NEW
Programmable Controller
FP7 SERIES
Conforming to
EMC Directive
FP7 series analog input unit
with high-speed processing of multiple channels now added!
High speed, easy collection and processing of analog signals
Not only equipped for high-speed processing, the FP7 is also easy to
operate and to configure.
NEW
Analog input unit
high-speed and multi-channel type
AFP7AD8
High-speed conversion
25 µs/channel
Averaging processing
Number of times, time, moving
Digital processing
Scale conversion setting / offset setting / gain setting
Setting
Software tool for easy operation
High-speed sampling that doesn’t depend on CPU unit scanning.
Sampling and data collection in the analog unit!
Use the AFP7AD8 for measurement applications because with the fixed
cycle, analog signal can be held in the buffer.
Dependent on scan of CPU
High-speed and
high-accuracy type
also available.
The scan gets delayed when the CPU
slows down due to other processes and
sampling becomes sporadic.
For details, please see the
back cover.
Occurrence of failure
Sampling in the analog unit
AFP7DA4H
AFP7AD4H
Accurate sampling possible with fixed
cycle.
Accurate sampling!
Expansion unit capable of bus expansion and distributed installation
Connect a maximum of 3 blocks and a total of 64 units
Three blocks can be expanded on one CPU unit. Distributed installation
achieved while maintaining high-speed bus transmission.
Expansion master unit
Total
CPU
unit
64 units
Previous
Maximum of 16 units for each unit
・・・・・・・・・
Expansion cable
Max.
3 blocks
NEW
NEW
End unit
(included)
Expansion master unit
Expansion slave unit
AFP7EXPM
AFP7EXPS
2014.10
panasonic.net/id/pidsx/global
Expansion slave units
Max. 16 units
・・・・・・・・・
Max. 16 units
・・・・・・・・・
Max. 16 units
・・・・・・・・・
*If required, a power supply unit can be connected on the left side of the expansion unit.
Pr o g r a mma b l e
c o n tr o lle r
FP7 SERIES
SPECIFICATIONS
Analog input unit (high-speed and multi-channel type)
AFP7AD8
8 channels
-10 to 10 V DC (resolution: 1/62,500)
0 to 10 V DC (resolution: 1/31,250)
0 to 5 V DC (resolution: 1/31,250)
1 to 5 V DC (resolution: 1/25,000) (Note)
0 to 20 mA (resolution: 1/31,250)
4 to 20 mA (resolution: 1/25,000) (Note)
Part No.
Number of channels
Voltage
Input range
(resolution)
Current
Conversion
speed
Voltage / current
Insulation method
Rated input voltage /
rated input current
Input impedance
Trigger input Operating voltage range
Min. ON voltage / Min. ON current
section
Max. OFF voltage / Max. OFF current
Response OFF→ON
time
ON→OFF
Input points per common
Current consumption
Net weight
25 μs/channel
±0.1 % F.S. or less (at 25 °C 77 °F)
±0.3 % F.S. or less (at 0 to 55 °C 32 to 131 °F)
Overall accuracy
Input
impedance
Part No.
Buffer function
Voltage input / Current input
1 MΩ approx. / 250 Ω
-15 to 15 V DC voltage input
-2 to 30 mA current input
Max. input range
Between input terminals and
internal circuit
Between analog input and
trigger input terminal
Conversion execution / non-execution
channel setting
Input range change method
Number of times
Averaging Time duration
Moving
Digital
processing Scale conversion setting
Offset setting
Gain setting
Insulation
method
Photocoupler and
isolated DC / DC converter
Part No.
Block
Unit
Distance between
Transmission blocks
distance
Total extension
Number of
expansion
Selectable per channel
Setting range: 2 to 60,000 times
Time setting range: 1 to 1,500 ms
Setting range: 2 to 2,000 times
Any value within ±30,000
Any value within ±3,000
Any value within 9,000 to 11,000
Possible to make settings on a channel-byMax. and min. value holding
channel basis
Possible to make settings on a channel-byComparison of upper and lower limit values
channel basis (hysteresis)
When less than 2.8 mA (only when current
Broken wire detection
input range 4 to 20 mA is set.)
Analog device lineup
Analog input and output units
Product name
FP7 analog input unit
(high-speed and multi-channel type)
FP7 analog input unit
(high-speed and high-accuracy type)
FP7 analog output unit
(high-speed and high-accuracy type)
24 V DC / 12 mA approx. (at 24 V DC)
2 kΩ approx.
21.6 to 26.4 V DC
19.2 V / 3.5 mA
5 V / 1.5 mA
0.1 ms or less
0.1 ms or less
1 point/common
85 mA or less
130 g approx.
Functions for the expansion unit
Selectable per channel unit
Note: The full scale (F.S.) on the accuracy of an analog voltage input range from +1 to +5 V and that of
an analog current input range from +4 to +20 mA are 0 to +5 V and 0 to +20 mA, respectively.
AFP7AD8
3 trigger types: Soft trigger,
external trigger and input level
Photocoupler
Current consumption (Note 2)
Max. allowable current
Expansion bus connector
Net weight
Accessories
AFP7EXPM
AFP7EXPS
Max. 3 blocks (total 4 blocks)
Max. 48 units (total 64 units)
Length of expansion cable (0.5 m 1.640 ft,
1 m 3.281 ft, 3 m 9.843 ft and 10 m 32.808 ft)
Max. 30 m 98.425 ft
(Expansion cable × 3 expansions) (Note 1)
120 mA or less
100 mA or less
3.0 A (at 24 V DC
–
power supply terminal)
MIL 40 pins
MIL 40 pins × 2
200 g approx.
120 g approx.
(including end unit)
Power supply cable
(Part No.: AFPG805)
–
End unit
(Part No.: AFP7END)
Notes: 1) Can support a maximum of 100 m 328.084 ft length between blocks. Please inquire with us
for details.
2) Differs depending on power supply voltage and number of expansion units.
Specifications
Number of channels
Voltage / current, conversion rate: 25 μs/channel, resolution: max. 16 bits, accuracy: ±0.1 % F.S. or
8 channels
less (at 25 °C 77 °F)
Voltage / current, conversion rate: 25 μs/channel, resolution: max. 16 bits, accuracy: ±0.05 % F.S. or
4 channels
less (at 25 °C 77 °F) / insulation between channels
Voltage / current, conversion rate: 25 μs/channel, resolution: max. 16 bits, accuracy: ±0.1 % F.S. or
4 channels
less (at 25 °C 77 °F) / insulation between channels
Part No.
AFP7AD8
AFP7AD4H
AFP7DA4H
Temperature input units
Product name
FP7 Thermocouple multiple analog
input unit
FP7 Resistance temperature detector
input unit
Specifications
Number of channels
Thermocouple (K, J, T, N, R, S, B, E, PLII and WRe5-26), Voltage / current, conversion rate: 5 ms/channel,
8 channels
resolution: max. 16 bits, accuracy: ±0.1 % F.S. or less (at 25 °C 77 °F), insulation between channels
Resistance temperature detector (Pt100, JPt100 and Pt1000), conversion rate: 25 ms/channel,
8 channels
accuracy: ±0.1 % F.S. or less (at 25 °C 77 °F), insulation between channels
Part No.
AFP7TC8
AFP7RTD8
Add-on cassettes
Product name
FP7 function cassettes
Specifications
Analog input, 2 channels, voltage / current
Analog input and output, input: 2 channels, output: 1 channel
Thermocouple input, 2 channels, K / J
Part No.
AFP7FCAD2
AFP7FCA21
AFP7FCTC2
Expansion unit lineup
Expansion units
Product name
FP7 expansion master unit
FP7 expansion slave unit
Expansion cables
Specifications
Expansion of up to 3 slave units possible
Up to 16 units can be connected to 1 slave unit.
Length: 0.5 m 1.640 ft
Length: 1 m 3.281 ft
Length: 3 m 9.843 ft
Length: 10 m 32.808 ft
Part No.
AFP7EXPM
AFP7EXPS
AFP7EXPCR5
AFP7EXPC01
AFP7EXPC03
AFP7EXPC10
New functions
Supports the following functions from Ver. 2.4 of Control FPWIN GR7.
• Mnemonic ladder
2014.10
• Simulation
• Data editor
panasonic.net/id/pidsx/global
Panasonic Industrial Devices SUNX Co., Ltd.
Global Sales Department
No. LCE-FP7V2ANALOG-7 October, 2014
2431-1 Ushiyama-cho, Kasugai-shi, Aichi, 486-0901, Japan
■Telephone: +81-568-33-7861 ■Facsimile: +81-568-33-8591