FP0 Series
Programmable Controllers
07/2007
1
FP0 – Super Compact PLC
Control FPWIN Pro
PLC Programming
Incredibly
Small, Alone
Software
or Even
conforming
as Multiple
to IEC61131-3
Combined Units
From I/O 10-points…
MM
Actual
size
«ÕÌÉÕÌ«ÕÌÊÌiÀ>
MM
4HEPHOTOSHOWSACONTROL
UNITWITH)/S
4HISSIZEISUNIFORMFOR
ALLEXCEPTTHE)/
POINT
CONTROLUNIT
3UPPLYVOLTAGE6$#
/""Ê«ÀÌ
(OOKSUPBYUSINGTHEPROGRAMMING
SOFTWARE #ONTROL&07).0RO
ANDASINGLECABLE
COM port: 2nd RS232C interface
(optional for all CPU units for serial communication)
Compact size
A control unit a mere 25mm* in width. Even expanded to 128 I/O points, the width is still only 105mm.
The attachment area is one of the smallest in its class.
The FP0 offers a compact design that breaks all previous
common sense rules on small-scale PLCs. With one of
the smallest-ever attachment area, the FP0 is perfect for
installation in machines, facilities, and control boards where
miniaturization is progressing even further.
Choose among 3 types of attachment
*30mm width for control units with 32 I/Os.
DIN rail
2
07/2007
Slim attachment plate
model
Flat attachment plate
model (cannot be used with
expansions)
Either 10 Points or the Maximum of 128 Points
You Save This Much Space!
…up to 128 I/Os
MM
#ONTROLUNIT
%XPANSIONUNIT
%XPANSIONUNIT
%XPANSIONUNIT
■ Networking:
- ETHERNET
- Modbus
- PROFIBUS
- S-LINK
- MEWNET-F
■ Analogue modules featuring different
numbers of input and output channels
■ Programming software:
- Control FPWIN Pro according
to IEC 61131-3
- Control FPWIN GR easy,
conventional programming
4HEPHOTOILLUSTRATESADDING
THREE
POINT)/EXPANSION
UNITSTOAN
POINT)/CONTROL
UNITYIELDINGPOINTS
3UPPLYVOLTAGE6$#
iV>ÕÃiÊvÊÌÃÊÃÕ«iÀÊV«>VÌÊÃ iÊ>`Ê
}
ÊV>«>LÌiÃ]Ê
Ì
iÊÕÌÃÊ>ÀiÊÕÃivÕÊÊ>Ê `iÊ >ÀiÌÞÊvÊ>««V>Ìð
Easy expansion
2ELAYSEQUENCE
REPLACEMENT
The expansion unit can be attached easily
without any cables.
The expansion unit can easily be attached directly to the
control unit. Special expansion cables, backplanes and
so forth are unnecessary as the expansion unit employs a
stacking system that uses expansion connectors and locking
levers on the surface of the unit itself.
0ARTSFEEDERS
!UTO
STOCKERS
Control
unit
Expansion
unit
Expansion
unit
)N
HOUSEDETECTORS
#ONVEYERCONTROL
&OODPROCESSINGAND
PACKAGINGMACHINES
0ARKINGMETERS
$RIVINGRANGE
Expansion
unit
(Maximum possible expansion is three units)
07/2007
3
FP0 CPU Units
A Rich Line-Up of Both Single and Combined Units
Control units
Relay output type
10 points
Input
6 points
Output
4 points
Transistor output type
10 points
Input
6 points
FP0-C10RSA
14 points
Output
4 points
Input
8 points
FP0-C10CRSA
14 points
Output
6 points
Input
8 points
FP0-C14RSA
with 2nd RS232C
16 points
Output
6 points
Input
8 points
16 points
Output
8 points
Input
8 points
Output
8 points
32 points
32 points
Input
Output
16 points 16 points
Input
Output
16 points 16 points
FP0-C14CRSA
FP0-C16PA (PNP) FP0-C16CPA (PNP) FP0-C32PA (PNP)
FP0-C32CPA (PNP)
with 2nd RS232C
FP0-C16TA (NPN) FP0-C16CTA (NPN) FP0-C32TA (NPN)
FP0-C32CTA (NPN)
with 2nd RS232C
with 2nd RS232C
Control unit 10k
AC power supply
This advanced FP0 CPU
offers additional features:
FP0-T32C
FP0-PSA2
■ 10,000 steps program memory
■ Battery backed RAM
■ Real-time clock
■ 16383-word
data register
32 points
Input
16 points
Output
16 points
Input
85 to 265VAC
Output
24VDC/0.7A
Terminal type
FP0-T32CPA (PNP)
FP0-T32CTA (NPN)
with 2nd RS232C
Expansion combinations
A maximum of 3 expansion units can be added to the control unit. (Combining relay output types and transistor output types is also
possible. In this event, the maximum number of I/O points when using a relay output type control panel is 110.)
Combinations with transistor output type – Examples
/Ì>ÊÕLiÀ
vÊÉ"Ê«ÌÃ
)NPUT
)NPUT
)NPUT
®
{n
/UTPUT
r
r
r
4
)NPUT
r
)NPUT
n
/UTPUT
r
)NPUT
È
/UTPUT
r
r
r
£Ón
r
)NPUT
)NPUT
/UTPUT
££Ó
)NPUT
#ONTROLUNIT
È{
r
)NPUT
/UTPUT
/UTPUT
)NPUT
)NPUT
)NPUT
)NPUT
)NPUT
® ³ %XPANSIONUNIT
® ³ %XPANSIONUNIT
® ³ %XPANSIONUNIT
®
8 9
8 9
8 9
ÎÓ
³
£È
³
ÎÓ
³
)NPUT
ÎÓ
³
)NPUT
£È
³
ÎÓ
³
³
)NPUT
ÎÓ
³
)NPUT
ÎÓ
³
/UTPUT
/UTPUT
/UTPUT
/UTPUT
/UTPUT
/UTPUT
£È
/UTPUT
/UTPUT
/UTPUT
)NPUT
)NPUT
)NPUT
)NPUT
)NPUT
£È
/UTPUT
ÎÓ
/UTPUT
ÎÓ
/UTPUT
ÎÓ
³
ÎÓ
³
ÎÓ
³
³
)NPUT
ÎÓ
³
)NPUT
ÎÓ
³
/UTPUT
/UTPUT
/UTPUT
ÎÓ
/UTPUT
/UTPUT
07/2007
/UTPUT
)NPUT
)NPUT
)NPUT
)NPUT
£È
/UTPUT
ÎÓ
/UTPUT
ÎÓ
/UTPUT
ÎÓ
³
)NPUT
ÎÓ
³
)NPUT
ÎÓ
³
/UTPUT
/UTPUT
/UTPUT
£È
)NPUT
/UTPUT
£È
/UTPUT
ÎÓ
/UTPUT
FP0 Expansion Units
Choose the Number of I/O Points to Suit the Application
Digital I/O units
Relay output type
8 points
Input
4 points
Output
4 points
Input only type
16 points
Input
8 points
FP0-E8RSA
Output
8 points
FP0-E16RSA
Transistor output type
32 points
8 points
16 points
8 points
Input
Output
16 points 16 points
Input
8 points
Input
16 points
Output
8 points
FP0-E32RS
FP0-E8XA
FP0-E16XA
FP0-E8YPA (PNP)
FP0-E16PA (PNP) FP0-E16YPA (PNP) FP0-E32PA (PNP)
FP0-E8YTA (NPN)
FP0-E16TA (NPN) FP0-E16YTA (NPN) FP0-E32TA (NPN)
Option:
16 points
Input
8 points
Output
8 points
16 points
32 points
Output
16 points
Input
Output
16 points 16 points
Output 8 points
FP0-E8YRSA
Analogue I/O units
Thermocouple and RTD units
3 points
4 points
4 points
8 points
4 points
8 points
6 points
Input
Output
2 points 1 points
Output
4 points
Output
4 points
Input
8 points
Input
4 points
Input
8 points
Input
6 points
FP0-A21A
FP0-A04I
FP0-A04V
FP0-TC4
FP0-TC8
• Input (12-bit):
! 10V, 0 – 5V,
0 – 20mA
• Output (12-bit):
! 10V, 0 – 20mA
–
–
–
–
4 – 20mA
! 10V
FP0-A80A
! 10V, ! 100mV
0 – 5V, 0 – 20mA
–
• K, J, T, R type thermocouples can
be used
• Resolution: 0.1°C
• Accuracy: 0.8°C (R type: 3°C)
• Temperature range:
-100 to 1500°C
FP0-RTD6
• Pt100, Pt1000,
Ni1000
• Temperature
range:
-200 to 500°C
Networking units
MEWNET-F
FP0-IOL
(MEWNET-F Slave)
S-LINK CPU
FP0-SL1
(S-LINK Master)
ETHERNET
FP WEB D
(Web-Server Unit)
PROFIBUS
FP0-DPS2
(DP Slave)
07/2007
5
FP0 – Impressive Capabilities
High Specifications for Both Speed and Capacity
0.9µs per basic instruction. Pulse catch and interrupt input functions meet the need for high-speed response.
High-speed execution
Execution speed of 0.9µs per basic instruction. 500 step programme yields a scanning time of 1ms.
SCAN
)/
REFRESH
0ROGRAM
EXECUTION
)/
REFRESH
0ROGRAM
EXECUTION
)/
REFRESH
0ROGRAM
EXECUTION
)NTERNALPROCESSINGINTHE&0
Internal processing in the FP0
Pulse catch function
Interrupt input function
Can read pulses as short as 50µs, which facilitates sensor
input.
)/
REFRESH
0ROGRAM
EXECUTION
)/
REFRESH
3ENSORINPUT
SIGNAL
Accurate processing, unaffected by scan time
0ROGRAM
EXECUTION
#ANNOT
READ
ÌiÀÀÕ«ÌÊ«À}À>ÊiÝiVÕÌi`ÊÜ
i
ÌiÀÀÕ«ÌÊ«ÕÌÊiÌiÀðÊ
0ROGRAM
EXECUTION
)/
REFRESH
)NTERRUPTINPUT
)/
REFRESH
7Ì
Ê«ÕÃiÊV>ÌV
ÊvÕVÌ
>
Ài>`t
,ENGTHENING
OFSENSOR
INPUTSIGNAL
)NTERRUPT
PROGRAM
0ROGRAM
EXECUTION
)NTERNALPROCESSINGINTHE&0
Pulse catch function
Interrupt input function
Large capacity
A 5k- and 10k-step programme capacity housed within a compact body. Furthermore, data capacity for internal devices like the data
register is also ample. The unit's performance can even handle complicated control tasks.
)/
POINT
POINT
POINTTYPE
0ROGRAMMESIZE
STEPS
)NTERNALRELAYS
6
&0
4#04
STEPS
STEPS
POINTS
4IMERS#OUNTERS
$ATAREGISTERS
ÌÀÊÕÌÊÌÞ«i
)/
POINTTYPE
POINTS
WORDS
WORDS
07/2007
WORDS
FP0 – Impressive Capabilities
FP0 Functions
Equipped with 2-axis independent positioning and high-speed counter for support of PWM output.
Pulse output function
The unit comes equipped with 2 channels for the output of up to 10kHz
pulses (5kHz during 2-channel output). Since these two channels can
be separately controlled, the PLC is also suitable for independent 2axis positioning. Setting automatic trapezoid control, automatic return
to home position and JOG operation are made very easy by using
instructions specially designed for such operations.
(For transistor output type only.)
Y0
Y2
Y1
Y3
Pulse output
Clockwise output/
counter-clockwise output
Motor
driver 1
Stepping motor
Servo motor
Motor
driver 2
Stepping motor
Servo motor
Pulse output
Clockwise output/
counter-clockwise output
Positioning control is a breeze with
the auto trapezoid control command!
High-speed counter function
Feeder roller
The high-speed counter is designed to use 4 channels in single-phase operation or
2 channels in 2-phase operation. In single phase operation, the total speed for all 4 channels is
10kHz, in 2-phase operation the 2-channel total is 2kHz total speed, making the unit suitable for
conveyer control, inverter control and so forth using an encoder.
Cutter
Lead wiring,
tape
Inverter
Motor
START/STOP
signal
Encoder
Cutter blade
control signal
Encoder output
inputted into
high-speed counter
PWM output function
Its PWM (Pulse Width Modulation) output function makes
it possible to provide temperature control with a single
compact FP0 unit. (For transistor output type only.)
# When pulse width values are increased…
power up
# When reduced…
Heater
power up
# When reduced…
Heater
power down
Serial communication function
• The FP0’s second RS232C port (types C10CRS, C14CRS, C16C, C32C,
and T32C) allows direct connection to computers and operation display
panels. Also, bi-directional data communication with barcode readers
and other RS232C devices is made easy.
# For connecting to computers and operation display panels
• Both the relay type and transistor output type control units can be optionally
equipped with a 2nd RS232C port.
# For data communication with RS232C devices
Host computer
(Personal computer)
FP0
RS-232C
POWER
KEY PAD
READY
MODE
A
B
C
COM COM D2
FLASH
D1
D4
D3
D6
D5
MONITOR
D8
D9
D7 READY
MICRO-IMAGECHECKER
M100
Matsuhita Electronic Works, Ltd.
24VDC
START ACK IN1
CAMERA
Operation
display panel
IN3
IN5
COM COM IN2 IN4
COM
Imagechecker
Bar code reader
Serial printer
Analogue control function
07/2007
0RESSURESENSOR
)NVERTER
25.
-/$%
02/'
%22/2
!,!225.
/&&/.
02/'
6
)
).
)
6
,ASERANALOGUE
SENSOR
/54
)
#/-
* ÊÊÓ£
Analogue control is made simple with four types of analoque modules featuring
different numbers of input and output channels.
Also, despite its small size, the I/O resolution is a high 1/4000 (12 bits).
Support various I/O ranges by setting the DIP switches on the analogue
I/O unit for simple operation.
0OTENTIOMETER
7
FP0 Communication
Serial Interfaces and Modem Compatible
Communication – Simple and efficient via two serial interfaces: TOOL port and COM port (RS232C interface).
Programming interface TOOL port (also for communication)
In MEWTOCOL-COM Slave mode, this port offers access to the entire FP0 memory area. For example during data exchange
between a host PC running SCADA software and an FP0 PLC, the Windows® based FP OPC Server assumes total control of
the communications protocol (MEWTOCOL.COM). Therefore the user can disregard the allocation of data ranges and transfer
parameters, because there is no additional programming required. The programmer is thus free to concentrate exclusively on the
project application requirements.
Communication Interface COM port
(Flexible with two modes of operation, MEWTOCOL-COM Slave (Computer Link) and Program controlled (General purpose))
In addition to the MEWTOCOL-COM Slave (Computer Link) communication possibilities described above, the optional, integrated
RS232C COM port in the FP0 CPU modul (types FP0-C10CRS, FP0-C14CRS, FP0-C16C, FP0-C32C and FP0-T32C) offers
flexible programme control (General purpose). In this configuration it is possible to realise communication connections with
various peripheral devices via RS232, e.g. bar code readers, slave devices, printers, measurement sensors, telecommunication
transmitters, etc.
Communication interface COM port
Freely programmable RS232C interface for CPU modules type FP0-C10CRS,
FP0-C14CRS, FP0-C16C, FP0-C32C and FP0-T32C
Programming interface TOOL port
For programming or additional master/slave communication using
MEWTOCOL COM (Panasonic protocol)
Modem compatible
Even modem communication function is built into this compact body. Using a single telephone line,
programming maintenance can be carried out in remote facilities. With C-NET, multiple FP0 units can be
connected.
■ 1:1 communication
8
■ 1:N communication
■ Multidrop communication
07/2007
FP0 Communication
Easier Maintenance Than Ever Before
Maintenance saving
Program memory uses EEPROM. In addition, programmes can be changed even in RUN mode!
■ Overwrite function in RUN mode
It is possible to overwrite a program while the FP0 is running, such as during program debugging and startup adjustments.
■ Backup battery unnecessary
The program memory uses EEPROM. The program and device contents can be stored without a backup battery, and even
programming for a machine builder is safe.
■ Password function
A password function can be set in order to change a program. Limited to people authorised to make programme changes,
protection can be guaranteed better than ever.
■ Input/output verification LED
Every unit is equipped with LED I/O indicators housed within a compact body. Input/output status can be verified
at a glance.
Simple installation
Comes with either terminal block or MIL connector, simplifying wiring.
Terminal block
MIL connector
The terminal type can be plugged
straight in without resorting to
crimping (made by Phoenix Contact
Co.). Can handle wires from
0.3 to 1.25mm2.
Compatible models
FP0-C10RS, C10CRS, C14RS, C14CRS, E8RS, E16RS, E32RS
07/2007
MIL connectors can be used
with 16-point and 32-point
units. Due to the loose-wiring,
pressure contact type design,
wiring is easy without the need
for insulation. (MIL-C-83503)
Compatible models
FP0-C16T/C16P/C16CT/C16CP, C32T/C32P/C32CT/C32CP,
E16T/E16P, E32T/E32P, FP0T32CP/T32CT
9
FP0 PROFIBUS DP Slave or Remote I/O Unit
For Cost Effective Control of Distributed Field Device
The FP0 DPS2 can operate either as a DP Slave module or as a remote I/O
system to which different decentralised inputs and outputs can be connected.
A DIP switch can be used to switch between the two modes:
Mode 1:
DP Slave module. Connect the FP0 or FPΣ (Sigma) CPU + expansion modules
to the PROFIBUS network.
Mode 2:
Remote I/O. Connect up to three expansion modules without CPU to the
PROFIBUS network.
In remote I/O mode, the unit can be connected to any PLC which offers a
PROFIBUS communication interface, making it totally independent of
Panasonic PLCs.
FP0-DPS specifications
Item
Description
Type designation
FP0 DP Slave unit, Ord. No. FP0DPS2
PROFIBUS standards complied with
EN 50170, DIN 19245 Part 1 and Part 3
9.6 / 19.2 / 93.75 / 187.5 / 500 / 1,500 / 3,000 / 6,000 / 12,000 Kbaud
Baud rates
automatic baud rate detection
Range of addresses that can be set
0..125
PROFIBUS connection
9-pin Sub-D connector
Configuration
DP-Slave
Remote I/O
2 words input / 2 words output, up to 6 words input / 6 words output if no other expansion is connected
Remote I/O, max. 3 FP0 expansion units
FP0 communication
Via FP0 system bus
Power supply
24VDC (21.6VDC … 26.4VDC)
Max. power consumption
100mA
PLC
Specially by developed software tools ensure
easy configuration and start-up of PROFIBUS
products.
(Master)
FP2 DP or FMS Master
PLC
(Slave)
FP0 DP Slave
FP
(Sigma) DP Slave
PROFIBUS DP-Configurator AFP86910
Remote I/O
DP Slave Remote I/O
Configuration with digital I/O
up to 96 transistor I/O or up to
48 relay I/O are possible
10
DP Slave Remote I/O Configuration
with analogue I/O up to 12 outputs
or 24 analogue inputs or up to 24
thermocouple inputs are possible
(Slave)
07/2007
FP0 S-LINK Unit
Connects Directly to the S-LINK for Reduced Wiring
S-Link is a system which simplifies connection of rapidly increasing control devices accompanying
progressing automation and is useful in reducing your costs and construction time.
Features
1. Small size of only W30xH90xD60mm.
Makes use of the T-shaped connectability of the S-LINK for reduced wiring and reduced size
of the control panel.
2. Controls 64 input points and 64 output points.
Able to control up to 128 points for S-LINK related devices.
3. Allows simultaneous use of expansion units.
Similar to other FP0 units, up to three expansion units can be used for efficient I/O wiring.
FP0-SL1
4. A wide range of I/O modules allow manifold customer-oriented network layouts.
Power supply specification
Item
Description
Power supply
24VDC
Applicable network
Performance specifications
Item
Description
Remote I/O
Control unit functions as S-LINK
master station.
Available as a slave station of
MEWNET-F by adding I/O link unit
Item
Description
Inter-PLC link
Not available
Number of I/O points
S-LINK block: 64 input points,
64 output points (fixed)
Computer link
Link with TOOL port or RS232C
port
Modem connection
Available, type with RS232C
port can also send data
Operation speed
Max. 3 units
Expansion section:
Max. 96 points
0.9µs/step
Internal memory
EEPROM
Memory capacity
5k-steps
Item
Description
Memory Internal relay
Timer/Counter
of
execution Data register
1008 points
144 points in total
Program block-edit
during RUN
Available
6144 words
Constant scan
Available
Adjustable input time
filtering
Not available
Clock/Calendar function
None
Expansion
Other built-in functions
Applicable functions
Item
Description
Pulse catch/Interrupt input
None
Analogue I/O
Available by adding analogue I/O unit
Volume input
None
High-speed counter
None
Pulse output
None
RS232C port
1 ch is equipped.
3P terminal blocks (made by
Phoenix Contact Co.)
Direct connection for reduced wiring
&0
3
,).+CONTROLUNIT
7s(s$
The layout of devices is flexible and the
design is easier due to the
‘T’-branch multi-drop wiring.
-AXIMUMLENGTHM
-AXPOINTS
4
BRANCHMULTI
DROPWIRING
SIGNALWIRES
POWER
SUPPLYWIRES
Wire-saving
The use of wires is greatly reduced and the number of connecting terminal blocks is minimised, resulting in large reduction in cost, as well as
waste generated during wiring.
Space saving
S-Link devices are compact. The control box can be mounted in a tight
space.
Quick construction
Sensors cab be easily connected with plug-in connection.
07/2007
11
FP0 MEWNET-F Unit
Networking Units
MEWNET-F
The FP0 can be used as a slave station for MEWNET-F (remote I/O system) by adding I/O link unit.
MEWNET-F is a reduced-wiring, remote I/O system that connects PLCs located
separately and I/O slave stations with 2-core cabling. By adding an I/O link unit
to the FP0, you can link master station PLC and FP0 inputs and outputs via the
network.
FP2 (Master station)
Twisted pair cable or VCTF
FP0 (Slave station)
FP0 (Slave station)
FP0-IOL
FP0 (Slave station)
FP0-IOL
FP0-IOL
MEWNET-F Slave
FP0-IOL
FP0-IOL Link Unit Specifications
Item
Description
Communication method
Two-wire, half duplex transmission
Synchronous system
Transmission line
Start stop synchronous system
2
2-wire cable (Twisted-pair cable or equivalent to VCTF 0.75 mm x 2C)
Transmission distance
(Total distance)
Max. 700m per port (using twisted pair cable)
Max. 400m per port (using VCTF cable)
Transmission speed (Baud rate)
0,5Mbit/s
Number of control I/O points
per an I/O link unit
64 points
(Input: 32 points. Output: 32 points)
Remote I/O map allocation
32X/32Y
Interface
Conforms to RS485
Transmission error check
CRC (Cyclic Redundancy Check) method
C-NET
By using C-NET, you can use multiple FP0s as data collection terminals.
By using the C-NET network and exclusive
adapters, you can connect multiple FP0s
by multi-drop connection with 2-wire cables.
You can use computers for separate control
or have network terminals for a centralised
management system.
#
.%4
ADAPTER
#
.%4
ADAPTER
3TYPE
!&0
&0
12
07/2007
!#TO6!&0
6$#
!&0
-AXUNITS
-AXM
Analogue Signal Processing
FP0 Analogue Units
Features
FP0-A21
FP0-A80
FP0-A04V
FP0-A04I
2 Inputs/1 Output
8 Inputs
4 Outputs
4 Outputs
■ Multimode A/D, D/A conversion
Voltage, current and temperature selectable
■ High resolution: 12-bit
■ 2 analogue inputs (FP0-A21):
-10 to + 10V, 0 to 5V, 0 to 20mA,
8 analogue inputs (FP0-A80):
-10 to + 10V, 0 to 5V, -100 to + 100mV, 0 to 20mA
■ High conversion speed
FP0-A04V, FP0-A04I: 500µs
■ PID instruction with auto tuning
■ 1 analogue output (FP0-A21): -10 to + 10V, 0 to 20mA
4 analogue outputs (FP0-A04V): -10 to + 10V
4 analogue outputs (FP0-A04I): 4 to 20mA
■ Screw terminal connection
The analogue units can be used with the FP0 and FP∑ (Sigma) so wide range applications are possible from smallscale machines to factory production systems.
Each CPU supports up to 3 FP0 analogue units. Combination with digital and analogue expansion units is freely allowed.
Highest performance is offered with 12-bit resolution. With a current and voltage output conversion time of up to
500µs, the units are capable of high-speed processing.
The multimode FP0 analogue unit can be configured via the DIP switches on the front side into the required analogue ranges.
Communication with the FP0 CPU unit is achieved via the expansion bus. The expansion bus is automatically connected after
the FP0 analogue unit is connected to the FP0 CPU unit.
Note: Function blocks for the FPWIN Pro programming system can be downloaded free of charge from our Web site.
07/2007
13
Analogue Signal Processing
FP0 Analogue Units
General specifications
Item
Rated operating voltage
Description
24VDC
Operating voltage range
21.6 to 26.4VDC
Rated current consumption
FP0-A80: 60mA or less, FP0-A21/A04V: 100mA or less, FP0-A04I: 130mA or less
Ambient temperature
0°C to + 55°C
Storage temperature
-20°C to + 70°C
Size
90 x 25 x 60mm
Weight
Approximately 100g
Analogue input specification
Item
Description
Product
FP0-A21
Input range selectable
( 2 CH)
Digital output
FP0-A80
2 channels/unit
Number of channels
8 channels / unit
Voltage mode
0 to 5V / -10V to +10V
Current mode
0 to 20mA
Thermocouple mode
-100 to +100mV / 0 to 5V / -10V to +10V
0 to 20mA
K, J, T type thermocouple
K up to 1000°C or -100°C to terminal temperature (selectable)
J up to 750°C or -100°C to terminal temperature (selectable)
T up to 350°C or -100°C to terminal temperature (selectable)
0 to 5V / 0 to 20mA:
K 0 to K 4000 (H 0000 to H 0FA0)
*1
-10 to +10V (-100 to +100mV):
K -2000 to K +2000 (HF830 to H07D0)
Thermocouple: The value of broken wire detection is K 20000.
For plus:
K temperature of terminal *2 to K 1000 (Unit is Celsius)
For minus:
K-100 to K temperature of terminal *3 (Unit is Celsius)
Resolution
Conversion speed
Overall accuracy
Input impedance
Maximum input
Insulation
FP0 input address
–
–
12 bits (1/4000)
Voltage/current mode:
Thermocouple mode:
1ms/ channel
2ms / channel
560ms/ channel
Voltage/current mode:
1% for full-scale (0 to 55°C), 0.6% for full-scale (at 25°C)
Thermocouple mode:
Offset error (0 to 55°C), 2% for full-scale (K-type)
2.7% for full-scale (J-type)
–
5.8% for full-scale (T-type)
Linearity error (0 to 55%): 1% for full scale
Voltage mode: 1M ohm or more
Current mode: 250ohm
Voltage mode: +/- 15V
Current mode: +30mA
Optical coupler insulation between analogue input terminal and FP0 internal circuit
(No insulation between analogue inputs)
DC/DC converter insulation between analogue input terminal and analogue I/O unit external power supply
DC/DC converter insulation between analogue input terminal and analogue output terminal
–
32 input contact points:
First 16 points analogue input
32 input contact points: First 16 points analogue input CH0 data (WX2) *4
CH0,
2,4,6 data (WX2) *4
Last 16 points analogue input CH1 data (WX3) *4
Last 16 points analogue input
CH1,3,5,7 data (WX3) *4
*1 K means decimal constants.
*2 Reference temperature → Reference points is start points.
*3 Reference temperature → Reference points is end points.
*4 The address varies depending on the position of the analogue unit. (WX2/3, WX4/5 or WX6/7)
Analogue output specification
Item
Product
Description
FP0-A21
Number of channels
Output signal selectable
Digital input *1
Voltage mode
Current mode
0 to 20mA:
-10V to +10V:
FP0-A04V
1
-10V to +10V
0 to 20mA
0 to 20mA: K 0 to K 4000
-10V to +10V: K -2000 to K+2000
500ms
Overall accuracy
Insulation
Reserved CPU addresses *4
14
K 0 to K 4000
500µs
500µs
Voltage mode: less than 0.50Ω
-
Voltage mode: +/- 10mA
-
Maximum output current
resistance
-10V to +10V
K -2000 to K+2000
1% for full-scale (0 to 55°C), 0.6% for full-scale (at 25 °C)
Output impedance
Allowable output load
4
4 to 20mA
12 bits (1/4000)
Resolution
Conversion speed
FP0-A04I
4
1000Ω or more
Less than 300Ω
Less than 500Ω
Optical coupler insulation between analogue output terminal and FP0 internal circuit
DC/DC converter insulation between analogue output terminal and analogue I/O unit external power supply
DC/DC converter insulation between analogue output terminal and analogue input terminal
16 output points
32 output points
32 output points
07/2007
FP0 Thermocouple Input Expansion Units
Enable High Precision Temperature Control at Low Cost
Temperature control
The FP0-TC4 and FP0-TC8 thermocouple units are suitable for user-friendly
temperature acquisition using standard thermocouples with
high precision.
■ Up to three units can be added to each control unit, enabling temperature
control of up to 24 channels.
■ The temperature data obtained using the thermocouple is converted to the
digital value to be read into the FP0 control unit.
■ Standard types of thermocouples can be used: K, J, T and R
■ 3 temperature measurement ranges are available:
-100°C to +500°C (thermocouple types: K and J)
-100°C to +400°C (thermocouple type : T)
- 0°C to +1500°C (thermocouple type : R)
■ The temperature data measured using the sensor is converted to degrees
Celsius or degrees Fahrenheit inside the thermocouple unit.
FP0-TC8
8 channels
■ The converted data (°C or °F) is averaged, so that even unstable input
signals can be properly read.
FP0-TC4
4 channels
■ Broken thermocouples can be detected.
FP0-TC4 and FP0-TC8 specifications
Item
Input points
Input range
Specification
Up to 8 channels per unit (The number of input points can be changed 2, 4, 6 and 8 channels are available)
Thermocouple types K, J
-100°C to 500°C
Thermocouple types T
-100°C to 400°C
Thermocouple types R
0°C to 1500°C
Resolution
Sampling cycle
Accuracy
0.1°C
300ms:
500ms:
700ms:
900ms:
when
when
when
when
using
using
using
using
Range for K and J
Range for T
Range for R
2
4
6
8
channels
channels
channels
channels
for
for
for
for
an
an
an
an
input
input
input
input
points
points
points
points
(-100°C to 500°C):
(-100°C to 400°C):
(0°C to 99.9°C):
(100°C to 299.9°C):
(300°C to 1500°C):
0.8°C
0.8°C
3°C
2.5°C
2°C
Input Impedance
More than 1MΩ
Insulation method
- Between thermocouple input terminals and control unit internal circuits Photo-coupler insulation/DC-DC insulation
- Between thermocouple input terminal channels PhotoMOS relay insulation
07/2007
15
FP0 RTD Input Expansion Unit
User Friendly Acquisition of Temperatures with High Precision
Features
■ The module can be easily installed in an existing system. Special connection
cables, backplanes, and so forth are unnecessary as the expansion unit
employs a stacking system that uses expansion connectors and lock levers
on the surface of the unit itself.
■ Multiple RTD types are allowed in one module, creating a cost-effective
solution.
■ About the application areas:
- Measurement and control equipments
- Process and machine controls
- Greenhouse and agricultural industries
FP0-RTD6
6 channels
Take advantage of the various FPWIN Pro libraries with many functions and function blocks. These ready-made programmes
can be saved and reused time and again and will help you to shorten the time needed to develop applications drastically, and
consequently save valuable human resource costs.
Process and Temperature Control Library: NCL-PTC-LIB*
The numerous functions of this library simplify the programming of
closed loop controlled electrical installations. The library includes linear
and non-linear controller types such as the P/I/PI/PID controller and
two-point / three-point controllers with and without hysteresis.
Functions for dead band, interpolation, lamp limiting, dead time and
averaging are also included.
* available November 2006
FP0-RTD specifications
Item
Specification
Input points
Up to 6 channels per unit
- 3 inputs per one Phoenix screw terminal
- for every sensor 3 screws
Pt100 -200°C to 500°C (3 wire)
Input type
Pt1000 -100°C to 200°C (2 wire)
Ni1000 -30°C to 150°C (2 wire)
Sampling cycle
Resistor measurement
0.1s / 1s for 6 channels
- depending on the switch setting
(slower cycle timer = higher accuracy)
Temperature resolution
0.1 K
Accuracy
at ambient temperature: 0-55°C
Cycle time 0.1s:
Pt100: 0.5% / 3.5K, Pt 1000: 05% / 2.5K, Ni 1000: 2K, Resistor: 2Ω
Cycle time 1s:
Pt100: 0.35% / 2.5K, Pt 1000: 035% / 1.7K, Ni 1000: 1K, Resistor: 1Ω
Accuracy
at ambient temperature: 25°C
Cycle time 1s:
Size
W25 x H90 x B60mm
16
Pt100: 0.3K from -10 to +30°C, 0.2% / 1.4K from -200 to +500°C
Pt1000: 0.3K from -10 to +30°C, 0.2% / 1.0K from -200 to +300°C
07/2007
FP0 Series
Specification Tables
FP0 specifications
4YPEOFCONTROLUNIT
#SERIES
#SERIES
#SERIES
#SERIES
2ELAYOUTPUTTYPEONLY 2ELAYOUTPUTTYPEONLY 4RANSISTOROUTPUTTYPEONLY 4RANSISTOROUTPUTTYPEONLY
3
,).+TYPE
4SERIES
4RANSISTOROUTPUTTYPEONLY
0ROGRAMMINGMETHOD#ONTROLMETHOD
2ELAYSYMBOL#YCLICOPERATION
4OTAL
.OEXPANSION
4OTAL
4OTAL
4OTAL
4OTAL
4OTAL
CONTROLUNITONLY
)NPUT/UTPUT
)NPUT/UTPUT
)NPUT/UTPUT
)NPUT/UTPUT
)NPUT/UTPUT
)NPUT/UTPUT
.UMBEROF
7EXPANSION
-AX
-AX
-AX
-AX
-AX
3AMETYPEOFCONTROLANDEXPANSIONUNITS
)/POINTS
%XPANSIONSECTION
MAXPOINTS
7EXPANSION
-AX
-AX
-AX
-AX
-AX
-IXTYPEOFRELAYANDTRANSISTORUNITS
0ROGRAMMEMORY
%%02/.OBACK
UPBATTERYREQUIRED
0ROGRAMCAPACITY
KSTEPS
KSTEPS
KSTEPS
+INDSOF
"ASIC
INSTRUCTION
(IGH
LEVEL
/PERATIONSPEEDCENTRALVALUESTEP
S"ASICINSTRUCTION
)NTERMALRELAY2
POINTS
2ELAY
4IMER#OUNTER4#
POINTS
-EMORYFOR
$ATAREGISTER$4
WORDS
WORDS
WORDS
EXECUTION
-EMORY
WORDS
)NDEXREGISTER)8)9
AREA
-ASTERCONTROLRELAY-#2
POINTS
.UMBEROFLABELS*-0AND,//0
LABELS
LABELS
$IFFERENTIALPOINTS
5 NLIMITEDNUMBEROFPOINTS
.UMBEROFSTEPLADDER
STAGES
STAGES
.UMBEROFSUBROUTINES
SUBROUTINES
SUBROUTINES
(IGH
SPEEDCOUNTER
PHASEPOINTSK(ZINTOTAL ORPHASESPOINTSK(ZINTOTAL
.OTAVAILABLE
!VAILABLESAMEAS
POINTSK(Z
INTOTAL ENABLETOCONTROL
0ULSEOUTPUT
.OTAVAILABLE
.OTAVAILABLE POINTSSERIES
CHANNELSINDIVIDUALLY
07-OUTPUT
.OTAVAILABLE
(ZTOK(Z
.OTAVAILABLE
0ULSECATCHINPUTINTERRUPTINPUT
POINTSWITHHIGH
SPEEDCOUNTER
.OTAVAILABLE !VAILABLESAMEAS
POINTSSERIES
3PECIAL
PROGRAMINTERNALPOINT
)NTERRUPTPROGRAMME
PROGRAMSEXTERNALPOINTSINTERNALPOINT
FUNCTIONS
0ERIODICALINTERRUPT
MSTOS
#ONSTANTSCAN
!VAILABLE
/NE23#PORTISMOUNTEDONEACHOFTHEMODELS&0
##2##2##4##0##4##04#44#0AND3,TYPE0TERMINALBLOCK
23#PORT
4RANSMISSIONSPEED"AUDRATE TOBITSS M#OMMUNICATIONMETHODHALFDUPLEX
4RANSMISSIONDISTANCEM
0ROGRAMMEANDSYSTEMREGISTER
3TOREDPROGRAMMEANDSYSTEMREGISTERIN%%02/-
-AINTENANCE
-EMORY
BACKUP
/PERATION
MEMORY
3ELF
DIAGNOSISFUNCTIONS
#LOCKCALENDERFUNCTION
/THERFUNCTIONS
3TOREDFIXEDAREAIN%%02/#OUNTERPOINTS
)NTERNALRELAYPOINTS
$ATAREGISTERWORDS
3TOREDFIXEDAREAIN%%02/#OUNTERPOINTS
)NTERNALRELAYPOINTS
$ATEREGISTERWORDS
7ATCHDOGTIMERPROGRAMSYNTAXCHECKINGETC
.OTAVAILABLE
2UNTIMEEDITINGPASSWORDSETTING
"ACKUPISPROVIDEDBY
SECONDARYBATTERY4HE
HOLDINGRANGEFORTHE
TIMERSCOUNTERSINTERNAL
RELAYSANDDATAREGIS
TERSARESPECIFIEDWITH
THEPROGRAMMINGTOOL
!VAILABLE
&ORTHELIMITATIONSWHILEOPERATINGUNITSSEETHEMANUAL
General specifications
)TEM
2ATEDOPERATINGVOLTAGE
/PERATINGVOLTAGERANGE
!LLOWABLENOVOLTAGETIME
!MBIENTTEMPERATURE
3TORAGETEMPERATURE
!MBIENTHUMIDITY
3TORAGEHUMIDITY
"REAKDOWNVOLTAGE
)NSULATIONRESISTANCE
6IBRATIONRESISTANCE
3HOCKRESISTANCE
.OISEIMMUNITY
/PERATINGCONDITION
POINTSPOINTSTYPE
POINTSPOINTS3
,).+TYPE
$ESCRIPTION
6$#
TO6$#
MSAT6 MSAT6
MSAT66
#TO #
#TO #
TO2(.ON
CONDENSING
TO2(.ON
CONDENSING
"ETWEENINPUTOUTPUTTERMINALSANDPOWERGROUNDTERMINALS6!#FORMINUTEFORTHERELAYOUTPUTTYPE6!#FORMINUTE
"ETWEENINPUTTERMINALSANDOUTPUTTERMINALS6!#FORMINUTEFORTHERELAYOUTPUTTYPE6!#FORMINUTE
"ETWEENINPUTOUTPUTTERMINALSANDPOWERGROUNDTERMINALSOV ER-7USINGA6$#MEGGER
"ETWEENINPUTTERMINALSANDOUTPUTTERMINALSOVER-7USINGA6$#MEGGER
TO(ZS WEEPMINDOUBLEAMPLITUDEOFMMMIN ONAXES
MS ORMORETIMESONAXES
6P
P WITHPULSEWIDTHSNSANDMSUSINGANOISESIMULATOR
&REEFROMCORROSIVEGASSESANDEXCESSIVEDUST
07/2007
17
FP0 Series
Specification Tables
Interfaces
Item
Description
Programming TOOL port
RS232, mini DIN socket (5 pin), 9600 or 19200 BAUD, (8 data bits, odd parity, 1 stop bit), Computer link for programming and communication with MEWTOCOL-COM, user configurable modem connection
Communication COM port
RS232 (SD, RD, GND) 3 way screw terminal, 300 to 19200 BAUD, (7 or 8 data bits, none/even/odd parity,
1 or 2 stop bits, start code: none/STX, end code: CR/CR+LF/ETX/none, CCU mode for programming and communication with MEWTOCOL.COM, user configurable modem connection, GENERAL PURPOSE MODE controlled by programme for general purpose RS232 communication
Input specifications
Item
Description
Insulation method
Optical coupler
Rated input voltage
24VDC
Operating voltage range
21.6 to 26.4VDC
Rated input current
4.3mA or less (at 24VDC)
Input points per common
6 points/common (C10RS) 8 points/common (C14RS,C16T/C16P,E16T/E16P) 16 points/common (C32T/C32P,E32T/E32P)
ON voltage/ON current
19.2V or less/ 3mA or less
OFF voltage/OFF current
2.4V or more/ 1mA or more
Input impedance
Approx. 5.6kΩ
50µs or less (at X0,X1) *
OFF➔ ON
100µs or less (at X2 to X5)
ON➔ OFF
Same as above
2ms or less (at X6 to XF)
Response time
Operating indicator
LED display
*: Since the response time of X0 to X5 is very fast (for high-speed counter input), the FP0 happens to catch chattering noise as an input signal.
To prevent this, it is recommended that timer instruction should be included in the programme.
Output specifications
1) Relay output type
2) Transistor output type
Item
Description
Item
Description
Output type
Normally open (1 Form A)
Insulation method
Optical coupler
Rated control capacity
2A 250VAC, 2A 30VDC (4.5A/common)
Output type
Open collector
OFF➔ ON
10ms or less
Rated load voltage
24VDC 5 to 24VDC
ON➔ OFF
8ms or less
Load voltage allowable range
4.75 to 26.4VDC
Mechanical
20million operations or more
Max. load current
0.1A/points (at DC26.4V) (1A/common) 1
Response time
Life
100k operations or more
Max. inrush current
0.3A
Surge absorber
Electrical
None
Leakage current at OFF time
100µA or less
Operation indicator
LED display
Max. voltage down at ON time
External power
Voltage
supply
Current
(For internal circuit)
OFF➔ ON
Response time
ON➔ OFF
1.5V or less
Surge absorber
Zener diode
The FP0 series conforms to the following standards under the EMC Directive and
the Low Voltage Directive.
EMC Directive (89/336/EEC)
Low Voltage Directive (73/23/EEC)
EN 50081-2: 1993
EN 50082-2: 1995
VDE 0160: 1988 (EN 50178: 1995)
(Overvoltage Category II,
non-mains-circuit, pollution degree 2)
EN 61131-2: 1995
07/2007
1ms or less
1ms or less
2
LED display
Operating indicator
8 points / common (C16T/C16P,E16T/E16P), 16 points / common (C32T/C32P,
T32CP, E32T/E32P)
2: 50µs or less at Y0, Y1 only
1:
18
21.6 to 26.4VDC
240mA or less
Control FPWIN Pro
Programming According to the International Standard IEC 61131-3
FPWIN Pro is the Panasonic programming software developed according to the international standard
IEC 61131-3 (for Windows 98, NT V4.0, 2000, ME or XP). This new version is a result of experience gained
over many years. We were one of the first PLC manufacturers to offer an IEC 61131-3 programming software,
and we are a leading member of the international organisation PLCopen.
Input and output variables
are defined once in the
global variable list
Multiple address assigment
is caught automatically
by the compiler
Local variables are allocated
automatically by the compiler
Type safe programming using
simple or complex data types
Comfortable programming in the
graphical LD editor (ladder diagram)
Functions can be saved in
libraries for future reuse
One instruction for different
data types (overloaded instructions)
Navigator with tree
representation of called
functions provides an
overview even for very
complex projects
Temporary variables are allocated
and released automatically by the
compiler
Long variable names make the
program self-explanatory
The SFC editor (Sequential
Function Chart) allows you to
easily visualize processes
Additional window for monitoring
and forcing variables
Special functions for controlling the
SFC program from another program
Using aliases for PLC-independent
access to the special data registers, e.g. RTC
The ST editor
(Structured Text)
solves complex
programming tasks
Structuring with
selection statements
Using loops for running
through incoming data
...or arrays
Easy handling of
formulas and
arithmetic
expressions
Using STRING
functions for analyzing
incoming data...
...or for generating
formatted output
strings
The most important highlights at a glance:
" One software for all FP Series PLCs.
" 5 programming languages (instruction list, ladder diagram, function block diagram,
sequential function chart, structured text) available for all PLCs.
" Programme organisation units, task and project management provide clear structure.
" Reuse of ready-made functions and function blocks saves time for programming and debugging.
" Online monitoring and diagnostics.
" Forcing – Turning off input and output contacts via the PC.
" Modem communication for remote programming, service and diagnostics.
" Extensive comments – online documentation created hand in hand with the programme.
" 6 languages are supported: English, German, French, Italian, Spanish and Japanese.
07/2007
Free demonstration CD
Part numbers:
FPWINPROF:
FPWINPROS:
Full version
supports all FP Series PLCs
Small version,
supports FP-e, FP0, FP-X
and FPΣ (Sigma)
19
FP Web-Server
Programme/Operate the FP0 Using a LAN or WAN Network
The multifunctional FP Web-Server provides users with the option of connecting the FP0 or any other
FP Series PLC to the Internet/Intranet thus enabling bi-directional communication. No changes to the PLC
programs are necessary. Simply assign an IP address to the FP Web-Server and connect the PLC to the
FP Web-Server via the serial RS232C interface. A standard browser e.g. MS Internet Explorer or Netscape
Navigator can be used for access at the PC.
The FP Web-Server´s 3 interfaces
" 10BaseT (RJ45, twisted pair)
– connects to the Ethernet at 10 Mbit/s
" RS232C (screw terminal)
– connects to the FPΣ (Sigma) at 1200 to 115.2 kbit/s
" RS232C (SUB-D 9 male)
– connects to a modem (PPP)
Part number
FPWEBD
FPWEBTOOL2D Configurator Software
Highlights
" Web-Server:
" Email:
-PLC data represented as HTML (or XML) pages
-PLC can send emails
-Access via standard Internet browser
-Email via LAN email server or Internet dial-up
-PLC data handling via HTML and Java Applet
-PLC-defined or pre-stored mail text
-Optional: Password protection, IP-Lok security
-PLC data array as attachment to an email
" RS232C device server:
" Modem/Ethernet gateway:
-Ethernet RS232C conversion (MEWTOCOL)
-FP Web-Server can be dialed up via modem
-Transparent RS232C data tunneling via Ethernet
-Programming and visualisation via TCP or UDP
-One remote gateway for multiple FP Web-Servers in
a local Ethernet network
" Modbus- TCP protocol:
" Network time server synchronisation:
-Communication via standard industrial Ethernet
protocol (server and client)
Protocols
Number of browsers
Number of emails
Number of email addresses
Number of PLC per unit
IP address
Security
Operating power
Dimensions
LEDs
Flash memory
Standards fulfilled
20
-PLC real-time clock update via NTP server
TCP/IP, UDP/IP, SMTP, PPP, NTP, FTP, TELNET, HTTP, MEWTOCOL-COM
Up to 64 browsers can be connected to one FP Web-Server
4 predefined in FP Web Flash memory
1 programmable in PLC DT memory as ASCII
4 predefined in FP Web flash memory, 1000 addresses in PLC DT memory,
assuming an average of 32 characters are used per email address and that an
FP0-T32CP is used, which has 16k word memory
Two PLCs can be connected
3-pin port (port number: 9094)
DB8 port (port number: 9095)
DHCP or manually set by software
Password and DIP switch
24VDC, 75mA (max.)
25 x 90 x 60mm (W x H x D)
Power, COM Ethernet connection, COM data exchange
512KBytes
CE, UL, cUL
07/2007
Control CommX, PCWAY, OPC Server
Visualisation Software for Ready Made or Customised Solutions
Control CommX
The connection in ActiveX technology.
■ Connects your Visual Basic application to Panasonic PLCs.
■ Gives you the possibility to easily develop highly customised control solutions.
■ Create your own application very quickly by simply adding the functionality of ActiveX control to your code written with Visual
Basic.
■ No knowledge of MEWTOCOL (Panasonic's PLC communication protocol) needed.
FP Data Analyzer
■ Convenient acquisition and recording of PLC data from inputs, switches,
sensors, outputs, internal and external relays, timers etc.
■ Monitoring PLC data graphically in real time
■ Analyze signal waveform in real time
■ Supports all kind of data types
■ Comprehensive trigger functions
■ Easy and convenient connection to any Panasonic PLC
using the integrated MEWNET Manager
PCWAY
Add-on software for Excel to monitor and change PLC data.
■ The Excel add-in software PCWAY is available for data collection of the networked PLCs.
The contents of the PLC bits and data registers can be simply shown and managed
on Excel worksheets.
■ Settings in PCWAY can be used to switch display contents and character colour
corresponding to contact on/off status and register values, and perform calculations based
on register values. Excel macros are not necessary.
Control FP OPC server 1
The connection between PLC and SCADA software.
■ Provides a standard interface between our FP Series PLCs and various
SCADA/HMI software used to build a monitoring system compliant with
commercially available OPC clients. It is also possible to use OPC automation interface to link our FP series PLCs with Visual Basic.
■ OPC (OLE for Process Control) is an interface standard for linking
software with various companies’ control devices. This standard
allows connections between OPC-compliant products.
,iÌiÊ
ÃÕ«iÀÛÃÀÞÊ
VÌÀ
*>Ì
1: available November 2006
07/2007
21
FP0 Control and Expansion Units
Products and Order Numbers
Control units
Relay output type
10 points
10 points
14 points
14 points
Input 6 points Output 4 points
Screw terminal type
Input 6 points Output 4 points
Screw terminal type
Input 8 points Output 6 points
Screw terminal type
Input 8 points Output 6 points
Screw terminal type
Order number:
FP0-C10RSA
Order number: FP0-C10CRSA
with 2nd RS232C interface
Order number:
FP0-C14RSA
Order number: FP0-C14CRSA
with 2nd RS232C interface
Transistor output type
16 points
16 points
32 points
32 points
Input 8 points Output 8 points
MIL connector type
Input 8 points Output 8 points
MIL connector type
Input 16 points Output 16 points
MIL connector type
Input 16 points Output 16 points
MIL connector type
Order number: FP0-C16PA
(PNP)
FP0-C16TA (NPN)
Expansion units
Order number: FP0-C16CPA (PNP)
FP0-C16CTA (NPN)
with 2nd RS232C
interface
Order number:
FP0-C32PA (PNP)
FP0-C32TA (NPN)
Order number:
FP0-C32CPA (PNP)
FP0-T32CPA (PNP, 10K)
FP0-C32CTA (NPN)
FP0-T32CTA (NPN, 10K)
with 2nd RS232C
interface
Relay output type
Input only type
8 points
16 points
32 points
8 points
16 points
Input 4 points Output 4 points
Screw terminal type
Input 8 points Output 8 points
Screw terminal type
Input 16 points Output 16 points
Screw terminal type
Input 8 points
MIL connector type
Input 16 points
MIL connector type
Order number:
FP0-E8RSA
Order number:
FP0-E16RSA
Order number:
FP0-E32RSA
Order number:
FP0-E8XA
Order number:
FP0-E16XA
Transistor output type
8 points
Output 8 points
MIL connector type
Order number: FP0-E8YPA
(PNP)
FP0-E8YTA (NPN)
16 points
Output 16 points
MIL connector type
Order number: FP0-E16YPA
(PNP)
FP0-E16YTA (NPN)
16 points
32 points
Input 8 points Output 8 points
MIL connector type
Input 16 points Output 16 points
MIL connector type
Order number: FP0-E16PA
(PNP)
FP0-E16TA (NPN)
Order number:
FP0-E32PA (PNP)
FP0-E32TA (NPN)
Notes:
A power cable (order number AFP0581) is enclosed with the control unit and the relay output type expansion units
(Transistor output type upgrade units do not require a power cable).
• Two Phoenix terminals (9-pin) are needed with the relay output type terminal type. A 2.5mm width screwdriver is needed for the wiring.
Have ready a dedicated terminal screwdriver (order number AFP0806: Phoenix order number SZS0, 4 X 2.5 compatible), or equivalent.
• A loose-wiring pressure socket and contact (2 pins with order numbers FP0-C16T/P, E16T/P, and 4 pins with order numbers FP0-C32T/P, E32T/P) are needed with
the transistor output type. A loose-wiring connector pressure contact tool (order number AXY52000) is needed for the wiring.
•
22
07/2007
FP0 Analogue and Networking Units
Products and Order Numbers
Analogue units
3 points
8 points
4 points
4 points
Input 2 points Output 1 points
Screw terminal type
Input 8 points
Output 4 points
Output 4 points
Order number:
FP0-A21A
Screw terminal type
Order number:
Screw terminal type
FP0-A80A
Order number:
FP0-A04V
Screw terminal type
Order number:
FP0-A04I
Temperature control units
4 points
8 points
6 points
Input 4 points
Screw terminal type
Input 8 points
Screw terminal type
Input 6 points
Screw terminal type
Order number:
FP0-TC4
Order number:
FP0-TC8
Order number:
FP0-RTD6
Networking units
PROFIBUS
MEWNET-F
S-LINK CPU
PROFIBUS
DP-Slave or Remote I/O
MEWNET-F
Slave
S-LINK
Master
Order number:
FP0-DPS2
Order number:
FP0-IOL
Order number:
FP Memory Loader
AC power supply
Input
Output
85 to 265VAC
24V DC / 0.7A
Screw terminal type
Order number:
FP0-PSA2
FP0-SL1
Input
Output
85 to 265VAC
24VDC / 2.1A
Screw terminal type
Order number:
Read or write programs from
or to a PLC
FP-PS24-050E
Order number:
07/2007
AFP8670
23
Accessories
Products and Order Numbers
Options
Wiring tools
Parts for attachment
I/O cables & networks
Attachment example
Terminal screwdriver
Necessary when wiring relay output type
& terminals (Phoenix).
Order number:
AFP0806
Slim attachment plate model
Transistor output type I/O cable
Screw-stop attachment plate. Slim model.
Order number:
Loose-wiring cable (10 leads) AWG24 with connectors
attached at one end, 1 set: 2 cables
AFP0803 (set of 10)
2 cable set
2 cable set
Order
number:
Order
number:
AFP0521
AFP0523
Attachment example
Flat attachment plate model
Screw-stop attachment plate. Flat model.
Order number:
Loose-wiring connector pressure
contact tool
Necessary when wiring transistor output
type connectors.
AFP0804 (set of 10)
DIN rail
Input simulator
DIN rail attachment
example
Stopper fitting
Standard DIN rail of width 35mm 1.378inch
and length 1m.
DIN rail stopper fitting.
Order number: AXY52000
Order number: ATA48011
ATA4806
Notes:
(1) One I/O cable set (2 cables) is necessary with the following models: FP0-C10RS, C14RS, E8RS, E16RS.
(2) One I/O cable set (2 cables) is necessary with the following models: FP0-C16T/C16P, E16T/E16P.
(3) Two I/O cable sets (total 4 cables) are necessary with the following models: FP0-C32T/C32P, E32T/E32P.
Order
number:
for FP0 relay output type, 6 switches
Order number:
C-NET adapter S2 type
Adapter for linking to a higher-placed computer.
With 30cm dedicated cable. Power source unnecessary.
Order number:
Additional parts
Terminal socket
Attaches to relay output terminal type.
Additional part.
Order number:
24
sockets
AFP0802(2per
pack )
Loose-wiring pressure socket
Power cable
Transistor output type connectors.
Additional part.
Attaches to control units and relay output
type expansion units. Length: 1m.
Order number:
Order number:
sockets
AFP0807(2per
pack )
07/2007
SWITCH-FP0
1 cable
AFP0581(per
pack )
AFP15402
Programming Tools and Current Consumption List
Products and Order Numbers
Programming software and cables
Control FPWIN Pro
English, German, French, Italian,
Spanish, Japanese menu selectable.
According to IEC 61131-3 Standard
Programming cable
PC 9-pin D-Sub to the PLC
(mini-DIN 5-pin)
Order number:
■ Small version for small PLC only
(FP0, FP-e, FPΣ (Sigma)
• FPWINPROSEN (English manual)
• FPWINPROSDE (German manual)
• FPWINPROSFR (French manual)
Order number:
AFC8513
■ Full version for all FP-Series PLCs
• FPWINPROFEN (English manual)
• FPWINPROFDE (German manual)
• FPWINPROFFR (French manual)
Control FPWIN GR
English, Italian, Spanish,
menu selectable
Ver.2.6
Order number:
■ Full version for all FP-Series PLCs:
• FPWINGRF2 (English manual)
© 1999-2006
Panasonic Electric Works Europe AG
Made in Germany
Software Tool
Order number
Software Tool
Order number
PCWAY with USB port dongle
AFW10031
FP Data Analyzer
AFPS04510D
PCWAY with Printer port dongle
AFW10011
Control Configurator MS, alarm notification system via SMS *
AFPS34610D
Control FP OPC Server (1 licence, available Nov.2006)
AFPS03510D
Control CommX with USB port dongle
AFW20031
Control FP OPC Server (10 licences, available Nov.2006)
AFPS03516D
Control CommX with Printer port dongle
AFW20011
* see www.panasonic-electric-works.com or ask your dealer for the CCMS flyer
Current consumption list
Control unit
Expansion unit
Intelligent unit
Part number
C10 series, C14 series
C16 series
C32 series, T32 series
SL1
E8X
E8YRS
E8YT, E8YP
E8RS
E16RS
E32RS
E16X
E16T, E16P, E16YT, E16YP
E32T, E32P
A21, A04V
A80
A04I
IOL
TC4,TC8, RTD6
PROFIBUS unit
FP programmer
C-NET adapter
FP0-DPS2
AFP1114V2
AFP15402
Current Consumption
Type of unit
Supply to the power supply connector of the control unit
1
Supply to the power supply connector of the expansion and intelligent units 2
100mA or less
40mA or less
60mA or less
150mA or less
10mA or less
10mA or less
15mA or less
20mA or less
20mA or less
–
–
–
–
–
100mA or less
–
50mA or less
100mA or less
20mA or less
20mA or less
25mA or less
40mA or less
20mA or less
20mA or less
20mA or less
200mA or less
–
–
–
100mA or less
60mA or less
130mA or less
30mA or less
40mA or less
25mA
10mA or less
50mA or less
50mA or less
–
100mA or less
–
–
Notes:
1: The current consumption from the power supply connector block of the control unit. Calculate the total current consumption based on the combination of the units.
2: The current consumption from the power supply connector block of the expansion unit and intelligent unit.
07/2007
25
FP0 Series
Power Supplies
Features
■ Small size:
- FP0 power supply: 90 x 60 x 30.4mm
- FP power supply: 115 x 75 x 42mm
■ Maximum output current:
- FP0 power supply: 0.7A (24VDC)
- FP power supply: 2.1A (24VDC)
■ Multiple voltage input:
85 to 265VAC
■ Optimal protection:
overvoltage, overcurrent,
overheating, etc.
■ Global approvals
(UL/cUL, EN, CE-marking)
■ DIN-rail mounting
(FP0 power supply also side
mounting)
Performance specifications
30.4mm
➝
Order number:
FP-PS24-050E
FP0-PSA2
➝
➝
Primary side:
Rated operating voltage
115 / 230VAC
Operating voltage range
85 to 265VAC
Rated operating frequency
50 / 60Hz
Operating frequency range
40 to 70Hz
Inrush current
Current consumption
90mm
< 50A at 55°C
< 50A at 25°C / < 70A at 55°C
145mA (at 230VAC and 0.7A output current)
400mA (at 230VAC and 2.1A output current)
Over voltage protection
PROTECTED
Secondary side:
Rated output voltage
24VDC
Output voltage range
23.5V to 24.5VDC
Nominal output current
➝
Output ripple
FP0 Power Supply
FP0-PSA2
➝
➝
➝
42mm
115mm
Short circuit protected
0 to 2.1A
< 60mVpp
Electronic, automatic restart mode
< 240mVpp
Continuous
Over voltage protected
Over load protected
Yes
Yes (switch off at approx. 0.8A and more)
Yes (switch off at approx. 3.5A and more)
Min. 20ms at 230VAC
Min. 110ms at 230VAC
–
Yes
Holding time
Power OK signal
General specifications
Ambient temperature
0°C to +55°C
Storage temperature
-20 °C to +70 °C
Ambient humidity
5 to 85% non-condensing
Storage humidity
5 to 85% non-condensing
Vibration resistance
10 to 55Hz, 1 cycle/min.: double amplitude of 0.75mm, 10 min. on 3 axes
Shock resistance
10g min., 4 times on 3 axes
7 years at nom. load, 25°C ambient temperature,
20000 h at 55°C with full load/continuous operation
Life time min.
Mounting
➝
FP Power Supply
FP-PS24-050 E
Notes:
• Mounting distance between the FP0 power supply and the FP0 CPU is needed to
permit heat radiation for the FP0-CPU
• For side mounting, 2 additional
blue clips are needed: order part-no.
677-021-17101 (1pce.) for FP0-PSA2
• Mounting distance between the power
supply FP-PS24-050E and other devices
is needed for cooling / heat radiation.
26
2.1A
0.7A
0 to 0.7A
Output current range
DIN rail or FP0 flat attachement plate
DIN rail
90 x 60 x 30.4mm
115 x 75 x 42mm
Size
Input connection AC side
Output connection DC side
Status display
MC connector, 2 pin
2 pin
MC connector, 6 pin, 3 pin for „+“ and 3 pin for „-“
5 pin, 2 pin for „+” and 2 pin for „-”; 1 pin Power OK
LED (green) at the front side for the secondary voltage indication
Standards
EMC
LVD
Others
EN 50082-2, EN50082-1,
EN 55011/B, EN 55022/B,
EN 50081-2, EN 50081-1
EN 61000-4-2, -4-3, -4-4, -4-5, -4-6, -4-11
EN 60950, EN 50178
EN 60950, EN 50178
(overvoltage category 3)
(overvoltage category 2)
UL Recognized according to UL 508, UL 1950,
cUL Recognized according to CAN/CSA-C22.2 No. 950.95
IP30
Protection
07/2007
IP20 outside/ IP67 inside
FP0 Product Overview
Order Numbers
Product Name
Part Number
1. Control Units
FP0-C10RS, 6 Inputs / 4 Outputs (p+n / Relay)
FP0-C10CRS, 6 Inputs / 4 Outputs (p+n / Relay), RS232 COM port Interface
FP0-C14RS, 8 Inputs / 6 Outputs (p+n / Relay)
FP0-C14CRS, 8 Inputs / 6 Outputs (p+n / Relay), RS232 COM port Interface
FP0-C16P, 8 Inputs / 8 Outputs (p+n / Transistor PNP)
FP0-C16CP, 8 Inputs / 8 Outputs (p+n / Transistor PNP), RS232 COM port Interface
FP0-C32P, 16 Inputs / 16 Outputs (p+n / Transistor PNP)
FP0-C32CP, 16 Inputs / 16 Outputs (p+n / Transistor PNP), RS232 COM port Interface
FP0-C16T, 8 Inputs / 8 Outputs (p+n / Transistor NPN)
FP0-C16CT, 8 Inputs / 8 Outputs (p+n / Transistor NPN), RS232 COM port Interface
FP0-C32T, 16 Inputs / 16 Outputs (p+n / Transistor NPN)
FP0-C32CT, 16 Inputs / 16 Outputs (p+n / Transistor NPN), RS232 COM port Interface
FP0-T32CP, 16 Inputs / 16 Outputs (p+n / Transistor PNP), RS232 COM port Interface, 10 000 steps Program memory
FP0-T32CT, 16 Inputs / 16 Outputs (p+n / Transistor NPN), RS232 COM port Interface, 10 000 steps Program memory
FP0-SL1, S-LINK CPU, Master
FP0-C10RSA
FP0-C10CRSA
FP0-C14RSA
FP0-C14CRSA
FP0-C16PA
FP0-C16CPA
FP0-C32PA
FP0-C32CPA
FP0-C16TA
FP0-C16CTA
FP0-C32TA
FP0-C32CTA
FP0-T32CPA
FP0-T32CTA
FP0-SL1
2. Expansion Units
FP0-E8RS, 4 Inputs / 4 Outputs (p+n / Relay)
FP0-E8X, 8 Inputs (p+n)
FP0-E8YP, 8 Outputs (Transistor PNP)
FP0-E8YT, 8 Outputs (Transistor NPN)
FP0-E16RS, 8 Inputs / 8 Outputs (p+n / Relay)
FP0-E16P, 8 Inputs / 8 Outputs (p+n / Transistor PNP)
FP0-E16T, 8 Inputs / 8 Outputs (p+n / Transistor NPN)
FP0-E16X, 16 Inputs (p+n)
FP0-E16YP, 16 Outputs (Transistor PNP)
FP0-E16YT, 16 Outputs (Transistor NPN)
FP0-E32RS, 16 Inputs / 16 Outputs (p+n / Relay)
FP0-E32P, 16 Inputs / 16 Outputs (p+n / Transistor PNP)
FP0-E32T, 16 Inputs / 16 Outputs (p+n / Transistor NPN)
FP0-A21, 2 analogue inputs / 1 analogue output
FP0-A80, 8 analogue inputs
FP0-TC4, 4 thermocouple inputs
FP0-TC8, 8 thermocouple inputs
FP0-RTD6, 6 RTD Inputs, Pt100, Pt1000, Ni1000
FP0-E8RSA
FP0-E8XA
FP0-E8YPA
FP0-E8YTA
FP0-E16RSA
FP0-E16PA
FP0-E16TA
FP0-E16XA
FP0-E16YPA
FP0-E16YTA
FP0-E32RS
FP0-E32PA
FP0-E32TA
FP0-A80A
FP0-TC4
FP0-TC8
FP0-RTD6
3. AC Power Supply
FP0-AC Power Supply 24VDC / 0.7A
FP0-PSA2
4. Network
FPWEBD
FP0-DPS2
FP0-IOL
FP0-SL1
AFP15402
AFP8536
FP Web-Server, Web-Server for Intranet/Internet LAN Ethernet, Email
FP0-DPS2, PROFIBUS DP Slave or Remote I/O unit
FP0-IOL, MEWNET-F Slave unit, I/O link
FP0-SL1, S-LINK CPU, Master
C-NET S2 Adapter (Multi drop network slave adapter)
C-NET Adapter (RS232/422 PORS485 Interface adapter), 230VAC
5. Programming Tools
Control FPWIN Pro programming software FP0/FP-e/FPΣ (Sigma), FP-X, including English manual
Control FPWIN Pro programming software for all FP-Series PLC (FP0/FP-e, FPΣ (Sigma), FP-X, FP2/2SH) including English manual
Control FPWIN GR programming software for all FP-Series PLC (FP0/FP-e, FPΣ (Sigma), FP-X, FP2/2SH) including English manual
Handheld programmer for FP0 and other FP programmable controllers
FP0 programming cable PC TOOL port (SUB-D/MiniDIN5), 3m
FP0 programming cable Handheld programmer TOOL port (SUB-D15/MiniDIN5), 1m
FP0 programming cable Handheld programmer TOOL port (SUB-D15/MiniDIN5), 3m
FPWINPROS EN
FPWINPROF EN
FPWINGRF
AFP1114V2
AFC8513
AFC8521
AFC8523
6. Additional Parts
Transistor output type I/O cable, Loose-wiring cable (10 leads), 1 set: 2 cables, 1m
Transistor output type I/O cable, Loose-wiring cable (10 leads), 1 set: 2 cables, 3m
Power cable, 1m, 1 cable per pack
Slim attachment plate model (set of 10)
Flat attachment plate model (set of 10)
Terminal socket (2 sockets per pack)
Loose-wiring pressure socket (2 sockets per pack)
Loose-wiring connector pressure contact tool
Input simulator for FP0 relay output type, 6 switches
07/2007
AFP0521
AFP0523
AFP0581
AFP0803
AFP0804
AFP0802
AFP0807
AXY52000
SWITCH-FP0
27
Global Network Services
Global Network
North America
Europe
Asia Pacific
China
Japan
Panasonic Electric Works
Please contact our Global Sales Companies in:
Europe
! Headquarters
! Austria
Panasonic Electric Works Europe AG
Panasonic Electric Works Austria GmbH
PEW Electronic Materials Europe GmbH
! Benelux
Panasonic Electric Works
Sales Western Europe B.V.
! Czech Republic Panasonic Electric Works Czech s.r.o.
! France
Panasonic Electric Works
Sales Western Europe B.V.
! Germany
Panasonic Electric Works Deutschland GmbH
! Ireland
Panasonic Electric Works UK Ltd.
! Italy
Panasonic Electric Works Italia s.r.l.
PEW Building Materials Europe s.r.l.
! Nordic Countries Panasonic Electric Works Nordic AB
PEW Fire & Security Technology Europe AB
! Portugal
Panasonic Electric Works España S.A.
! Spain
Panasonic Electric Works España S.A.
! Switzerland
Panasonic Electric Works Schweiz AG
! United Kingdom Panasonic Electric Works UK Ltd.
Rudolf-Diesel-Ring 2, 83607 Holzkirchen, Tel. (08024) 648-0, Fax (08024) 648-111, www.panasonic-electric-works.com
Josef Madersperger Str. 2, 2362 Biedermannsdorf, Tel. (0 22 36) 2 68 46, Fax (0 22 36) 4 61 33, www.panasonic-electric-works.at
Ennshafenstraße 9, 4470 Enns, Tel. (0 72 23) 8 83, Fax (0 72 23) 8 83 33, www.panasonic-electronic-materials.com
De Rijn 4, (Postbus 211), 5684 PJ Best, (5680 AE Best), Netherlands, Tel. (0499) 37 27 27, Fax (0499) 372185, www.panasonic-electric-works.nl
Prumtyslová 1, 34815 Planá, Tel. 374 799 990, Fax 374 799 999, www.panasonic-electric-works.cz
French Branch Office, B.P. 44, 91371 Verrières le Buisson CEDEX, Tél. 01 60135757, Fax 01 60135758, www.panasonic-electric-works.fr
Rudolf-Diesel-Ring 2, 83607 Holzkirchen, Tel. (08024) 648-0, Fax (08024) 648-555, www.panasonic-electric-works.de
Dublin, Tel. (01) 4600969, Fax (01) 4601131, www.panasonic-electric-works.co.uk
Via del Commercio 3-5 (Z.I. Ferlina), 37012 Bussolengo (VR), Tel. (045) 6752711, Fax (045) 6700444, www.panasonic-electric-works.it
Piazza della Repubblica 24, 20154 Milano (MI), Tel. (02) 29005391, Fax (02) 29003466, www.panasonic-building-materials.com
Sjöängsvägen 10, 19272 Sollentuna, Sweden, Tel. (08) 59476680, Fax (08) 59476690, www.panasonic-electric-works.se
Citadellsvägen 23, 21118 Malmö, Tel. (040) 6977000, Fax (040) 6977099, www.panasonic-fire-security.com
Portuguese Branch Office, Avda Adelino Amaro da Costa 728 R/C J, 2750-277 Cascais, Tel. (21) 4812520, Fax (21) 4812529
Barajas Park, San Severo 20, 28042 Madrid, Tel. (91) 3293875, Fax (91) 3292976, www.panasonic-electric-works.es
Grundstrasse 8, 6343 Rotkreuz, Tel. (041) 7997050, Fax (041) 7997055, www.panasonic-electric-works.ch
Sunrise Parkway, Linford Wood, Milton Keynes, MK14 6LF, Tel. (01908) 231555, Fax (01908) 231599, www.panasonic-electric-works.co.uk
North & South America
! USA
PEW Corporation of America
629 Central Avenue, New Providence, N.J. 07974, Tel. 1-908-464-3550, Fax 1-908-464-8513, www.pewa.panasonic.com
Asia Pacific / China / Japan
! China
Panasonic Electric Works (China) Co., Ltd.
! Hong Kong
Panasonic Electric Works
(Hong Kong) Co., Ltd.
Matsushita Electric Works, Ltd.
Panasonic Electric Works Asia Pacific Pte. Ltd.
! Japan
! Singapore
16
Level 2, Tower W3, The Towers Oriental Plaza, No. 2, East Chang An Ave., Dong Cheng District, Beijing 100738, Tel. (010) 8518-5988,
Fax (010) 8518-1297
RM1205-9, 12/F, Tower 2, The Gateway, 25 Canton Road, Tsimshatsui, Kowloon, Hong Kong, Tel. (0852) 2956-3118, Fax (0852) 2956-0398
1048 Kadoma, Kadoma-shi, Osaka 571-8686, Japan, Tel. (06) 6908-1050, Fax (06) 6908-5781, www.mew.co.jp/e-acg/
101 Thomson Road, #25-03/05, United Square, Singapore 307591, Tel. (06255) 5473, Fax (06253) 5689
07/2007
C opyright © 2006 • Printe d in G ermany
4093 eu en 09/06