KW4M Eco-POWER METER (DIN48) (AKW5)
Eco-POWER METER
makes energy management
easy for all your facilities
and machines!
KW4M
Eco-POWER METER (DIN48)
FEATURES
Compliance with RoHS Directive
• Electrical power measurement
function
Instantaneous electrical power,
integrated electrical energy, each phase
voltage and each phase current
• Hour meter function installed
Measuring the power distribution time of
loads possible
• Counter function installed
Supports pulse output devices including
flow meters
• Support for 400 V AC power
measurement (use with external
voltage transformer)
• Supports 4 types of dedicated
current transformer (CT) to cover wide
measuring range
• Supports Networking
- An RS485 communications port
comes standard
- Comes with MODBUS (RTU) and
easily connects to PLC
DIN48
IP66
PRODUCT TYPES
Main unit
Phase and wire system
Single-phase two-wire system
Single-phase three-wire system
Three-phase three-wire system
Operating power
supply
Measured voltage
input
100 to 240 VAC
Terminal type
Communication protocol
Model number
Screw terminal
M3.5 “+/−” screw (crimp terminal)
MEWTOCOL
MODBUS (RTU)
MEWTOCOL
MODBUS (RTU)
AKW5111
AKW5112
AKW5211
AKW5212
100/200 VAC
11-pins
Dedicated current transformer (CT)
Rated primary current
5A/50A (common)
100A
250A
400A
Model number
AKW4801C
AKW4802C
AKW4803C
AKW4804C
* When connectors are not necessary for trunk cables, cutting processing by users is necessary.
* Please order in accordance with the type of power distribution system you will be measuring.
(Even if you will be using a secondary 5A CT, you will need an AKW4801C.)
Tool and Software
Product name
KW Monitor*1
(Data collection software
for Eco-POWER METER)
KW Watcher
(Electric power monitoring
software)
Descriptions
Remark
For parameter settings, editing of measurement values, and monitoring, etc.
Please use in situations where Web Datalogger Unit (DLU)/Data Logger Light (DLL) and
Eco-POWER METER are used together.
For easy “visualization” of data collected in DLU or DLL
You can download from our website
(free of charge)*2
Notes: *1. KW Monitor only uses MEWTOCOL. You cannot use MODBUS (RTU) type (AKW5112, AKW5212) for communication.
*2. Customer registration is required to download data.
Other tool
Product name
KW4M Eco-POWER METER
User’s manual (PDF)
Descriptions
Detailed explanation of Eco-POWER METER usage
Remark
You can download from our website
(free of charge)*2
Options
Product name
Installation frame
Terminal protective cover
Mounting frame
Rubber gasket
Protective cover
DIN rail terminal socket
Rear terminal socket
11P cap
Mounting rail
Descriptions
Used for DIN48 size Main unit installation panel (For use when installation on the board is not possible)
Used for screw terminal type Cover for shielding terminals of the main unit
Supplied with a unit Used for mounting in a panel
Supplied with a unit Used for mounting in a panel
Used for protecting a front display (common to Timer/Counter)
For 11-pin type (surface mounting)
For 11-pin type (embedded mounting)
For 11-pin type (connectable directly with soldering)
DIN rail terminal socket fixing rail
All Rights Reserved © COPYRIGHT Panasonic Electric Works Co., Ltd.
Model No.
AKW4822
AKW4823
ATA4811
ATC18002
AQM4803
ATC180041
AT78051
ATA4861
ATA48011
KW4M Eco-POWER METER (DIN48) (AKW5)
Measurement items
Item
Unit
kW
Instantaneous electric power (Active)
Integrated electrical energy (Active)
Current
Voltage
Corresponding value
Hour meter
L1(CT1)-phase current
L2(CT2)-phase current
Voltage between 1-2
Voltage between 2-3
Yen
Dollars
Electricity
Euros
charge*
Yuan
No currency
Carbon dioxide (kg-CO2)
ON-time
OFF-time
Pulse input
kWh
MWh
A
A
V
V
JPY
$
EUR
CNY
CHG
CO2
h (Hour)
h (Hour)
Count
Data displayed range
0.00 to 9999.99
0.00 to 9999.99kWh to 10.00MWh to 9999.99MWh
9-digit display: 0.00 to 9999999.99 kWh
0.0 to 6000.0
0.0 to 6000.0
0.0 to 9999.9
0.0 to 9999.9
0 to 999999
0.0 to 99999.9
0.0 to 99999.9
0 to 999999
0 to 999999
0.0 to 999999
0.0 to 99999.9
0.0 to 99999.9
0 to 999999
* Eco-POWER METER is designed chiefly to manage saving energy.
It is neither intended nor can it be legally used for billing.
SPECIFICATIONS
Main unit
Item
Rated operating voltage
Rated frequency
Rated power consumption
Allowable operating voltage range
Allowable momentary power-off time
Ambient temperature
Ambient humidity
Breakdown voltage (initial)
Insulation resistance (initial)
Vibration resistance
Shock resistance
Display method
Power failure memory method
Protection
Weight
Specifications
100 to 120/200 to 240V AC
50/60Hz common
8VA (240V AC at 25°C)
85 to 132/170 to 264V AC (85% to 110% of rated operating voltage)
10ms
–10 to +50°C (–25°C to +70°C at storage)
30 to 85%RH (at 20°C non-condensing)
[Use as a Power meter]
• Insulated circuit (Between (1)-(2), (2)-(3), (1)-(3))
(1) Power terminal (1 (R), 2 (N, S), 3 (T))
Between the isolated circuits: 2000V for 1min
CT input terminal (CT1 (+), CT2 (+), CT1, 2 (–))
(2) RS485 terminal (+, –)
(3) Pulse output terminal (+, –)
• Outer edge (case)-all terminals
[Use as a Pulse counter]
• Insulated circuit (Between (1)-(2), (2)-(3), (1)-(3))
(1) Power terminal (1 (R), 2 (N))
Between the isolated circuits: 100MΩ or more
Pulse input terminal (CT1 (+), 0V)
(measured with 500V DC)
(2) RS485 terminal (+, –)
(3) Pulse output terminal (+, –)
• Outer edge (case)-all terminals
10 to 55Hz (1cycle/min) single amplitude: 0.75mm (1h on 3 axes)
Min. 294m/s2 (5 times on 3 axes)
LCD with backlight
Upper section: Green, 4-digit, 16-segment, Letter height: 6.5 mm
Lower section: Amber, 6-digit, 7-segment, Letter height: 7.5 mm
EEP-ROM (more than 100,000 overwrite)
IEC Standard IP66 (only front panel with rubber gasket)
Note: Mounted in a row, waterproofing property will be lost.
Approx. 140g (Screw terminal type), Approx. 130g (11-pin type)
All Rights Reserved © COPYRIGHT Panasonic Electric Works Co., Ltd.
KW4M Eco-POWER METER (DIN48) (AKW5)
Power input specifications *Will not operate simultaneously with pulse measurement mode.
Item
Phase and wire system
Rating
Allowance
Input
voltage
Allowable measurement voltage
VT ratio
Input
current
Primary side rating
CT ratio
Special
functions
Accuracy
(without
error in CT
and VT)
Cut-off current
Hour meter threshold current
Instantaneous electric power
Integrated electric power
Voltage
Indication Current
accuracy Electricity charge
Calculated CO2 value
Hour meter
Specifications
Single-phase two-wire system, Single-phase three-wire system, Three-phase three-wire system
Single-phase two-wire: 100 to 120/200 to 240V AC (common)
Single-phase three-wire: 100 to 120V AC
Three-phase three-wire: 200 to 240V AC
85% to 110% of rated input voltage
Single-phase two-wire: 85 to 132/170 to 264V AC (common)
Single-phase three-wire: 85 to 132V AC
Three-phase three-wire: 85 to 264V AC
1.00 to 99.99 (Set with setting mode)
*Voltage transformer (VT) is required when you measure a load with voltage over 200V system.
*Secondary current rating of commercial VT is 110V.
• 5A/50A/100A/250A/400A (Select with setting mode)
• 1 to 4000A (Set with setting mode)
*Accuracy coverage: 10 to 100% of rated current of CT
1 to 4000 (Set with setting mode)
*In case measuring CT of secondary rated current 5A.
1.0 to 50.0%F.S.
1.0 to 100.0%F.S.
±2.5% F.S. ±1 digit
(at 20°C, rated input, rated frequency, power factor 1)
*Accuracy coverage: 10 to 100% of rated current of CT
±0.01%+1 digit (at 20°C) (In case power on start or current energizing, ±0.01%+1s+1 digit)
±1.5% F.S./10°C+1 digit
(Range of –10 to 50°C based on 20°C for rated input power factor 1)
±1.5% F.S.+1 digit
(Frequency change ±5% based on rated frequency, for rated input power factor 1)
Temperature characteristics
Frequency characteristics
Pulse input specifications *Will not operate simultaneously with electrical power measurement mode.
Item
Specifications
Input mode
Max. counting speed
Addition (Fixed)
2kHz/30Hz (Select with setting mode)
Min. input signal width: 0.25ms (When selected 2kHz)/16.7ms (When selected 30Hz)
ON : OFF ratio = 1 : 1
Contact/No contact (open collector)
• Impedance when shorted: Max. 1kΩ
• Residual voltage when shorted: Max. 2V
• Impedance when open: Min. 100kΩ
HOLD (Over count)
6-digit (0 to 999999) (Selectable with setting mode)
Setting possible up to 3 digits after decimal point (Auto-setting)
0.001 to 100.000 (Selectable with setting mode)
CNT / l / kl / m3 (Selectable with setting mode)
(Count value does not change even if the unit setting is changed during counting.)
Pulse input
Input signal
Output mode
Number of digit
Pre-scale
setting
Decimal point
Range
Unit
Pulse output (transistor output) specifications
Item
Number of output point
Insulation method
Output type
Output capacity
Pulse width
ON state voltage drop
OFF state leakage current
Power measurement
Pulse output
unit
Pulse input measurement
Specifications
1 point
Optical coupler
Open collector
100mA 30V DC
Approx. 100ms*
1.5V or less
100µA or less
0.001/0.01/0.1/1/10/100kWh/Alarm (Selectable with setting mode)
HOLD (Over count)
* We recommend the setting of minimum unit for pulse output for measurement shown as below. Output pulse: 4 pulse or less per 1sec.
How to calculate: (Unit for pulse output : PL-P) > (Max. measurement power [kW]) / (3600[s] × 4 [pulse/s])
Notes: 1. Count errors may occur if pulse output unit is set so that 4 or more pulses are output per 1 second.
2. The connected counter or PLC may cause count errors if the OFF time of the pulse output unit is short.
All Rights Reserved © COPYRIGHT Panasonic Electric Works Co., Ltd.
KW4M Eco-POWER METER (DIN48) (AKW5)
Communication specifications
Item
Interface
Protocol
Isolation status
Number of connected units
Transmission distance
Transmission speed
Specifications
Conforming to RS485
MEWTOCOL/MODBUS (RTU) (different model)
Isolated with the internal circuit
99 (max.)*2, *3
1200m*1
38400/19200/9600/4800/2400bps (selectable with setting mode)
8 bit/7 bit (selectable with setting mode) (MEWTOCOL type)
8 bit (fixed)
(MODBUS type)
Not available/Odd number/Even number (selectable with setting mode)
1 bit (fixed)
Half-duplex
Synchronous communication method
Approx. 120Ω (built-in)*4
Data length
Transmission
format
Parity
Stop bit
Communication method
Synchronous system
Ending resistance
Notes: *1. Please check with the actual devices when some commercial devices with RS485 interface are connected.
The number of connected devices, transmission distance, transmission speed may be different according to using transmission line.
*2. For RS485 converter on the computer side, we recommend SI-35 (from LINE EYE Co., Ltd.).
*3. When using SI-35 or PLC from our company (which can be connected up to 99 units), up to 99 Eco-POWER METER can be connected. (However, 32 units (max.)
using connection with C-NET adapter) In case using this system with the other devices, up to 31 Eco-POWER METER can be connected.
*4. Change the sliding switch of main unit as a terminal station. (Factory setting; General side)
* MODBUS Protocol is a communications protocol developed for PLCs by Modicon Inc.
*For RS485 communication and recommended cable, please refer to “PRECAUTIONS IN USING Eco-POWER METER”.
PARTS NAMES
2
3
Panasonic EcoPOWER METER
MODE Lock
1 2 OP CT1
3 4
CT2
6
4
5
MODE
7
SET
TIME
COUNT
1
V
CHARGE
kW/kWh
A
Mode indicator (16-segment LCD)
Lock indicator
Illuminates when locked.
Mode indicator
Illuminates when setting a mode.
Output indicator
Illuminates during pulse output.
CT direction
Illuminates when the CT direction is correct and a
notification display
current flows that exceeds the set current value.
6 Value display
Displays the integrated electrical energy, instantaneous
(7-segment)
electrical power, current, voltage, electricity charge,
1
2
3
4
5
KW4M
8
9
7 MODE key
8 SET key
9 Select key
hour meter time, count, and all settings.
Used to move between different modes.
Used to make settings.
Changes the item displayed.
Used to move between modes.
All Rights Reserved © COPYRIGHT Panasonic Electric Works Co., Ltd.
KW4M Eco-POWER METER (DIN48) (AKW5)
DIMENSIONS (mm inch)
The CAD data of the products with a
CAD Data
mark can be downloaded from: http://panasonic-electric-works.net/ac
Tolerance: ±1.0 ±.039
CAD Data
Screw terminal type (AKW5111/AKW5112)
Pin type (AKW5211/AKW5212)
87.5
3.445
Panasonic
TIME
COUNT
V
CHARGE
kW/kWh
A
MODE Lock
1 2 OP CT1
3 4
CT2
MODE
SET
TIME
COUNT
V
CHARGE
KW4M
48
1.890
KW4M
48
1.890
81.9
3.224
Screw terminal: M3.5 .138
Panel cut-out dimensions
Panel mount diagram
Min. 80
Min. 3.150
Rubber gasket
(supplied)
(ATC18002)
45+0.6
0
1.772+.024
0
Mounting frame
(supplied)
(AT8-DA4)
Mounting screw
(attached to mounting frame)
73
2.874
Dimensions for flush mounting
(with adapter installed)
Pin type
Rubber gasket
ATC18002
(supplied)
Mounting frame for
flush mounting
AT8-DA4
11P cap
(supplied)
(AT8-DP11
sold separately)
Panel
50
1.969
45+0.6
0
1.772+.024
0
45+0.6
0
1.772+.024
0
Min. 80
Min. 3.150
kW/kWh
A
66 2.598
SET
(44.5)
(1.752)
MODE Lock
1 2 OP CT1
3 4
CT2
MODE
EcoPOWER METER
(44.5)
(1.752)
EcoPOWER METER
Panasonic
14.5
.571
5.5
.217
5.5
.217
A
Dimension A when ‘u’ products
are mounted in a row:
A = (48∗n–2.5)+0.6
0
Note: If the products are mounted in a row,
they lose their waterproofing properties.
Panel (thickness: 1 to 5.0mm)
104.5
4.114
1
.039
Dimensions for front panel installations
DIN rail terminal socket
11-pin type AT8-DF11K
(sold separately)
Device installation rail
AT8-DLA1
(sold separately)
112.9
4.445
All Rights Reserved © COPYRIGHT Panasonic Electric Works Co., Ltd.
KW4M Eco-POWER METER (DIN48) (AKW5)
TERMINAL ARRANGEMENT AND WIRING DIAGRAMS
Terminal type
Pin type
Screw terminal type
1, R, R
RS485 −
2, N, S
CT1 (k)/IN
3, T, T
CT1 (l), CT2 (l)
RS485 +
CT2 (k)
RS485 −
0V
Pulse output (+)
Pulse output (+)
Pulse output (−)
Pulse output (−)
CT1 (k)/IN
1, R, R
CT1 (l), CT2 (l)
2, N, S
CT2 (k)
3, T, T
0V
RS485 +
No.
1
2
3
4
5
6
7
8
9
10
11
Notes: 1. Be sure to wire correctly according to the terminal arrangement and wiring
diagrams.
2. A DIN rail terminal socket (AT8-DF11K) should be used for 11-pin type
Eco-POWER METER.
Caution for Wiring
(1) Terminal fastening torque should be approx. 1.0 N·m. In case
of using a crimping terminal, with insulating sleeve applicable to
M3.5 screw. (Refer to the below.)
3.7mm
6.6mm or less
Terminal arrangement
* Round terminals cannot be used in KW4M. Use Y shape terminals.
(2) To protect the device, it is necessary to install power switch
and circuit breaker in operating power supply circuit. Therefore it
is necessary to install them in the circuit near main unit.
(3) We recommend a wire with the cross section of 0.75 to 1.25
mm2 for operating power supply line and measured voltage input
line.
(4) Use fire resistant electrical wire (UL electrical wire, etc.)
Be sure to wire correctly according to the wiring
diagram. The input (applied) voltage to each pin
(terminal) is as follows.
Phase and
wire
Main unit type
Single-phase
two-wire
Single-phase
three-wire
Three-phase
three-wire
Pin type
Pin
(Terminal)
(1)-(2)
Screw terminal type (8)-(9)
Pin type
(1)-(2)-(3)
Screw terminal type (8)-(9)-(10)
Pin type
(1)-(2)-(3)
Screw terminal type (8)-(9)-(10)
Input (Applied) voltage
100 to 120/200 to 240VAC
(100 to 120/200 to 240V~)
100 to 120VAC
(100 to 120V~: 3W)
200 to 240VAC
(200 to 240V 3~)
Note: Please connect a breaker to the voltage input part for safety reasons and to
protect the device.
Power measurement
• Please connect a breaker to the voltage input part for safety reasons and to protect the device.
• After wiring, turn on the power once again (ON → OFF → ON).
1) When measuring load with 100 to 200VAC system
2) When measuring load with 400V or more system
• Single-phase two-wire system
* VT (Voltage transformer) is needed when you measure a load with voltage over
240VAC.
Use commercial VT, those secondary rating is 110V.
*One CT is required.
K
Power supply 1
side 2
CT1
k
l
L
K
CT1
k
l
L
Load
side
• Single-phase two-wire system
K
Power supply 1
side 2
56 7
6 7 8 9 10
11
1 2 3 4 5
Pin type
Screw terminal type
4
3
2
8
9
10
1 11
CT1
k
l
L
K
CT1
k
l
L
Load
side
VT
VT
• Single-phase three-wire system/Three-phase three-wire system
56 7
4
8
3
9
2
10
1 11
6 7 8 9 10
11
1 2 3 4 5
Pin type
Screw terminal type
*Two CTs are required.
K
Power supply
side
RR 1
NS 2
TT3
L
CT1
k l
CT2
k l
K
L
CT1
k l
CT2
k l
Load
side
• Single-phase three-wire system/Three-phase three-wire system
K
Power supply
side
56 7
4
3
2
8
9
10
1 11
Pin type
6 7 8 9 10
11
1 2 3 4 5
RR 1
NS 2
TT3
K
L
CT1
k l
CT2
k l
Load
side
VT
VT
Screw terminal type
L
CT1
k l
CT2
k l
56 7
4
8
3
9
2
10
1 11
6 7 8 9 10
11
1 2 3 4 5
Pin type
Screw terminal type
* Grounding the secondary side of voltage transformer (VT) and current transformer
(CT) is not necessary with low voltage circuit.