Your Simple, Accurate and Economical
Temperature Controller
Compact temperature controller (DIN
48×24) that can support pattern control
Additions to KT2 series
KT Temperature
Controller
Broad lineup of temperature controllers
allow you to satisfy application and space requirements.
KT2 Series
KT4 Series
[48×24×98.5mm]
[48×48×95mm]
KT7 Series
[22.5×75×100mm]
KT4H
KT8 Series
KT9 Series
KT4H/B Series
[48×96×98.5mm]
[96×96×98.5mm]
[48×48×56mm]
KT4B
Compliance with RoHS Directive
FEATURES
1. Multi-input
Versatile thermocouple, RTD, DC voltage
and DC current input for temperature
detecting sensors
2. Simple operation enables highly
accurate temperature control
All required operations can be enabled
by the front keys and highly accurate PID
control mode ensures an input span of
±0.2%.
3. DIN Rail mounting types are aligned
taking global market demand into
consideration
The KT7 series is equipped with DIN rail
mounting complying to DIN standards.
Furthermore, because its control panel is
compact, the KT7 saves space.
2009.10
4. Nine step pattern control possible.
For KT2 series, despite DIN 48 × 24 size,
selection is possible of control with fixed
set point and nine step pattern control.
5. Meets market demands for costeffectiveness
The KT series offers both economy and
high performance.
6. The KT series complies with UL,
CSA standards and CE marking.
7. Improved visibility and ease of
operation
More compact than before
The KT4H/KT4B series features the
largest PV digit size in the industry.
Visibility is improved with an 11-segment
display. Connectable to a PC, it offers a
full range of control and communication
functions.
panasonic-electric-works.net/ac
8. Communication specification uses
RS485 (Modbus protocol)
(Sample System Configuration)
FPΣ Programmable Controller
(Panasonic Electric Works)
RS-485
Up to 31 units can be connected
* In the configuration above, the FPΣ requires a
communication cassette (FPG-COM3).
* Modbus is a communication protocol developed for
PLCs by Modicon Inc.
KT (AKT2,4,7,8,9,4H,4B)
PRODUCT TYPES
1. KT2 Series
Base
model
Power
supply
Sensor
input
Control
output
Alarm
output
Heating/
cooling
control
Heater
burnout
alarm
Communication
function
AKT2
1
2
1
1
2
3
2
0
0
Blank
1
1
0
Blank
1
0
0
1
0
1
0
1
Description
48 × 24 × 98.5mm
100 to 240V AC
Must be
specified
24V AC/DC
Multi-input (Thermocouple, RTD, DC current and DC voltage)
Relay contact output 1a 3A 250V AC
Must be
Non-contact voltage output (for SSR drive)
specified
Current output
When both heating/cooling and communication functions are not added:
Relay contact output (alarm 1): Can be used
Open collector output (alarm 2): Can be used
When only heating/cooling function is added:
Relay contact output (alarm 1): Cannot be used
Open collector output (alarm 2): Can be used
When only communication function is added:
Relay contact output (alarm 1): Can be used
Open collector output (alarm 2): Cannot be used
When both heating/cooling and communication functions are added:
Relay contact output (alarm 1): Cannot be used
Open collector output (alarm 2): Cannot be used
* When heating/cooling is selected, alarm output 1 cannot be used.
When the communication function is selected, alarm output 2 cannot be used.
• Part No.
(Ex) Part No. when the optional functions (of Heating/Cooling control: relay contact output + Communications function) is added on to
the basic model are as follows; Part No.: AKT21110101
• Options
Product name
Shunt resistor (for Current input)
Terminal cover
Part No.
AKT4810
AKT2801
Note: When Current input is specified, a shunt resistor (sold separately) is required.
2. KT4 Series
Base
model
Power
supply
Sensor
input
Control
output
Alarm
output
Heating/
cooling
control
Heater
burnout
alarm
Communications
function
AKT4
1
2
1
1
2
3
1
2
0
4
0
1
2
3
4
1
Description
48 × 48 × 95mm
100 to 240V AC
24V AC/DC
Multi-input (Thermocouple, RTD, DC Voltage and DC Current)
Relay contact output 1a 3A 250V AC
Non-contact voltage output (for SSR drive)
Current output
Relay contact output 1a (Alarm output 1)
Relay contact output 1a (Alarm output 2)
Not available
SSR output 0.3A 250V AC (Heating/Cooling control not supported when 2
alarm output points are selected)
Not available
5A (Heater burn-out alarm not supported when control output is current
output type/not supported when heating and cooling control is selected)
10A (Heater burn-out alarm not supported when control output is current
output type/not supported when heating and cooling control is selected)
20A (Heater burn-out alarm not supported when control output is current
output type/not supported when heating and cooling control is selected)
50A (Heater burn-out alarm not supported when control output is current
output type/not supported when heating and cooling control is selected)
Not available
Available
Notes: 1. CT1 or CT2 for current detection is provided as an accessory when heater burn-out alarm function is added.
2. Event output will be shared if you choose alarm output 2 and the heater burnout alarm.
• Part No.
(Ex) Part No. when the optional functions (of Heating/Cooling control: SSR output + Communications function) is added on to the
basic model are as follows; Part No.: AKT41111401
• Options
Product name
Shunt resistor (for Current input)
Terminal cover
Part No.
AKT4810
AKT4801
Note: When Current input is specified, a shunt resistor (sold separately) is required.
2
KT (AKT2,4,7,8,9,4H,4B)
3. KT8 Series
Base
model
AKT8
Power
supply
Sensor
input
Control
output
Alarm
output
Heating/cool- Heater burn- Communicaing control
out alarm tions function
1
2
1
1
2
3
1
2
0
1
2
3
0
1
2
3
4
1
Description
48 × 96 × 98.5mm
100 to 240V AC
24V AC/DC
Multi-input (Thermocouple, RTD, DC Voltage and DC Current)
Relay contact output 1a1b 3A 250V AC
Non-contact voltage output (for SSR drive)
Current output
Relay contact output 1a (Alarm output 1)
Relay contact output 1a (Alarm output 2)
Not available
Relay contact output 1a
Non-contact voltage output (for SSR drive)
Current output
Not available
5A (Heater burn-out alarm not supported when control output is current
output type/not supported when heating and cooling control is selected)
10A (Heater burn-out alarm not supported when control output is current
output type/not supported when heating and cooling control is selected)
20A (Heater burn-out alarm not supported when control output is current
output type/not supported when heating and cooling control is selected)
50A (Heater burn-out alarm not supported when control output is current
output type/not supported when heating and cooling control is selected)
Not available
Available
Notes: 1. CT1 or CT2 for current detection is provided as an accessory when heater burn-out alarm function is added.
2. If a communication function is added, second main setup is not possible
• Part No.
(Ex) Part No. when the optional functions (of Alarm output; Alarm output 2 + Heating/Cooling control: Current output) are added on to
the basic model are as follows; Part No.: AKT8111230
• Options
Product name
Shunt resistor (for Current input)
Terminal cover
Part No.
AKT4810
AKT8801
Note: When Current input is specified, a shunt resistor (sold separately) is required.
4. KT9 Series
Base
model
AKT9
Power
supply
Sensor
input
Control
output
Alarm
output
Heating/cool- Heater burn- Communicaing control
out alarm tions function
1
2
1
1
2
3
1
2
0
1
2
3
0
1
2
3
4
1
Description
96 × 96 × 98.5mm
100 to 240V AC
24V AC/DC
Multi-input (Thermocouple, RTD, DC Voltage and DC Current)
Relay contact output 1a1b 3A 250V AC
Non-contact voltage output (for SSR drive)
Current output
Relay contact output 1a (Alarm output 1)
Relay contact output 1a (Alarm output 2)
Not available
Relay contact output 1a
Non-contact voltage output (for SSR drive)
Current output
Not available
5A (Heater burn-out alarm not supported when control output is current
output type/not supported when heating and cooling control is selected)
10A (Heater burn-out alarm not supported when control output is current
output type/not supported when heating and cooling control is selected)
20A (Heater burn-out alarm not supported when control output is current
output type/not supported when heating and cooling control is selected)
50A (Heater burn-out alarm not supported when control output is current
output type/not supported when heating and cooling control is selected)
Not available
Available
Notes: 1. CT1 or CT2 for current detection is provided as an accessory when heater burn-out alarm function is added.
2. If a communication function is added, second main setup is not possible
• Part No.
(Ex) Part No. when the optional functions (of Alarm output; Alarm output 2 + Heating/Cooling control: Non-contact voltage output) are
added on to the basic model are as follows; Part No.: AKT9111220
• Options
Product name
Shunt resistor (for Current input)
Terminal cover
Part No.
AKT4810
AKT9801
Note: When Current input is specified, a shunt resistor (sold separately) is required.
3
KT (AKT2,4,7,8,9,4H,4B)
5. KT7 Series
Base
model
Power
supply
Sensor
input
Control
output
Heating/
cooling
control
Alarm
output
Heater
burnout
alarm
Communications
function
AKT7
1
2
1
1
2
3
1
0
0
1
2
3
4
1
Description
22.5 × 75 × 100mm
100 to 240V AC
24V AC/DC
Multi-input (Thermocouple, RTD, DC Voltage and DC Current)
Relay contact output 1a 3A 250V AC
Non-contact voltage output (for SSR drive)
Current output
Open collector output (Alarm output 1)
Not available (without Heating/Cooling function)
Not available
5A (not available for the Current output type) Open collector output
10A (not available for the Current output type) Open collector output
20A (not available for the Current output type) Open collector output
50A (not available for the Current output type) Open collector output
Not available
Available
Note: CT1 or CT2 for current detection is provided as an accessory when heater burn-out alarm function is added.
• Part No.
(Ex) Part No. when the optional function (of Heater burnout alarm: 10A) is added on to the base model are as follows;
Part No.: AKT7111102
• Options
Product name
Shunt resistor (for Current input)
Part No.
AKT4811
Note: When Current input is specified, a shunt resistor (sold separately) is required.
6. KT4H Series
Base
model
Power
supply
Sensor
input
Control
output
Alarm
output
Heating/
cooling
control
Heater
burnout
alarm
Communications
function
Description
AKT4H
1
2
1
1
2
3
0
1
2
0
0
1
2
0
0
0
1 or 2
0
3
1 or 2
0
4
1 or 2
0
5
1 or 2
0
6
Blank
1
2
100 to 240V AC
24V AC/DC
Multi-input (Thermocouple, RTD, DC Voltage and DC Current)
Relay contact
Non-contact voltage (for SSR drive)
Heater burn-out alarm not possible.
DC current
1 point (1a)
2 points (1a + 1a)
Heating/cooling control output not possible.
Not available
Relay contact
Heater burn-out alarm not possible.
Non-contact voltage (for SSR drive) Heater burn-out alarm not possible.
Not available
Single phase 20A (Heater burn-out alarm not supported when control output is DC
output type/not supported when heating and cooling control is selected)
Single phase 50A (Heater burn-out alarm not supported when control output is DC
output type/not supported when heating and cooling control is selected)
Three phase 20A (Heater burn-out alarm not supported when control output is DC
output type/not supported when heating and cooling control is selected)
Three phase 50A (Heater burn-out alarm not supported when control output is DC
output type/not supported when heating and cooling control is selected)
Not available
Serial communication RS-485
Contact input
Notes: 1. CT1 or CT2 for current transformer is provided as an accessory when heater burn-out alarm function is added.
2. Under some conditions, option functions (shaded items) may not be available; please check the “Descriptions” of the above table for non-functioning circumstances.
• Part No.
(Ex) Part No. when the optional functions (Heating/Cooling control + communication function) are added on to the basic model are as
follows; Part No.: AKT4H1111101
• Options
Product name
Shunt resistor (for Current input)
Terminal cover
Tool cable
• Setting software
Part No.
AKT4810
AKT4H801
AKT4H820
Product name
KT Monitor
Description
Editing of all types of data, File saving
Monitoring of readings, Saving of log files
Note: Please download user manual from the company website.
4
Remark
Available for download at no charge from
company website.
http://www.panasonic-electric-works.net/ac
KT (AKT2,4,7,8,9,4H,4B)
7. KT4B Series
Base
model
Power supply
Sensor input
Control output
Alarm output
Heating/cooling
control
Heater burnout
alarm
1
(1 point)
1
(Relay contact)
2
(2 points)
1
(1 point)
AKT4B
1
(100 to 240V AC)
1
(Multi-input)
0
(Not available)
2
(Non-contact voltage)
2
(2 points)
1
(1 point)
3
(DC current)
2
(2 points)
*Please inquire if you need specifications not included in the model numbers above.
*Use RS485 for serial communication.
Example Model No.: AKT4B111100
Specifications: Power supply 100 to 240V AC, Heating/cooling control: Not available,
Sensor input: Multi-input, Heater burnout alarm: Not available,
Control output: Relay contact, Communications function: Not available,
Alarm output: 1 point
0
(Not available)
Communications
function
Blank
(Not available)
1
(Serial communication)
Blank
(Not available)
1
(Serial communication)
Blank
(Not available)
1
(Serial communication)
Blank
(Not available)
1
(Serial communication)
Blank
(Not available)
1
(Serial communication)
Blank
(Not available)
1
(Serial communication)
Model No.
AKT4B111100
AKT4B1111001
AKT4B111200
AKT4B1112001
AKT4B112100
AKT4B1121001
AKT4B112200
AKT4B1122001
AKT4B113100
AKT4B1131001
AKT4B113200
AKT4B1132001
• Options (Common for KT4H and KT4B)
Product name
Shunt resistor (for Current input)
Terminal cover
Tool cable
Model No.
AKT4810
AKT4H801
AKT4H820
5
KT (AKT2,4,7,8,9,4H,4B)
RATING & SPECIFICATIONS
Display
Size (W × H × D)
KT2
48 × 24 × 98.5mm
Supply voltage (Must be specified)
Frequency
Power consumption
Input type
Approx. 5VA
K
Specifications
KT8
KT9
48 × 96 × 98.5mm 96 × 96 × 98.5mm
100 to 240V AC
24V AC/DC
50/60Hz
Approx. 8VA
Input range
–200 to 1370°C (–320 to 2500°F)
KT7
22.5 × 75 × 100mm
KT4H/4B
48 × 48 × 62mm
Approx. 6VA
Approx. 8VA
–199.9 to 400.0°C (–199.9 to 750.0°F)
J
R
S
Thermocouple B
E
–200.0 to 400.0°C
(–320 to 750.0°F)
–200 to 1000°C (–320 to 1800°F)
0 to 1760°C (0 to 3200°F)
0 to 1760°C (0 to 3200°F)
0 to 1820°C (0 to 3300°F)
–200 to 800°C (–320 to 1500°F)
T
–199.9 to 400.0°C (–199.9 to 750.0°F)
N
PL-II
C (W/Re5-26)
–200.0 to 400.0°C
(–320 to 750.0°F)
–200 to 1300°C (–320 to 2300°F)
0 to 1390°C (0 to 2500°F)
0 to 2315°C (0 to 4200°F)
–200 to 850°C (–300 to 1500°F)
Pt100
–199.9 to 850.0°C (–199.9 to 999.9°F)
RTD
–200.0 to 850.0°C
(–320.0 to 1500.0°F)
–200 to 500°C (–300 to 900°F)
JPt100
4 to 20mA DC
0 to 20mA DC
0 to 1V DC
DC
0 to 10V DC
Voltage
1 to 5V DC
0 to 5V DC
Thermocouple
RTD
0 to 20mA DC
DC
current
4 to 20mA DC
0 to 1V DC
0 to 5V DC
DC
voltage
1 to 5V DC
0 to 10V DC
Relay contact (contact
material: silver alloy)
Control output
(Must be
Non-contact DC voltage
specified)
–199.9 to 500.0°C (–199.9 to 900.0°F)
Multi-input
Current
DC current
Alarm output 1 (EVT1)
Relay contact
(Contact material: Ag alloy)
Alarm output 2 (EVT2)
Control mode
Target temperature setting
Program control function
Thermocouple
Accuracy
RTD
DC current and DC voltage
Sampling period
6
KT4
48 × 48 × 95mm
–200.0 to 500.0°C
(–320.0 to 900.0°F)
–1999 to 9999, –199.9 to 999.9
–19.99 to 99.99, –1.999 to 9.999
–2000 to 10000
• Scaling and change to the decimal point position is possible for DC current and DC voltage input.
• DC current input is supported with an externally mounted 50Ω shunt resistor (sold separately).
K, J, R, S, B, E, T, N, PL-II, C (W/Re5-26) External resistor: Max. 100Ω (max. 40Ω external resistor for B input)
Pt100, JPt100Ω 3-conductor system (Allowable input conductor resistance for each conductor: max. 10Ω)
Input impedance: 50Ω (Connect 50Ω shunt resistor between input terminals.)
Allowable input current: max. 50 mA (when 50Ω shunt resistor is used)
Input impedance: min. 1 MΩ, Allowable input voltage: max 5 V, Allowable signal source resistance: max. 2 kΩ
Input impedance: min. 100 kΩ, Allowable input voltage: max 15 V, Allowable signal source resistance: max. 100Ω
1a
1a
1a1b
1a
1a
3A 250V AC (Resistive load), 1A 250V AC (Inductive load cosφ =0.4), Electric life: 100,000 times
12V DC ±15%,
Max. load current:
12 +20 V DC, Max. load current: 40mA (Short-circuit protected)
40mA (Shortcircuit protected)
4 to 20mADC Load resistance: Max. 550Ω
Relay contact 1a
Relay contact 1a:
Open collector,
3A 250V AC
3A 250VAC
Relay contact 1a 3A 250VAC (Resistive load)
Control capacity:
(Resistive load),
(Resistive load)
Electric life: 100,000 times
24V DC 0.1A
1a 1A 250V AC
Electric life:
(Max.)
(Inductive load
100,000 times
cosφ =0.4)
Open collector
Same as
The same as the one of Alarm output 1
None
0.1A 24V DC
Alarm output 1
Actions mentioned below can be selected by key operation. [Default PID] PID (with auto-tuning function), PI, PD (with manual
reset function), P (with manual reset function), ON/OFF action
Primary setting/
Primary setting/
secondary setting/
secondary setting
Primary setting/secondary setting
third setting/fourth
—
—
(switched by
(switched by external terminal)
setting (switched
external terminal)
by external
terminal)
1 pattern, 9 step
setting is possible
(However, make
function selection
—
setting of either
control with fixed
set point or
program control.)
Within ±0.2% ±1 digit of each input span or within ±2°C (4°F) whichever is greater
However, R and S input; Within ±6°C (12°F) in the range of 0 to 200°C (0 to 400°F)
B input 0 to 300°C (0 to 600°F): Accuracy is not guaranteed.
K, J, T, E, and N input less than 0°C (32°F): Within ±0.4% ±1 digit of input span
Within ±0.1% ±1 digit of each input span or ±1°C (2°F) whichever is greater
Within ±0.2% ±1 digit of each input span
250ms
KT (AKT2,4,7,8,9,4H,4B)
Display
Hysteresis (ON/OFF)
Proportional band
Specifications
KT2
KT4
KT8
KT9
Thermocouple & RTD: 0.1 to 100.0°C (32.18 to 212°F)
DC current and DC voltage: 1 to 1000 (The decimal point place follows the selection)
For sensor input
range and DC
current,
DC voltage
0.0 to 110.0%
Integral time
Derivative time
Proportional cycle
Allowable voltage fluctuation
Insulated resistance
Breakdown voltage
Thermocouple: 0 to 1000°C (0 to 2000°F)
RTD: 0.0 to 999.9°C (0.0 to 999.9°F)
DC current and DC voltage: 0.0 to 100.0%
1.5kV AC for 1 min
between input
terminal and power
terminal, & between
output terminal and
power terminal
1.5kV AC for 1min between input terminal and ground terminal,
between input terminal and power terminal
between power terminal and ground terminal
between output terminal and ground terminal, & between output
terminal and power terminal
10 to 55 Hz (0.35 mm) to each direction (120ms sweep) for 10 min.
Breakdown vibration
10 to 55 Hz (0.75 mm) to each direction (120ms sweep) for 10 min.
Waterproof
Approx. 120g
PV: 8.7mm,
SV: 8.7mm (PV/SV
switching display)
Heating/Cooling
control
(Relay contact
material: silver
alloy)
Relay contact:
1a 3A 250V DC
(Resistive load)
Approx. 130g
Heater burn-out
alarm output
(Relay contact
material: silver
alloy)
—
PV: 10.2mm
SV: 8.8mm
PV: 11.2mm
SV: 11.2mm
Non contact relay
0.3A 250V AC
(Resistive load)
10 to 55 Hz
(1 cycle/min.)
single amplitude
0.35 mm
(10 min. on 3 axes)
10 to 55 Hz
(1 cycle/min.)
single amplitude
0.75 mm
(1 hour on 3 axes)
PV: 18mm
SV: 13.2mm
• Relay contact:
1a 250V AC 3A (Resistive load),
250V AC 3A (Inductive load cosø=0.4),
Electric life: 100,000 times
• Non-contact voltage:
12 +20 V DC Max. 40mA
(Short-circuit protected)
• DC current: 4 to 20mA DC
Load resistance: Max. 550Ω
Approx. 150g
None
PV: 7.4mm
SV: 7.4mm
None
Options
Communication
function
Tool port
Accessories
Heater rated current must be selected from 5A, 10A, 20A and 50A.
Open collector,
Setting accuracy: Within 5% of heater rated current
Control capacity:
Relay contact 1a 250V AC 3A (Resistive load), Electric life:
24V DC 0.1A (Max.)
100,000 times
Approx. 120g
IP66 (applicable only
to the front panel
subject to rubber
gasket employed)
PV: 12mm
SV: 6mm
Relay contact:
Control capacity 1a:
3A 250V AC
(Resistive load),
Electric life: 100,000
times
Non-contact voltage:
12V DC±15% Max.
40mA (Short-circuit
protected)
Specify either singlephase 20 A, singlephase 50 A, 3-phase
20 A, or 3-phase
50 A for rated heater
current.
Setting accuracy:
within ±5% of rated
heater current
Relay contact 1a: 3A
250V AC (Resistive
load), Electric life:
100,000 times
RS-485/Modbus Protocol (Modbus is a communication protocol developed for PLCs by Modicon Inc.)
Communication speed: 2400/4800/9600/19200bps
—
Mounting frame
Terminal cover
Rubber gasket
0 to 1000°C
(32 to 1832°F)
The decimal point
input: 0.0 to 1000°C
(32 to 1832°F)
DC current and DC
voltage: 0.0 to
100.0%
1.5kV AC for 1 min
between input terminal and power terminal,
& between output terminal and power
terminal
X, Y & Z each direction for 5 times 98m/s2 (10G)
Same as above, but 294m/s2 (30G)
0 to 50°C
35 to 85%RH (No condensation)
Approx. 240g
Approx. 370g
IP66 (applicable only to the front panel subject to rubber gasket employed)
Display character height
For sensor input
range and DC
current,
DC voltage
0.0 to 110.0%
KT4H/4B
0 to 1000 seconds
0 to 300 seconds
1 to 120 seconds
When 100 to 240V AC; 85 to 264V AC When 24V AC/DC; 20 to 28V AC/DC
500V DC 10MΩ or greater
Malfunction vibration
Malfunction shock
Breakdown shock
Ambient temperature
Ambient humidity
Mass
KT7
Included with unit
Sold separately
Not available
Not available
Not available
Communication
interface
C-MOS level
Cannot be used at
the same time as
serial communication (option).
*This port can only
be used with the tool
cable (AKT4H820).
Included with unit
Not available
Included with unit
7
KT (AKT2,4,7,8,9,4H,4B)
COMMUNICATION FUNCTION OVERVIEW
Specification
Item
KT2, 4, 8, 9, 7
Communication type
Communication speed
Synchronization type
Protocol
Coding
Error correcting
Error detection
Data structure
Interface
No. of nodes
Maximum cable length
KT4H/4B
Half-duplex
Select 2400, 4800, 9600, or 19200 bps using key operation.
Asynchronous
Modbus
ASCII
Command re-send
Parity check, check sum
Start bit: 1, Data bit: 7, Parity: Even parity, Stop bit: 1
EIA RS485 compliant
31
1,000 m (cable resistance must be within 50Ω)
Modbus RTU, Modbus ASCII, MEWTOCOL (Slave)
Binary/ASCII
Note: That main setting No. 2 will not be possible on the KT8 and KT9 when the communications functions is added.
PARTS AND FUNCTIONS
1. KT2 series
3
4
5
1 PV/SV display (red):
6
7
1
8
2
9
10
11
12
13
2 MEMO/STEP display (green): Indicates memory number during fixed value control. Indicates step number
during program control.
3 PV indicator (red):
Lights up when the input value (PV) is indicated.
4 SV indicator (green):
Lights up when main setting value (SV) is indicated.
5 AT indicator (yellow):
Flashes during AT (auto-tuning).
6 T/R indicator (yellow):
Flashes during serial communication (Lit while sending data, Unlit while
receiving data)
7 OUT indicator (green):
Lights up when control output or OUT1 (Heating side, option Heating/Cooling
control) is ON. (For DC current output type, it flashes corresponding to the
manipulated variable in a 0.25 second cycle)
8 EV1 indicator (red):
Lights up when Event output 1 or OUT2 (Cooling side, option Heating/Cooling
control) is ON.
9 EV2 indicator (red):
Lights up when Event output 2 is ON.
10 Increase key (
Increases the numeric value.
):
11 Decrease key (
12 Mode key (
MODE
):
):
13 OUT/OFF key ( OUTOFF ):
8
Indicates the input value and setting value. During setting mode, characters
and setting value of the setting item are indicated in turn.
Decreases the numeric value.
Selects the setting mode or registers the setting value.
(By pressing the Mode key, the setting value or selected value can be
registered)
The control output OUT/OFF or program control RUN/STOP can be switched.
KT (AKT2,4,7,8,9,4H,4B)
2. KT4 series
3. KT8 series
1
1
1 PV display
Indicates PV (process variable).
2 SV display
Indicates SV (setting value).
3 Increase key
Increases numerical value.
4 Decrease key
Decreases numerical value.
5 Mode key
Switches the setting mode.
6 OUT/OFF key
Control output is turned on or off when
control output is ON.
2
2
3
4
6
5
3
4
4. KT9 series
6
5
5. KT7 series
1
1
2
3
5
4
2
3
4
5
6
Note: Color selection is the same for each size.
6. KT4H/4B series
1
2
3
4
9
5
7
6
8
(Bottom side)
1 Action indicators (backlight: orange)
°F °C ..................... Lights respectively when temperature unit °F/°C is selected.
T/R ........................ Lights during Serial communication (option) TX output.
AT ......................... Flashes during auto-tuning or auto-reset
OUT1 .................... Lights when control output is ON or Heating output (option) is
ON.
For DC current output type, it flashes corresponding to the
manipulated variable in 0.25 second cycles.
OUT2 .................... Lights when Cooling output (option) is ON.
EVT1 ..................... Lights when Alarm 1 output is ON.
EVT2 ..................... Lights when Alarm 2 output (option) is ON or Heater burnout
alarm (option) is ON.
LOCK .................... Lights when Lock 1, Lock 2 or Lock 3 is selected.
2 MEMO display ....... Indicates the set value memory number (backlight: green).
3 PV display ............. Indicates the PV (process variable) (backlight: red/orange/green).
4 SV display ............. Indicates the SV (set value) (backlight: green).
5 Mode key ............... Selects the setting mode, and registers the set value.
6 OUT/OFF key ........ The control output ON/OFF or Auto/Manual control can be
switched.
7 Increase key .......... Increases the numeric value.
8 Decrease key ........ Decreases the numeric value.
9 Tool connector ....... By connecting the tool cable, the following operations can be
conducted from the external computer using the exclusive tool
software.
- Reading and setting of SV, PID and various set values from
external computer
- Reading of PV and action status
- Function change
9
KT (AKT2,4,7,8,9,4H,4B)
DIMENSIONS (unit: mm inch) Tolerance: ±1 ±.039
1. KT2 series
• External dimension
• Panel cutout
M3 M.118
47.6 1.874
45+0.6
0
1.772+.024
0
44.8
1.764
22.2+0.3
0
.874+.012
0
40
1.575
Rubber packing
Mounting frame
60
2.362
36.5 1.437
MEMO/STEP
PV
SV
AT
T/R
OUT
24
.945
EV1
EV2
OUT
MODE
21.6
.850
OFF
KT2
48
1.890
Note: The communications terminal is the screw terminal on the
back of the unit.
98.5
3.878
10.6
.417
2. KT4 series
• External dimension
• Panel cutout
Rubber gasket
Screw type mounting
PV
OUT2
A1
EVT
TX/RX
45+0.5
−0
1.772+.020
−0
44.5
1.752
59.7
2.350
SV
SV2
45+0.5
−0
1.772+.020
−0
75
2.953
OUT1
SV1
75
2.953
M3 M.118
AT
45+0.5
−0
1.772 +.020
−0
OUT
MODE
OFF
KT4
48
1.890
11.5
.453
n × 48 – 3+0.5
−0
n × 1.890 – .118+.020
−0
Lateral close mounting
n: Number of units mounted
Note: The communications terminal is the screw terminal on the
back of the unit.
95
3.740
3. KT8 series
• External dimension
• Panel cutout
Rubber gasket
Screw type mounting
75
2.953
M3 M.118
92+0.5
−0
3.622+.020
−0
PV
SV
SV1
OUT1
OUT2
HB
AT
TX/RX
A1
A2/LA
130
5.118
91
3.583
106.2
4.181
96
3.780
SV2
+0.5
−0
+.020
−0
92
3.622
OUT
n × 48 – 3+0.5
−0
n × 1.890 – .118+.020
−0
Lateral close mounting
n: Number of units mounted
45+0.5
−0
1.772 +.020
−0
MODE
OFF
KT8
11.5
.453
48
1.890
98.5
3.878
Note: The communications terminal is the screw terminal on the
back of the unit.
4. KT9 series
• External dimension
• Panel cutout
Rubber gasket
Screw type mounting
M3 M.118
130
5.118
92+0.8
−0
3.622+.031
−0
PV
SV
91
3.583
106.2
4.181
SV1
SV2
OUT1
OUT2
HB
AT
TX/RX
A1
A2/LA
130
5.118
n × 96 – 3+0.5
−0
n × 3.780 – .118+.020
−0
Lateral close mounting
n: Number of units mounted
OUT
92+0.5
−0
3.622+.020
−0
MODE
OFF
KT9
96
3.780
10
11.5
.453
98.5
3.878
Note: The communications terminal is the screw terminal on the
back of the unit.
KT (AKT2,4,7,8,9,4H,4B)
5. KT7 series
• External dimension
M3 M.118
1
2
3
4
OUT
EVT
T/R
AT
PV
75
2.953
SV
MODE
KT7
5
6
7
8
9
M2 M.079
97
3.819
100
3.937
22.5
.886
6. KT4H/4B series
• External dimensions
Rubber gasket
1.5
.059
Mounting frame
Note: The communications terminal is the modular jack on the
bottom of the unit.
Terminal cover
(Sold separately)
• Panel cutout
• Lateral close mounting
+0.5
45 0
+.020
1.772 0
M3 screw
75
2.953
n × 48 − 3
+0.5
44.5
59.2
1.752
2.331
47.5
1.870
45 0
+.020
1.772 0
45
6
.236
56.0
2.205
61.0
2.402
+0.5
0
+.020
0
n: Number of units mounted
+0.5
0
1.772
48
1.890
n × 1.890 − .118
+.020
0
Notes: If lateral close mounting is used for the controller,
IP66 specification (Dust-proof/Drip-proof) may be
compromised, and all warranties will be invalidated.
11
KT (AKT2,4,7,8,9,4H,4B)
INSTALLATION
1. KT2 series
Please install vertically in order to satisfy the IP66 specification for dust and splash proofing.
The possible control panel plate thickness for installation is between 1 to 10 mm.
(1) Insert the unit from the front of the control panel.
(2) Insert the mounting frame until that the edges (2) make contact with the panel.
(3) Tighten the clamp screw and then turn it 3/4 of a turn after the edge of the screw reaches the panel.
2. KT4, 7, 8, 9 series
• Panel Mounting
Mountable panel thickness: Within 1 to 15mm .039 to .591inch
Insert a controller from the front side of the panel.
Attach the mounting brackets by the holes at the top and bottom
of the case and secure the controller in place with the screws.
• DIN rail mounting (KT7)
1) Hook 1 of the KT7 on the upper side of the DIN rail.
2) Making the 1 part of the KT7 as a support, fit the lower part
of the KT7 to the DIN rail.
KT7 will be completely fixed to the DIN rail with a “Click” sound.
Recommended DIN rail: Part No. ATA48011
Recommended fastening plate: Part No. ATA4806
1
DIN rail
pv
av
G/T
T
EV
T/B
AT
DE
MO
G/T
pv
EV
T
K
T
T/B 7
AT
Fastening plate
av
Notice
As the case is made of resin, do not
use excessive force while screwing
in the mounting bracket. The torque
is approximately 0.12N·m
3. KT4H/4B series
Please install vertically in order to satisfy
the IP66 specification for dust and splash
proofing.
The possible control panel plate
thickness for installation is between 1 to 5
mm.
1) Insert the unit from the front of the
control panel.
2) Push the installation frame fully into
contact with the panel and tighten the
screws (screw torque from 0.05 N·m to
0.06N·m).
12
MO
5
6
7
8
DE
2
9
Rubber gasket
KT (AKT2,4,7,8,9,4H,4B)
OPTION
1. Shunt resistor
AKT4810 (for KT2, 4, 8, 9, 4H and 4B)
AKT4811 (for KT7)
26±1
1.024±.039
74±6
2.913±.236
2. Terminal cover
AKT2801 (for KT2)
AKT4801 (for KT4)
9 × 8.4 = 75.6
9 × .331 = 2.976
47.5
1.870
AKT8801 (for KT8)
AKT9801 (for KT9)
9 × 8.4 = 75.6
9 × .331 = 2.976
19
.748
AKT4H801 (for KT4H/4B)
20
.787
40
1.575
23.8
.937
44.5
1.752
48
1.890
3.5
.138
15.5
.610
88
3.465
92
3.622
>PC<
6
.236
47.7
1.878
20
.787
46.5
1.831
22.3
.878
44.5
1.752
47.5
1.870
17
.669
24.5
.965
29
1.142
6
.236
Note: 2pcs of terminal cover of AKT8801 can be used as an AKT9801 cover.
3. Current transformer (CT)
• External dimension
1) CT1 (for 5,10 and 20A)
2) CT2 (for 50A)
l
15
.591
5.8 dia.
.228 dia.
k
l
0.5
.020
7.5
.295
30
1.181
k
2.8
.110
K
100
3.937
L
25
.984
10.5
.413
21
.827
40
1.575
30
1.181
3
.118
40
1.575
10
.394
2-3.5 dia.
2-.138 dia.
40
1.575
30
1.181
12 dia.
.472 dia.
15
.591
2-M3 .118
Note: CT1 or CT2 for current detection is provided as an accessory when heater
burn-out alarm function is added.
4. Tool cable
AKT4H820
n2.5 Plug 3-Pole type
20
.787
USB Plug
35
1.378
200±20
7.784±.787
50
1.969
2000±40
78.74±1.575
13
KT (AKT2,4,7,8,9,4H,4B)
EXTERNAL CONNECTION DIAGRAM
1. KT2 series
2. KT4 series
RS-485
B
YA (–)
YA (+)
POWER
SUPPLY
SG
D1
EV1/OUT2
EV2
8
9
10
NO
3A
250V
AC
2
3
TC
4
0.1A
24V
DC
5
CT
OUT2
6
S
3A
250V
AC
YA (–)
3
A1
6
24V AC/DC
POWER SUPPLY
5
0.3A
250V
AC
B
YB
(+)
NO
10
15
SG
• POWER SUPPLY: Power supply
• OUT1: Control output 1 (heat output)
• OUT2: Control output 2 (cooling output)
• RELAY: Relay contact output
• V/A: DC voltage output/direct current output
• V: Contactless relay output
• A1: Alarm 1 output
• EVT: Event output (A2 output and heater cutoff alarm output)
• CT: CT input
• TC: Thermocouple
• RTD: Resistance temperature detection
• DC: Direct current or DC voltage
• RS-485: Serial communications
3. KT8 and KT9 series
4. KT7 series
GND
2
24V AC/DC
1
POWER
SUPPLY
2
12
NO
100 to 240V AC
3
3
YA(–)
11
A2/(HB)
RS-485
13
250V AC
4
YB(+)
14
SV2
NC
OUT1
5
15
RELAY
V/A
CT
NO
6
16
3A
250V AC
7
17
SG
NO
A1
8
OUT2/HB
A
18
3A
250V AC
19
9
RELAY
V/A
NO
250V AC
B
TC
20
10 3A
KT8/KT9
B
DC
• POWER SUPPLY: Power
supply
• OUT1: Control output 1
• OUT2: Control output 2
(cooling output)
• RELAY: Relay contact output
• V/A: DC voltage output/direct
current output
• A1: Alarm 1 output
• A2: Alarm 2 output
• HB: Heater cutoff alarm
output
• SV2: Second main setup
• CT: CT input
• TC: Thermocouple
• RTD: Resistance
temperature detection
• DC: Direct current or DC
voltage
• RS-485: Serial
communications
RTD
Note: That main setting No. 2 will not be possible on the KT8 and KT9 when the communications
functions is added.
POWER SUPPLY
24V AC/DC
1
2
OUT
V/A
RELAY
POWER SUPPLY
100to 240V AC
1
2
3
3A
250V AC
KT7
5
TC
RTD A
DC
B
TC RTD DC
KT4
• TC: Input terminal for thermo couple.
• RTD: Input terminal for the resistance temperature sensor.
• DC: Input terminal for DC current or DC voltage.
For DC current input, connect a separately sold receipt resistor (50Ω) between the input
terminals.
• OUT1: Output terminal for the control output or heating output [option: heating/cooling control].
• POWER SUPPLY: Power supply terminal.
• EV1/OUT2: Output terminal for event output 1 or cooling output [option: heating/cooling control].
• EV2: Output terminal for event output 2.
• DI: Input terminal for DI input. (There are three types of D1 input, the SV1/SV2 external switching
function, the OUT/OFF (RUN/STOP) output switching function, and timer function.)
• RS-485: Communication terminal for serial communication. (EV1, 2 is alarm output)
POWER
SUPPLY
A
9
14
NO
EVT
5
3A
250V
AC
8
13
RS-485
4
DC
6
RELAY
V/A
7
NO
12
2
2
100 to 240V AC
POWER SUPPLY
V/A
OUT1
11
100 to
240V AC
RELAY
B
RTD
A
OUT1
1
24V AC/DC
12
3A
250V
AC
NO
1
11
KT2
7
POWER
SUPPLY
1
4
0.1A
24V DC
6
7
B
8
B
9
EVT
RS-485
No.1
No.2
No.3
No.4
No.5
No.6
SG
NC
YB(+)
YA(–)
NC
SG
No.1
No.6
No.1
No.6
CT
• POWER SUPPLY: Power supply
• OUT: Control output
• RELAY: Relay contact output
• V/A: DC voltage output/direct current output
• EVT: Event output
[Alarm, loop fault alarm or heater cutoff alarm (optional)]
• TC: Thermocouple
• RTD: Resistance temperature detection
• DC: Direct current or DC voltage
• RS-485: Serial communications
• CT: CT input
5. KT4H/4B series
POWER SUPPLY ....... Power supply
EVT1 .......................... Alarm 1 output
EVT2 .......................... Alarm 2 output (option) or heater burn-out
Alarm output (option)
OUT1 ......................... Control output or heating output (option)
OUT2 ......................... Cooling output (option)
TC .............................. Thermocouple input
RTD ........................... Resistance temperature detection input
DC .............................. Direct current input (DCA) or DC voltage input (DCV)
(For DC voltage input, + side terminal number differs depending on the voltage.
Also, DC current input, connect s shunt resistor between No. 10 and 12 terminal.)
CT1 ............................ Current transformer input 1 (option: Single, three phase)
CT2 ............................ Current transformer input 2 (option: Three-phase)
DI ............................... Contact input (option)
RS-485 ....................... Serial communication RS-485 (option)
14
KT (AKT2,4,7,8,9,4H,4B)
Communication Function Connection Diagram (PLC Connection Diagram)
1. KT2, 4, 8 and 9 series
RS-485
2. KT7 series
KT2
KT4
(–)
10 YA (–)
13 YA (–)
KT8 , 9
11 YA (–)
(+)
11 YB (+)
14 YB (+)
14 YB (+)
12 COM
15 COM
17 COM
PLC
No.0
KT7
No.1
PLC
No.30
(–)
(+)
Shielded cable
Communicatin cable
3 to YB (+)
Terminal
4 to YA (–)
Terminal
KT2
KT4
10 YA (–)
13 YA (–)
KT8 , 9
11 YA (–)
11 YB (+)
14 YB (+)
14 YB (+)
12 COM
15 COM
17 COM
Notes: 1. Terminating Resistors (Terminators)
The KT series has a built-in pull-up resistor or pull-down resistor, which
serves as the terminating resistor. For this reason, do not connect the
terminating resistor on the communication line.
2. Please use a RJ-116 polarized type modular connector.
Please use a cable that is suitable for a modular connector.
3. KT4H/4B series
PLC
(−)
RS-485
(+)
KT4H
16 YA (−)
17 YB (+)
18 COM
Shielded cable
KT4H
16 YA (−)
Notes:
1. To prevent current flow along shield sections, ground one end of the shield line. (If both ends of the
shield section are grounded, a closed circuit with the earth will form and electricity flowing through the
shield line will cause increased susceptibility to noise.)
2. Terminating Resistors (Terminators)
The KT4H series has a built-in pull-up resistor or pull-down resistor. For this reason, do not connect the
terminating resistor on the communication line.
17 YB (+)
18 COM
NOTICE ON OPERATION
1. NOTICE ON SITE SELECTION
This instrument is intended to be used in
the following environment (IEC61010-1)
Overvoltage category II, Pollution degree
2
Mount the controller in a place with:
1) A minimum of dust, and an absence of
corrosive gases
2) No flammable, explosive gases
3) Few mechanical vibrations or shocks
4) No exposure to direct sunlight, an
ambient temperature of 0 to 50°C (32 to
122°F) that does not change rapidly
(When installing inside a panel, make
particular allowance for heat dissipation.
Avoid installation in situations such as
above equipment that generates heat.)
5) Locations in which temperature rapidly
changes may cause condensation.
6) Locations or atmospheres in which
gasoline, thinners, alcohol, or other
organic solvents are present, or in which
ammonia, sodium hydroxide, or other
strong alkaline substances may adhere.
7) Locations susceptible to direct impact
or the transmission of vibrations, or
where splashing with water is possible.
8) In the proximity of equipment in which
large switching surges occur or near
high-voltage cables, high-voltage
equipment, power lines, power
equipment, ham radio transmitters, or
equipment containing these or similar
devices.
9) An ambient non-condensing humidity
of 35 to 85%RH
10) No large capacity electromagnetic
switches or cables through which large
current is flowing
11) No water, oil or chemicals or where
the vapors of these substances can come
into direct contact with the controller
2. NOTICE ON THE WIRING
1) The terminal block of KT4, 8, 9, 4H, 4B
series are designed to be wired from the
left side (KT2 series are designed to be
wired from the upper and lower direction).
The lead wire must be inserted from the
left side of the terminal, and fastened by
the terminal screw. Use a solderless
terminal with insulation sleeve that fits to
the M3 screw.
Wirepressed
terminal
Company
name
Fork type
NICHIFU
Co., Ltd.
J.S.T. Mfg.
Co., Ltd.
Round
type
NICHIFU
Co., Ltd.
J.S.T. Mfg.
Co., Ltd.
Part number
1.25Y-3
VD1.25-B3A 0.6 N⋅m,
Max.
1.0 N⋅m.
1.25-3
V1.25-3
3.2mm dia.
.126inch dia.
Max. 5.8mm
.228inch
Fastening
torque
3.2mm
.126inch
Max. 5.8mm
.228inch
2) Terminal fastening torque is approximately 0.6N·m to 1.0N·m (KT4, 8, 9, 4H
and 4B).
For KT7 series by M3.0 screw is less
than 0.5N·m and by M2.0 screw 0.25N·m
respectively.
3) Use a thermocouple and
compensating lead wire according to the
input specification of the controller.
4) Use a 3-wire system of RTD according
to the input specification of the controller.
5) This controller has no built-in power
switch, circuit breaker or fuse. Therefore,
it is necessary to install them in the circuit
near the external controller.
(Recommended fuse: Time-lag fuse,
rated voltage 250V AC, rated current 2A)
6) In the case of 24V AC/DC power
supply, do not confuse the polarity when
it is DC.
7) With the relay contact output type, use
an auxiliary electromagnetic switch
externally according to the capacity of the
load to protect the built-in relay contact.
8) When wiring, keep input wire
(thermocouple, RTD, etc.) away from AC
source and load wire to avoid external
interference.
9) Turn the power supply to the
instrument off before wiring or checking.
Working or touching the terminal with the
power switched on may result in Electric
Shock which could cause severe injury or
death.
15
KT (AKT2,4,7,8,9,4H,4B)
10) Do not drop wire chips into the holes
of vent when wiring, because they could
cause fire, malfunction or trouble with the
device.
11) To prevent the unit from harmful
effects of unexpected high level noise, it
is recommended that a surge absorber
be installed between the electromagnetic
switch coils.
3. NOTICE ON THE MOUNTING
1) Do not use excessive force while
screwing in the mounting bracket of KT4,
8, 9, 4H and 4B series. For KT4, 8 and 9
series, recommended torque is approximately 0.12N·m. For KT4H and 4B,
recommended torque is approximately
0.05 to 0.06 N·m.
2) When mounting the KT7 series to the
DIN rail, mount it in a lateral direction.
Make sure a click is audible when fixed
into place.
4. OPTIONAL HEATER BURN-OUT
ALARM OUTPUT (KT4, 7, 8, 9, 4H and
4B series)
1) This alarm is not available for detecting
current under phase control.
2) Use the current transformer (CT)
provided, and pass one lead wire of the
heater circuit into the hole of CT.
3) When wiring, keep CT wire away from
AC source and load wire to avoid external
interference.
4) In three phase installations, ensure
that R, S, and T are each connected to a
2-line CT that connects with CT1 ((13)–
(14)) and CT2 ((14)–(15)) terminals.
CT input terminal
5. Please use rod terminals for the
terminal portion of the KT7 series.
We recommend terminals made by
Phoenix Contact.
(1) to (4) are AI0.25–8YE, AI0.34–8TQ,
AI0.5–8WH, AI0.75–8GY, AI1.0–8RD,
and AI1.5–8BK.
(5) to (9) are AI0.25–8YE, AI0.34–8TQ,
and AI0.5–8WH.
The screw tightening torque for (1) to (4)
should be no more than 0.5 N·m and for
(5) to (9) it should be no more than 0.25
N·m. Make sure no screw is loose.
Power supply
CT
Heater
KT Monitor
Available for download free of charge. Use it to acquire data from the KT series temperature controller.
FEATURES
1. Parameters can be set from a computer.
2. Measurement data can be monitored from a computer.
3. Measurement data can be logged to a computer.
Download from http://www.panasonic-electric-works.net/ac
Applications
Contributing to space savings of various heater control systems
Injection molding machine
Temperature controlled bath
Sensor
Printing machine
Heater
Controller
KT4H Temperature Controller
LCD curing oven
Kitchen appliance
Panasonic Electric Works Co., Ltd.
Automation Controls Business Unit
Head Office: 1048, Kadoma, Kadoma-shi, Osaka 571-8686, Japan
16Telephone: +81-6-6908-1050
panasonic-electric-works.net/ac
Facsimile: +81-6-6908-5781
All Rights Reserved © 2009 COPYRIGHT Panasonic Electric Works
Specifications are subject to change without notice.
ARCT1B317E 200910-0YT
Printed in Japan.