KW1M/KW1M-H Eco-POWER METER (AKW1)
Simple and compact
power meter perfect
for control panels
KW1M
Eco-POWER METER (Standard type)
FEATURES
KW1M
(Standard type)
AKW1110
• In addition to simple measurement of
voltage, current, power and integrated
electrical power, etc., output of alarm
signal is possible using the “alarm
setting”.
• 50 mm thickness
• Both screw and DIN rail installation
(easy installation).
• Switchable between electrical power
and electricity charge usage.
• Display of calculated CO2 value
possible.
KW1M
(Standard type)
AKW1111
Only AKW1111
• Direct input with 400 VAC system
• Three-phase four-wire system
• Power factor and frequency
measurement
• Simultaneous power/pulse
measurement
Compliance with RoHS Directive
PRODUCT TYPES
Main unit
Product name
KW1M Eco-POWER METER
Standard type
Phase and wire system
Single-phase two-wire system
Single-phase three-wire system
Three-phase three-wire system
Three-phase four-wire system*1
Operating
power supply
100 to 240 VAC,
50/60 Hz
Measured voltage input
Terminal type
Model number
100/200 VAC
Screw terminal
(M3.5 “+/−” screw)*2
(M3 “+/−” screw)
AKW1110
100/200/400 VAC
(Select with setting mode)
AKW1111
Notes: *1. Three-phase four-wire system: for AKW1111 only
*2. The M3.5 “+/−” screws are only for the operation voltage and voltage input terminals (P0, P1, P2, and P3) of AKW1111.
Dedicated current transformer (CT)
Rated primary current
5A/50A (common)
100A
250A
400A
Model number
AKW4801C
AKW4802C
AKW4803C
AKW4804C
Please order in accordance with the type of power distribution system you will be measuring.
(Even if you will be using a secondary 5A CT, you will need an AKW4801C.)
Options
Product name
Mounting rail
Fastening plate
Mounting frame
Descriptions
Rail for holding DIN rail terminal socket
Plate for holding DIN rail
Used for mounting in a panel
Model number
AT8-DLA1
ATA4806
AKW1822
Tool and Software
Product name
KW Monitor*1
(Data collection software
for Eco-POWER METER)
KW Watcher
(Electric power monitoring software)
Descriptions
Remark
For parameter settings, editing of measurement values, and monitoring, etc.
Please use in situations where Web Datalogger Unit (DLU)/Data Logger Light (DLL) and
Eco-POWER METER are used together.
For easy “visualization” of data collected in DLU or DLL
You can download from our website
(free of charge)*2
Notes: *1. KW Monitor only uses MEWTOCOL. You cannot use MODBUS (RTU) type.
*2. Customer registration is required to download data.
Other tool
Product name
KW1M Eco-POWER METER
User’s manual (pdf)
Descriptions
Remark
Detailed explanation of Eco-POWER METER usage
You can download from our website
(free of charge)*2
All Rights Reserved © COPYRIGHT Panasonic Electric Works Co., Ltd.
KW1M/KW1M-H Eco-POWER METER (AKW1)
KW1M-H
Eco-POWER METER (SD card type)
Simple and compact
power meter perfect
for control panels
FEATURES
• In addition to simple measurement of
voltage, current, power and integrated
electrical power, etc., output of alarm
signal is possible using the “alarm
setting”.
• 50 mm thickness
• Both screw and DIN rail installation
(easy installation).
• Switchable between electrical power
and electricity charge usage.
• Display of calculated CO2 value
possible.
KW1M-H
(SD card type)
• Internal memory (Read by SD card)
• Built-in battery (for clock and log
data backup)
• Addition of measurement items
- Power factor, frequency, and pulse
counter
- Integrated electrical power by
month/day/hour
- Calendar timer function
Compliance with RoHS Directive
PRODUCT TYPES
Main unit
Product name
KW1M-H Eco-POWER METER
SD card type
Phase and wire system
Single-phase two-wire system
Single-phase three-wire system
Three-phase three-wire system
Three-phase four-wire system
Operating
power supply
Measured voltage input
Terminal type
Model number
100 to 240 VAC,
50/60 Hz
100/200/400 VAC
(Select with setting mode)
Screw terminal
(M3 “+/−” screw)
AKW1121
Dedicated current transformer (CT)
Rated primary current
5A/50A (common)
100A
250A
400A
Model number
AKW4801C
AKW4802C
AKW4803C
AKW4804C
Please order in accordance with the type of power distribution system you will be measuring.
(Even if you will be using a secondary 5A CT, you will need an AKW4801C.)
Options
Product name
Mounting rail
Fastening plate
Backup battery
Mounting frame
Descriptions
Rail for holding DIN rail terminal socket
Plate for holding DIN rail
Used for memory backup function or clock function
Used for mounting in a panel
Model number
AT8-DLA1
ATA4806
AFPG804
AKW1822
Tool and Software
Product name
KW Monitor*1
(Data collection software
for Eco-POWER METER)
Descriptions
Remark
For parameter settings, editing of measurement values, and monitoring, etc.
KW View (Power display tool)
For KW1M-H
You can then display the data as a graph by Eco-POWER METER data (electric power
only). (1 hour units fixed)
KW Watcher
(Electric power monitoring software)
Please use in situations where Web Datalogger Unit (DLU)/Data Logger Light (DLL) and
Eco-POWER METER are used together.
For easy “visualization” of data collected in DLU or DLL
You can download from our website
(free of charge)*2
Notes: *1. KW Monitor only uses MEWTOCOL. You cannot use MODBUS (RTU) type.
*2. Customer registration is required to download data.
Other tool
Product name
KW1M-H Eco-POWER METER
User’s manual (pdf)
Descriptions
Remark
Detailed explanation of Eco-POWER METER usage
You can download from our website
(free of charge)*2
All Rights Reserved © COPYRIGHT Panasonic Electric Works Co., Ltd.
KW1M/KW1M-H Eco-POWER METER (AKW1)
MEASUREMENT ITEMS
Item
Instantaneous electric power (Active)
Integrated electric power (Active)
R current
S current*1
T current
R (RS) voltage
Voltage
S (RT) voltage*1
T (TS) voltage
Electricity charge*2
Converted CO2 value
Power factor*1
Frequency*1
ON time
Hour meter
OFF time
Pulse counter*1
Current
Unit
kW
kWh/MWh
A
A
A
V
V
V
—
kg-CO2
—
Hz
h (Hour)
h (Hour)
—
Data displayed range
0.00 to 9999.99
0.00 to 9999.99kWh
0.00 to 9999999.99kWh (When 9-digit display)
0.0 to 6000.0
0.0 to 6000.0
0.0 to 6000.0
0.0 to 9999.9
0.0 to 9999.9
0.0 to 9999.9
0.00 to 999999
0.00 to 999999
0.0 to 1.00 (Identify leading phase “–” or lagging phase) (Only in range of phase angle θ = –90° to +90°)
47.5 to 63.0
0.0 to 99999.9
0.0 to 99999.9
0 to 999999
*1. For AKW1110, AKW1121 only
*2. Eco-POWER METER is designed chiefly for managing energy saving. It is not intended to be used for billing.
SPECIFICATIONS
Main unit
Item
Rated operating voltage
Rated frequency
Rated power consumption
Allowable operating voltage range
Allowable momentary power-off time
Ambient temperature
Ambient humidity
Breakdown voltage (initial)
Insulation resistance (initial)
Vibration resistance
Shock resistance
Display method
Power failure memory method
Size
Weight
Specifications
100 to 240V AC
50/60Hz common
AKW1110: 6 VA (240V AC at 25°C) / AKW1111, AKW1121: 8 VA (240V AC at 25°C)
85 to 264V AC (85% to 110% of rated operating voltage)
10ms
–10 to +50°C (–25°C to +70°C at storage)
30 to 85%RH (at 20°C non-condensing)
• Outer edge (case) – all terminals
Between the isolated circuits: 2000V for 1min
• Insulated circuit
- Operating power supply terminals – Analog input terminals*1
- Operating power supply terminals – Pulse input terminals*1
Between the isolated circuits: 100MΩ or more
- RS485 – All other terminals
(measured with 500V DC)
- Pulse output terminals – All other terminals
10 to 55Hz (1cycle/min) single amplitude: 0.375mm (1h on 3 axes)
Min. 294m/s2 (5 times on 3 axes)
LCD with backlight
Upper section: Green, 4-digit, 16-segment, Letter height: 6.5 mm
Lower section: Amber, 6-digit, 7-segment, Letter height: 7.5 mm
EEP-ROM (more than 100,000 overwrite)
75 × 90 × 50 mm
AKW1110 and AKW1111: approx. 170g, AKW1121: approx. 180g (without battery)
*1. Analog input terminals: No.3 to No.6 (for AKW1111), No.4 to No.6 (for AKW1110 and AKW1121)
Pulse input terminals: No.12 and No.13 (for AKW1111)
No Connection terminal (N.C.) is internally connected to the analog input circuit.
All Rights Reserved © COPYRIGHT Panasonic Electric Works Co., Ltd.
KW1M/KW1M-H Eco-POWER METER (AKW1)
Power input specifications
Specifications
Item
AKW1110
Phase and wire system
Rating
Input
voltage
Allowable measurement voltage
VT ratio
Input
current
Special
functions
Accuracy
(without
error in CT
and VT)
AKW1111 and AKW1121
Single-phase two-wire, Single-phase three-wire,
Three-phase three-wire (common)
Primary side rating
Cut-off current
Cut-off voltage
Current threshold for hour meter
Instantaneous electric power
Integrated electric power
Voltage
Indication Current
accuracy Electricity charge
Calculated CO2 value
Single-phase two-wire, Single-phase three-wire, Threephase three-wire, Three-phase four-wire (common)
Single-phase two-wire: 0 to 440V AC (Line voltage)
Single-phase two-wire: 0 to 220V AC (Line voltage)
Single-phase three-wire: 0 to 220V AC (Phase voltage)
Single-phase three-wire: 0 to 110V AC (Phase voltage)
Three-phase three-wire: 0 to 440V AC (Line voltage)
Three-phase three-wire: 0 to 220V AC (Line voltage)
Three-phase four-wire: 0 to 254V AC (Phase voltage)
Up to 120% of rated input voltage
Single-phase two-wire: 0 to 528V AC (Line voltage)
Single-phase two-wire: 0 to 264V AC (Line voltage)
Single-phase three-wire: 0 to 264V AC (Phase voltage)
Single-phase three-wire: 0 to 132V AC (Phase voltage)
Three-phase three-wire: 0 to 528V AC (Line voltage)
Three-phase three-wire: 0 to 264V AC (Line voltage)
Three-phase four-wire: 0 to 300V AC (Phase voltage)
1.00 to 99.99 (Set with setting mode)
*A Voltage transformer (VT) is required when measuring loads that exceed the rated input voltage (AKW1110 is
200 VAC and AKW1111 and AKW1121 are 440 VAC). (Please use a commercially available VT with rated
secondary measurement voltage of 110 V.)
5 A/50 A/100 A/250 A/400 A (Select with setting mode)
1 to 4000 A (Set with setting mode)
*Use a commercial CT with secondary side current of 5A when measure 400A or more.
*Accuracy coverage: 10 to 100% of rated current of CT
1.0 to 50.0%F.S. (Select with setting mode)
Within 5% of rated voltage (within voltage value sought by rated voltage × 0.05 × VT ratio) (fixed)
1.0 to 100.0%F.S.
±2.5% F.S. +1 digit (at 20°C, rated input, rated frequency, power factor 1)
*Accuracy coverage: 10 to 100% of rated current of CT
±0.01%+1digit (at 20°C), Monthly accuracy: ±260 sec. (for your reference)
(In case power on start or current energizing: ±0.01%+1s+1 digit, at 20°C)
±1.5% F.S. /10°C +1 digit (Range of –10 to 50°C for rated input, power factor 1)
±1.5% F.S. +1 digit (Frequency change±5% based on rated frequency, for rated input, power factor 1)
Hour meter
Temperature characteristics
Frequency characteristics
Pulse input specifications (For AKW1111 and AKW1121)
Item
Specifications
Addition (Fixed)
2kHz/30Hz (Select with setting mode)
Min. input signal width: 0.25ms (When 2kHz selected)/16.7ms (When 30Hz selected), ON : OFF ratio = 1 : 1
Input mode
Max. counting speed
Pulse input
Contact/No contact (open collector)
• Impedance when shorted: Max. 1kΩ
• Residual voltage when shorted: Max. 2V
• Impedance when open: Min. 100kΩ
HOLD (Over count)
Setting possible up to 3 digits after decimal point
0.001 to 100.000 (Select with setting mode)
Input signal (at 20°C)
Output mode
Pre-scale setting
Decimal point
Range
Pulse output (transistor output) specifications
Item
Number of output point
Insulation method
Output type
Output capacity
Pulse width
ON state voltage drop
OFF state leakage current
AKW1110
Pulse output unit
(Select with setting
AKW1111 and AKW1121
mode)
Specifications
1 point
Optical coupler
Open collector
100mA 30V DC
Approx. 100ms
1.5V or less
100µA or less
0.001/0.01/0.1/1/10/100 kWh/Power alarm (AL-P)/Current alarm (AL-C)
0.001/0.01/0.1/1/10/100 kWh/Power alarm (AL-P)/Current alarm (AL-C)/Standby power alarm (AL-S)/
Counter (Cnt)
* We recommend the setting of minimum unit for pulse output for measurement shown as below.
Output pulse: 4 pulse or less per 1sec.
Calculation method: (Pulse output unit: value of PL-P) > (Max. measured power [kW]) / (3600 [s] × 4 [pulse/s])
Note 1: Count errors may occur if pulse output unit is set so that 4 or more pulses are output per 1 second.
Note 2: The connected counter or PLC may cause count errors if the OFF time of the pulse output unit is short.
All Rights Reserved © COPYRIGHT Panasonic Electric Works Co., Ltd.
KW1M/KW1M-H Eco-POWER METER (AKW1)
Communication specifications
Item
Interface
Protocol
Isolation status
Number of connected units
Transmission distance
Transmission speed
Data length
Transmission format Parity
Stop bit
Communication method
Synchronous system
Ending resistance
Specifications
Conforming to RS485
MEWTOCOL/MODBUS (RTU) (selectable with setting mode)
Isolated with the internal circuit
99 (max.)*2, *3
1200m*1
38400/19200/9600/4800/2400 bps (selectable with setting mode)
8bit/7bit (selectable with setting mode)*4
Not available/Odd number/Even number (selectable with setting mode)
1 bit (fixed)
Half-duplex
Synchronous communication method
Approx. 120Ω (built-in)
*1. Please check with the actual devices when some commercial devices with RS485 interface are connected. The number of connected devices, transmission distance,
transmission speed may be different according to using transmission line.
*2. For RS485 converter on the computer side, we recommend SI-35 and SI-35USB (from LINE EYE Co., Ltd.).
*3. When using SI-35, SI-35USB or our PLC (which can be connected up to 99 units), up to 99 Eco-POWER METER can be connected. In case using this system with the
other devices, up to 31 Eco-POWER METER can be connected.
*4. With MODBUS (RTU) protocol, it works only with data length (8bit/7bit).
* Modbus Protocol is a communications protocol developed for PLCs by Modicon Inc.
*For RS485 communication and recommended cable, please refer to “PRECAUTIONS IN USING Eco-POWER METER”.
Memory specifications of main unit (KW1M-H only)
Item
Specifications
Save cycle
File type 1
(instantaneous value)*5
File type 2
(difference value)*5
60 min. (on the hour) (fixed)
Save data
Save data amount
Save cycle
Save data
Save data amount
Save cycle
File type 3
(instantaneous value detail)*5
Save data
Save data amount
Main unit display
Calendar timer function
Content of battery backup/Battery life*6
Instantaneous value: Integrated electric power, Instantaneous electric power, Current, Voltage, Power factor,
Frequency, Pulse count value
24 records per file (max. approx. 1.5 years worth of data)
60 min. (on the hour) (fixed)
Difference value: Integrated electric power, Pulse count value
24 records per file (max. approx. 1.5 years worth of data)
Select among 1 min, 5 min, 10 min, 15 min, 30 min, or 60 min.
Saved timing:
When 1 min is selected: starts immediately after power is turned on
When 5 min is selected: 00, 05, 10, 15, 20, 25, 30... min after the hour
When 10 min is selected: 00, 10, 20, 30, 40, 50 min after the hour
When 15 min is selected: 00, 15, 30, 45 min after the hour
When 60 min is selected: 00 min after the hour
Integrated electric power, Instantaneous electric power, Current, Voltage, Power factor, Frequency,
Pulse count value
Max. 7,200 records, Approx. 5 days (when save cycle is 1 min.)
Integrated electric power by month (latest data covering 1.5 year period)/Integrated electric power by day (latest
data covering 1 month period)/Integrated electric power by hour (latest data covering 24 hours period)
Time accuracy; monthly accuracy: ±240 sec. (at –10°
C)/monthly accuracy: ±70 sec. (at 25°
C)/
monthly accuracy: ±240 sec. (at 50°
C)
Time measurement and log data retained/Approx. 2 years (at ambient temperature 25°
C) (During discontinuity)
*5. In file types 1, 2, and 3, whether or not writing on SD card is conducted can be selected by each respective setting mode.
*6. When the remaining battery level is low, the “BATT” display flashes. Replace the battery according to the battery replacement procedure. In addition, when the temperature
of the main unit is high, the battery life decreases.
External memory specifications (KW1M-H only)
Item
Support media
Supported format standards
Specifications
SD card*7
Compliant with SD and SDHC standards*8
*7. Operation verified maker: Panasonic Corporation
(SD/SDHC memory card: 2 GB, 4 GB, 8 GB)
*8. To format SD cards, please download and use the formatting software available on the Panasonic website.
[Panasonic website → Customer support → SD/SDHC card page → Software download list] http://panasonic.jp/support/sd_w/download
The file system on a SD card that was formatted using standard PC software does not comply with the SD card standard.
All Rights Reserved © COPYRIGHT Panasonic Electric Works Co., Ltd.
KW1M/KW1M-H Eco-POWER METER (AKW1)
DIMENSIONS (mm inch)
The CAD data of the products with a
CAD Data
mark can be downloaded from: http://panasonic-electric-works.net/ac
Tolerance: ±1.0 ±.039
KW1M Standard type: AKW1110 and AKW1111
KW1M-H SD card type: AKW1121
CAD Data
Mounting hole dimensions (1:2)
67±0.5
2.638±.020
• AKW1111/AKW1121
75
2.953
67
2.638
39.1
1.539
1±0.5
.039±.020
Terminal cover
(transparent)
6
.236
Connectors for current
transformer (CT)
• AKW1110
11 11
1±0.5
.039±.020
.433 .433
67.8
2.669
1.1±0.5
.043±.020
90
3.543
82
3.228
18.2
.717
82±0.5
3.228±.020
2-5 .197 dia.
(Mounting hole)
2×M4 .157
SD card
throttle*
M3 .118 (Fastening torque: 0.5 to 0.6 N·m)
39.1
1.539
1±0.5
.039±.020
50
1.969
47
1.850
25.1
.988
8
.315
R1 .039
AKW1110/1121
Terminal cover
(transparent)
1±0.5
.039±.020
11
.433
AKW1111
67.8
2.669
71
2.795
60
2.362
58
2.283
18.2
.717
35.4
1.394
Connectors for current
transformer (CT)
*SD card throttle only applies to SD card type KW1M-H.
(54*)
(2.126*)
(55*)
(2.165*)
*When installing DIN rail
TERMINAL ARRANGEMENT AND WIRING DIAGRAMS
Terminal wiring
Be sure to wire correctly according to the terminal arrangement and wiring diagrams. After completing wiring, be sure to attach the
terminal cover for safety reasons.
Terminal arrangement
• AKW1110
Function
Operating
power supply
E
IOP{} qw
Terminal No.
Function
L
N
Q
W
E
I
O
P
+
−
E
RS485
P1
P0
P2
R
T
Y
U*1
{
}
q*1
w*1
+
−
Pulse output
N.C.
Measured
voltage input
RS485 Pulse output
N.C.
N.C.
*1. U, q and w terminals are connected internal to analog input circuit.
Please do not use for wiring with daisy chain.
QWERTYU
P1 P0 P2
Operating Measured
power supply voltage input
RS485 Pulse output Pulse input
E
• AKW1111
UIOP{}q
Function
Operating
power supply
Measured
voltage input
Screw
L
N
P1
P0
P2
P3
M3.5
“+/−” screw
Terminal No.
Screw
Function
Q
U
W
I
+
−
E
R
T
Y
O
P
{
}
q
E
+
−
+
−
M3
“+/−” screw
RS485
Pulse output
Pulse input
QWERTY
P1 P0 P2 P3
Operating Measured
power supply voltage input
All Rights Reserved © COPYRIGHT Panasonic Electric Works Co., Ltd.
KW1M/KW1M-H Eco-POWER METER (AKW1)
RS485 Pulse output Pulse input
E
• AKW1121
IOP{} qw
Function
Terminal No.
Q
W
E
I
O
P
+
−
E
P1
P0
P2
P3
R
T
Y
U
{
}
q
w
+
−
+
−
N.C.
Measured
voltage input
Function
L
N
Operating
power supply
RS485
Pulse output
Pulse input
QWERTYU
P1 P0 P2 P3
Operating
power supply
Measured
voltage input
The input voltage to each terminal is as follows. (AKW1111)
Terminal
Phase and wire system
Between terminals
Operating power supply
Single-phase two-wire
Single-phase two-wire
Single-phase three-wire
Three-phase three-wire
Three-phase four-wire
Q-W
E-R
E-R-T
E-R-T
E-R-T-Y
Measured voltage input
Input voltage
AKW1111
100 to 240VAC (100-240V~) (Line voltage)
0 to 440VAC (0-440V~) (Line voltage)
0 to 220VAC (0-220V~: 3W) (Phase voltage)
0 to 440VAC (0-440V 3~) (Line voltage)
0 to 254VAC (0-254V 3N~) (Phase voltage)
The input voltage to each terminal is as follows. (AKW1110 and AKW1121)
Terminal
Phase and wire system
Between terminals
Operating power supply
Single-phase two-wire
Single-phase two-wire
Single-phase three-wire
Three-phase three-wire
Three-phase four-wire
Q-W
R-T
R-T-Y
R-T-Y
R-T-Y-U
Measured voltage input
Input voltage
AKW1110
AKW1121
100 to 240VAC (100-240V~) (Line voltage)
0 to 220VAC (0-220V~) (Line voltage)
0 to 440VAC (0-440V~) (Line voltage)
0 to 110VAC (0-110V~: 3W) (Phase voltage) 0 to 220VAC (0-220V~: 3W) (Phase voltage)
0 to 220VAC (0-220V 3~) (Line voltage)
0 to 440VAC (0-440V 3~) (Line voltage)
—
0 to 254VAC (0-254V 3N~) (Phase voltage)
Wiring diagrams
• AKW1110
Measure load of 100 to 200VAC system
• Single-phase two-wire system
• Single-phase three-wire system/Three-phase three-wire system
*One CT is required.
+
–
8
9
*Two CTs are required.
Pulse output
RS485
E
10
+
–
11
12
RS485
13 14
*1 *1
0.1A
30VDC
1
2
3
4
*1
Power 1
supply
side 2
Operating power supply
100 to 240VAC
50/60Hz
–
8
9
Pulse output
E
10
5
P0
6
7
*1 *1
Measured
voltage input
+
–
11
12
13 14
*2 *2
0.1A
30VDC
CT1
N.C.
P1
+
1
2
3
4
CT1 CT2
5
6
N.C.
*2
*Do not connect to CT2 and CT3.
CT1
Power R R 1
supply N S 2
side T T 3
Load side
K
L
Direction of CT
Operating power supply
100 to 240VAC
50/60Hz
P1
P0
P2
7
*2
Measured
voltage input
*Do not connect to CT3.
CT1
Load side
CT2
K
L
Direction of CT
*1. Do not wire to E, Y, U, q, w terminal. They are connected internal.
*2. Do not wire to E, U, q, w terminal. They are connected internal.
When measuring a load with exceed rated input voltage
The voltage transformer (VT) is required when you measure a load with exceed rated input voltage (220 V AC system).
Use commercial VT, those secondary rating is 110 V.
• Single-phase two-wire system
Eco-POWER METER (Secondary side)
• Single-phase three-wire system/
Three-phase three-wire system
Eco-POWER METER (Secondary side)
RT
RTY
VT
VT
Power 1
supply
side 2
(Primary side)
Load side
Power 1 R R
supply 2 N S
side 3 T T
(Primary side)
Load side
*Grounding the secondary side of voltage transformer (VT) and current transformer (CT) is not necessary with low voltage circuit.
All Rights Reserved © COPYRIGHT Panasonic Electric Works Co., Ltd.
KW1M/KW1M-H Eco-POWER METER (AKW1)
• AKW1111
Measure load of 100 to 200 VAC and 400 VAC system
• Single-phase two-wire system
• Single-phase three-wire system/Three-phase three-wire system
*One CT is required.
*Two CTs are required.
RS485
+
–
7
8
Pulse output Pulse input
E
9
RS485
+
–
+
–
+
–
10
11
12
13
7
8
5
*1
6
*1
0.1A
30VDC
1
2
3
P1
Power 1
supply
side 2
P0
1
2
–
+
–
11
12
13
5
6
*2
3
CT1
Power R R 1
supply N S 2
side T T 3
Load side
L
K
4
P1
*Do not connect to CT2 and CT3.
Measured
voltage input
+
10
0.1A
30VDC
CT1
4
Operating power supply
100 to 240VAC
50/60Hz
Pulse output Pulse input
E
9
Direction of CT
P0
CT1 CT2
P2
Operating power supply
100 to 240VAC
50/60Hz
*Do not connect to CT3.
Measured
voltage input
–
7
8
*1. Do not wire to T, Y terminal. They are connected internal.
*2. Do not wire to Y terminal. They are connected internal.
Pulse output Pulse input
E
9
+
–
+
–
10
11
12
13
5
6
0.1A
30VDC
1
2
3
R1
Power S 2
supply
side T 3
N4
CT1 CT2 CT3
4
P1
L
K
Direction of CT
*Three CTs are required.
+
Load side
CT2
• Three-phase four-wire system
RS485
CT1
P0
P2
P3
Operating power supply
100 to 240VAC
50/60Hz
Measured
voltage input CT1
CT2
Load side
CT3
L
K
Direction of CT
When measuring a load with exceed rated input voltage
The voltage transformer (VT) is required when you measure a load with exceed rated input voltage (440 V AC system).
Use commercial VT, those secondary rating is 110 V.
• Single-phase two-wire system
• Single-phase three-wire system/
Three-phase three-wire system
• Three-phase four-wire system
Eco-POWER METER (Secondary side)
Eco-POWER METER (Secondary side)
ER
Eco-POWER METER (Secondary side)
ERT
ERTY
VT
VT
(Primary side)
Power 1
supply
side 2
Power 1 R R
supply 2 N S
side 3 T T
Load side
VT
(Primary side)
(Primary side)
Power R
supply S
side T
N
Load side
Load side
*Grounding the secondary side of voltage transformer (VT) and current transformer (CT) is not necessary with low voltage circuit.
• AKW1121
Measure load of 100 to 200 VAC and 400 VAC system
• Single-phase two-wire system
• Single-phase three-wire system/Three-phase three-wire system
*One CT is required.
RS485
+
–
8
1
*Two CTs are required.
Pulse output Pulse input
RS485
+
–
+
–
+
–
9
E
10
11
12
13
14
8
2
3
4
1
0.1A
30VDC
N.C.
Power 1
supply
side 2
+
–
+
–
9
11
12
13
14
2
3
4
6
7
*2
0.1A
30VDC
CT1
5
P1
Pulse output Pulse input
E
10
P0
Operating power supply
100 to 240VAC
50/60Hz
6
7
*1 *1
CT1 CT2
5
N.C.
P1
*Do not connect to CT2 and CT3.
Measured
voltage input
CT1
Load side
L
K
Direction of CT
Power R R 1
supply N S 2
side T T 3
Operating power supply
100 to 240VAC
50/60Hz
P0
P2
Measured
voltage input
–
8
9
*1. Do not wire to Y, U terminal. They are connected internal.
*2. Do not wire to U terminal. They are connected internal.
Pulse output Pulse input
E
10
+
–
+
–
11
12
13
14
6
7
0.1A
30VDC
1
2
3
4
CT1 CT2 CT3
5
N.C.
P1
R1
Power S 2
supply
side T 3
N4
Operating power supply
100 to 240VAC
50/60Hz
P0
P2
L
Direction of CT
*Three CTs are required.
RS485
Load side
CT2
K
• Three-phase four-wire system
+
*Do not connect to CT3.
CT1
P3
Measured
voltage input
CT1
CT2
Load side
CT3
K
L
Direction of CT
All Rights Reserved © COPYRIGHT Panasonic Electric Works Co., Ltd.
KW1M/KW1M-H Eco-POWER METER (AKW1)
When measuring a load with exceed rated input voltage
The voltage transformer (VT) is required when you measure a load with exceed rated input voltage (440 V AC system).
Use commercial VT, those secondary rating is 110 V.
• Single-phase two-wire system
• Single-phase three-wire system/
Three-phase three-wire system
Eco-POWER METER (Secondary side)
Eco-POWER METER (Secondary side)
RT
Eco-POWER METER (Secondary side)
RTY
RTYU
VT
VT
Power 1
supply
side 2
• Three-phase four-wire system
(Primary side)
Power 1 R R
supply 2 N S
side 3 T T
Load side
VT
(Primary side)
Load side
(Primary side)
Power R
supply S
side T
N
Load side
*Grounding the secondary side of voltage transformer (VT) and current transformer (CT) is not necessary with low voltage circuit.
3.7mm dia.
6.6mm or less
3.2mm
• M3.5 screw: AKW1111
(1) Terminal fastening torque should be approx. 1.0 N·m. In case
of using a crimping terminal, with insulating sleeve applicable to
M3.5 screw. (Refer to the below.)
6.6mm or less
3.2mm dia.
5.8mm or less
5.8mm or less
Caution for Wiring
• M3 screw: AKW1110 and AKW1121
(1) Terminal fastening torque should be 0.5 to 0.6N·m. In case of
using a crimping terminal, use it with insulating sleeve applicable
to M3 screw. (Refer to the below.)
3.7mm
(2) To protect the device, it is necessary to install power switch and circuit breaker in operating power supply circuit. And this has no
built-in power switch, circuit breaker or fuse for measured voltage input parts. Therefore it is necessary to install them in the circuit
near main unit.
(3) We recommend a wire with the cross section of 0.75 to 1.25 mm2 for operating power supply line and measured voltage input line.
(4) Use fire resistant electrical wire (UL electrical wire, etc.)
CAUTIONS FOR SAFETY
Please use correctly only after you have thoroughly read “User’s Manual, Instruction Manual, and Catalog”.
All Rights Reserved © COPYRIGHT Panasonic Electric Works Co., Ltd.