Solid Green
On
Blinking Green
On
Any warning Levels (Input UV/OV, OC, Inlet Temp, Output and STBY OV/UV, OC, OTP, FAN) No Change
No Change
Blinking 1Hz
Depends on PS
Any Fault Levels (Input UV/OV, OC, Inlet Temp, Output and STBY OV/UV, OC, OTP, FAN)
Depends on PS Status Depends on PS Status
3
The Input OK LED blinks to indicate that there is still energy inside the power supply until the input bulk capacitors are completely discharged or the
housekeeping circuit is shut down.
4
The Fault LED and PS Fault signal shall be turned on to indicate that there is one or more of the following internal faults currently detected inside the power supply:
VSB out of range
Output stage OT
Fan fault
ORING fault (Output voltage less than bus voltage)
OC shutdown
OT shutdown
OV shutdown
Input stage OT
Fault induced shutdown occurred
Thermal sensor fault
Vout out of range
PFC Boost Vbulk fault
As soon as all of the above faults are removed and the power supply operates normally, the Fault LED and PS Fault signal
shall be turned off. LED Definition: Three LEDs shall be located on the front faceplate; these are:
LED
Status
Input OK = ON
Output OK = ON
Fault = ON
www.murata-ps.com/support
D2U5T-H3-5000-380-HU3C.A04 Page 5 of 8
D2U5T-H3-5000-380-HU3C
AC-DC Three Phase Power Converter
CONTROL SIGNALS
Signal (I/O)
PS_ON_H
PS_KILL
PS_PRESENT
PS_FAULT_L
PWR_GOOD_H
STBY_SEL_IN
AC_OK_H
SMB_ALERT_L
VOUT_PRE-CHARGE, +/A0, A1 & A2
Description
Internal 10K pull-up resistor to internal VDD.5
Leaving signal pin open = Main Output ON
Tying signal pin to GND = Main Output OFF
Short pin; internal 10K pull-up resistor to internal VDD.5
Leaving signal pin open = All Outputs off
Tying signal pin to GND = All Outputs enabled
Interanally shorted to SIG_GND, STBY_RTN
used by system (where signal may be pulled up) for detection of a power module being installed into backplane.
Internal 10K pull-up resistor to internal VDD5
PSU Fault Status
Internal 10K pull-up resistor to internal VDD.5
Main Output Status OK
Internal 10K pull-up resistor to internal VDD5
Leaving signal pin open = +5VSTBY
Tying signal pin to GND = +3V3STBY
Internal 10K pull-up resistor to internal VDD.5
AC OK Status
Internal 10K pull-up resistor to internal VDD5
SMB Alert signal output
Input to Power Module for hotswap function.
+ VOUT_PRE_CHARGE: internally pulled up via 1K OHM resistor to main output return “+“
- VOUT_PRE_CHARGE: internally pulled up via 1K OHM resistor to main output return “-“
Addressing bit lines used can be used to assign the power supply’s controller and EEPROM device PMBus address. The table below
lists the possible address combinations that can be assigned.
DEVICE ADDRESS PIN STRAPPING ADDRESS OPTIONS
Serial Address Bits
A2
A1
A0
Bit 2
Bit 1
Bit 0
LOW
LOW
LOW
LOW
LOW
HIGH
LOW
HIGH
LOW
LOW
HIGH
HIGH
HIGH
LOW
LOW
HIGH
LOW
HIGH
HIGH
HIGH
LOW
HIGH
HIGH
HIGH
Corresponding Power Module Slave Device Address
PSU Main Controller
PSU EEPROM
(Secondary)
(External)
0xB0
0xA0
0XB2
0xA2
0xB4
0xA4
0XB6
0xA6
0XB8
0XA8
0xBA
0xAA
0xBC
0xAC
0xBE
0xAE
Each address line is pulled up via 10K to internal VDD
All three (3) pins unterminated result in address BE and AE respectively
Refer to Applcation notes ACAN-61 and ACAN-63 for further details
5
VDD depends on Standby Voltage selection of either 3.3V or 5V.
www.murata-ps.com/support
D2U5T-H3-5000-380-HU3C.A04 Page 6 of 8
D2U5T-H3-5000-380-HU3C
AC-DC Three Phase Power Converter
OUTPUT CONNECTOR & PIN ASSIGNMENT (Power Module Connector: FCI Power Blade Part # 51915-424 (MATING CONNECTOR: FCI 51939-826LF)
Pin
P13
P12
P11
Designation
-VOUT_PRE-CHARGE
-VOUT
+VOUT_PRE-CHARGE
Function
Hot Swap Pre Charge
380Vdc return
Hot Swap Pre Charge
Signal Direction
Output
Output
Output
Pin
B1
B2
B3
Designation
A2
PS_ON_H
+VSB
Function
I2C Address Bit 2 Signal
Enable PSU
+3.3V/5V STBY Out
Signal Direction
Input
Input
Output
P10
P9
P8
P7
P6
P5
P4
P3
P2
P1
A1
A2
A3
A4
A5
A6
+VOUT
Not fitted
Not fitted
AC1
Not fitted
AC2
Not fitted
AC3
Not fitted
GND
A1
PS_FAULT_L
A0
PS_PRESENT
SCL
SGND
380Vdc
AC Line Voltage Ph 1
AC Line Voltage Ph 2
AC Line Voltage Ph 3
Safety ground
I2C Address Bit 1 Signal
PSU Fault Status
I2C Address Bit 0 Signal
PSU Seated into Connector
I2C Clock Signal
Signal ground (return)
Output
Input
Input
Input
Input
Input
Output
Input
Output
Bi-Directional
Output
B4
B5
B6
C1
C2
C3
C4
C5
C6
D1
D2
D3
D4
D5
SDA
PS_KILL
VSB_RTN
STBY_SEL_IN
AC_OK_H
+VSB
+VSB
VSB_RTN
VSB_RTN
SMB_ALERT_L
PWR_GOOD_H
+VSB
+VSB
VSB_RTN
I2C Data Signal
Enable PSU
VSTBY_RT
Selects +3V3 or +5VSTBY
AC(DC) OK Status
+3.3V/5V STBY Out
+3.3V/5V STBY Out
VSTBY_RT
VSTBY_RT
SMB Alert signal output
Power OK Status
+3.3V/5V STBY Out
+3.3V/5V STBY Out
VSTBY_RT
Bi-Directional
Input
Output
Input
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
D6
VSB_RTN
VSTBY_RT
Output
CHANICAL DIMENSIONS
www.murata-ps.com/support
D2U5T-H3-5000-380-HU3C.A04 Page 7 of 8
D2U5T-H3-5000-380-HU3C
AC-DC Three Phase Power Converter
MECHANICAL DIMENSIONS
OPTIONAL ACCESSORIES
Description
Part Number
12V D2U5T-380 Output Connector Card
D2U5T-380-CONC
APPLICATION NOTES
Document Number
Description
Link
ACAN-62
D2U5T-380-CONC Customer Interface Connector Card
http://power.murata.com/datasheet?/data/apnotes/acan-62.pdf
ACAN-63
PMBusTM Communication Protocol for:
D2U5T-H3-5000-380-Hu3C
http://power.murata.com/datasheet?/data/apnotes/acan-63.pdf
Murata Power Solutions, Inc.
129 Flanders Road
Westborough, MA 01581
ISO 9001 and 14001 REGISTERED
This product is subject to the following operating requirements and the Life and Safety Critical Application Sales Policy.
Refer to: http://www.murata-ps.com/requirements/
Murata Power Solutions, Inc. (“Murata”) makes no representation that the use of its products in the circuits described herein, or the use of other technical information contained herein, will not infringe upon
existing or future patent rights. The descriptions contained herein do not imply the granting of licenses to make, use, or sell equipment constructed in accordance therewith. Buyer represents and agrees that it has all
the necessary expertise to create and implement safeguards that anticipate dangerous consequences of failures, monitor failures and their consequences, lessen the likelihood of failures that might cause harm, and
take appropriate remedial actions. Buyer will fully indemnify Murata, its affiliated companies, and its representatives against any damages arising out of the use of any Murata products in safety-critical applications.
Specifications are subject to change without notice.
© 2018 Murata Power Solutions, Inc.
www.murata-ps.com/support
D2U5T-H3-5000-380-HU3C.A04 Page 8 of 8